ABB DDA202AS630.3 DDA202 A S-63/0.3 is a 2-pole 63 A 300 mA Type A selective residual current device block designed for coordinated earth-fault protection with compatible ABB miniature circuit breakers.
£121.88
The ABB DDA202AS630.3, manufacturer type DDA202 A S-63/0.3, is a 2-pole Type A selective residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. As part of the ABB DDA200 RCD series, it combines Type A residual-current detection with an intentional tripping delay to support selectivity with downstream instantaneous residual-current protection devices.
The DDA202 A S-63/0.3 detects sinusoidal alternating and pulsating DC residual currents. Its selective operating characteristic helps coordinate protection by delaying operation relative to suitable downstream instantaneous devices, making it particularly useful in commercial and industrial distribution systems where continuity and discrimination between protective devices are important.
With a rated current of 63 A, rated residual operating current of 300 mA and a 2-pole configuration, the DDA202AS630.3 is designed for 230/400 V AC systems at 50–60 Hz. It can be combined with compatible ABB S200-series miniature circuit breakers to create a coordinated residual-current and overcurrent protection assembly.
Selective residual current devices incorporate an intentional tripping delay to help coordinate operation with downstream instantaneous protective devices. In a correctly designed installation, this allows a downstream device nearest to an earth fault to operate first, helping reduce unnecessary interruption to unaffected upstream circuits.
The ABB DDA202 A S-63/0.3 combines this selective behaviour with Type A detection for sinusoidal alternating and pulsating DC earth-fault currents. Its modular DDA200 construction allows combination with compatible ABB miniature circuit breakers, providing a practical solution for coordinated residual-current and overcurrent protection in commercial and industrial distribution systems.
| Series | DDA200 |
|---|---|
| SKU | DDA202AS630.3 |
| ABB order code | 2CSB202201R3630 |
| Product type | Selective residual current device block / RCD block |
| Residual-current type | Type A |
| Operating characteristic | Selective (S) |
| Number of poles | 2 |
| Rated current | 63 A |
| Rated residual operating current | 300 mA |
| Rated voltage | 230/400 V AC |
| Rated operational voltage | 230 V |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Rated frequency | 50–60 Hz |
| Power loss | 5 W |
| Surge-current resistance | 5 kA |
| Protection rating | IP2X |
| Operating ambient temperature | -25 to +55 °C |
| Standard | IEC/EN 61009 Annex G |
| Dimensions (W × H × D) | 70 × 93 × 69 mm |
| Weight | approx. 0.21 kg |
| EAN | 8012542799405 |
The ABB DDA202AS630.3 is a selective Type A RCD block used with compatible ABB miniature circuit breakers to provide residual-current protection in commercial and industrial electrical installations.
The ABB DDA202 A S-63/0.3 has a rated current of 63 A.
The DDA202 A S-63/0.3 has a rated residual operating current of 300 mA.
The selective S characteristic provides an intentional tripping delay that helps achieve selectivity with suitable downstream instantaneous residual-current devices.
As a Type A device, it is designed to respond to sinusoidal alternating residual currents and pulsating DC residual currents.
ABB DDA200 selective Type A RCD blocks provide coordinated residual-current protection for commercial and industrial distribution systems, combining Type A earth-fault detection with intentional tripping delay for improved selectivity.