2CSB202199R1400 ABB DDA202 A-40/0.03 110V RCD Block 2P 40 A 30 mA Type A

2CSB202199R1400 ABB DDA202 A-40/0.03 110V RCD Block 2P 40 A 30 mA Type A

ABB DDA202 A-40/0.03 110V is a 2-pole Type A residual current device block rated at 40 A with 30 mA sensitivity, a 110 V test voltage and a 230 V AC rated operational voltage.

SKU: 2CSB202199R1400Alt SKU: DDA202A400.03110VMPN: 2CSB202199R1400
Price
List Price £124.91 ex VAT
Your Price (ex VAT) Save 35%
£81.19 35% OFF
You save £43.72 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £81.19
Trade pricing is personalised to your account

Manufacturer Lead Time

£81.19

Why Choose the ABB DDA202 A-40/0.03 110V RCD Block?

The ABB DDA202 A-40/0.03 110V is a 2-pole Type A residual current device (RCD) block designed for assembly with compatible ABB miniature circuit breakers. Part of the ABB DDA200 RCD series, it combines a 40 A rated current with sensitive 30 mA residual-current protection for residential, commercial and industrial electrical installations.

Its Type A characteristic detects sinusoidal alternating residual currents and pulsating DC residual currents. This makes the DDA202 A-40/0.03 110V suitable for circuits supplying modern electrical and electronic equipment where pulsating DC earth leakage can occur, while its 30 mA sensitivity provides additional protection against direct contact as well as protection against indirect contact.

This special DDA200 version has a 110 V test voltage and is suitable for applications at 230 V AC. The modular design allows the RCD block to be combined with compatible ABB circuit breakers, creating a coordinated assembly that provides residual-current, overload and short-circuit protection.

Key Advantages

  • Reliable Type A residual-current protection for sinusoidal AC and pulsating DC residual currents.
  • 30 mA rated residual current for additional protection against electric shock.
  • 40 A rated current for compatible electrical distribution circuits.
  • Special version with a 110 V test voltage and suitability for 230 V applications.
  • 2-pole configuration for two-conductor circuit protection arrangements.
  • Designed for assembly with compatible ABB S200 series and S300P miniature circuit breakers.

Key Features

  • ABB DDA200 RCD series.
  • 2-pole Type A RCD block.
  • 40 A rated current.
  • 30 mA rated residual current.
  • 230 V AC rated operational voltage.
  • 110 V test voltage.
  • 50/60 Hz rated frequency.
  • 500 V rated insulation voltage.
  • 4 kV rated impulse withstand voltage.
  • IP2X degree of protection.

Type A 30 mA Protection for Modern Electrical Loads

Type A residual-current protection responds to sinusoidal alternating earth fault currents and pulsating direct residual currents. This capability makes the ABB DDA202 A-40/0.03 110V suitable for circuits containing electronic equipment where residual-current waveforms can differ from the purely sinusoidal currents addressed by Type AC devices.

The DDA200 RCD block is designed to be assembled with compatible ABB miniature circuit breakers to create combined residual-current and overcurrent protection. Its 30 mA sensitivity provides additional protection against direct contact, while the associated circuit breaker provides overload and short-circuit protection for the protected circuit.

Typical Applications

  • Residential electrical distribution systems.
  • Commercial building electrical installations.
  • Industrial electrical distribution boards.
  • Applications requiring a 110 V test circuit and 230 V operating voltage.
  • Circuits requiring 30 mA Type A residual-current protection.
  • Circuits supplying equipment containing electronic components.
  • Control panels and modular electrical distribution equipment.
  • Combined RCD and MCB protection assemblies using compatible ABB devices.

Technical Specifications

Series DDA200
SKU DDA202A400.03110V
Order code 2CSB202199R1400
EAN 8012542078937
Product type Residual current device (RCD) block
Residual-current type Type A
Number of poles 2
Rated current 40 A
Rated residual current 30 mA
Rated voltage 230 V AC
Rated operational voltage 230 V AC
Test voltage 110 V
Rated frequency 50/60 Hz
Rated insulation voltage 500 V
Rated impulse withstand voltage 4 kV
Residual-current waveform Sinusoidal AC and pulsating DC
Degree of protection IP2X
Power loss 3.2 W
Standard IEC 61009 Annex G
Operating ambient temperature -25 to +55 °C
Conductor connection capacity up to 25 mm²
Dimensions (W × H × D) 70 × 93 × 76 mm
Weight approx. 0.18 kg

Frequently Asked Questions

What is the ABB DDA202 A-40/0.03 110V used for?

The DDA202 A-40/0.03 110V is a 2-pole Type A RCD block designed for assembly with a compatible ABB miniature circuit breaker to provide 30 mA residual-current protection in residential, commercial and industrial electrical installations.

What is the rated current of the DDA202 A-40/0.03 110V?

The ABB DDA202 A-40/0.03 110V has a rated current of 40 A.

What residual-current sensitivity does this RCD block provide?

The device has a rated residual current of 30 mA, providing sensitive earth leakage detection and additional protection against direct contact.

What does the 110V designation mean on this DDA202 RCD block?

This special DDA200 version has a 110 V test voltage. The DDA202 A-40/0.03 110V itself has a rated operational voltage of 230 V AC, so the 110V designation should not be interpreted as its maximum circuit operating voltage.

Is the DDA202 A-40/0.03 110V a complete RCBO on its own?

No. The DDA202 A-40/0.03 110V is an RCD block designed to be assembled with a compatible ABB miniature circuit breaker, which provides the associated overload and short-circuit protection.

Trusted ABB Circuit Protection

ABB DDA200 residual current device blocks provide modular residual-current protection for residential, commercial and industrial electrical installations, combining with compatible ABB circuit breakers to create coordinated circuit protection assemblies.