ABB ST202M-D2 is a 2 A two-pole D-characteristic miniature circuit breaker with 15 kA IEC short-circuit breaking capacity and UL 1077 supplementary protection for industrial control and high-inrush electrical loads.
£61.65
The ABB ST202M-D2 is a high-performance two-pole miniature circuit breaker (MCB) designed to provide supplementary overcurrent and short-circuit protection in industrial, commercial and machine-building electrical systems. As part of the ABB System pro M compact ST200M series, it combines a D tripping characteristic with a 2 A rated current for dependable protection of circuits supplying equipment with high starting and inrush currents.
Designed for applications requiring UL 1077 supplementary protection, the ST202M-D2 provides simultaneous two-pole circuit protection in a compact DIN rail format. Its D tripping characteristic makes it particularly suitable for circuits supplying highly inductive equipment and other loads that can produce substantial transient currents during start-up.
With a rated current of 2 A, a two-pole configuration and an ultimate short-circuit breaking capacity of 15 kA at 400 V AC and 125 V DC according to IEC/EN 60947-2, the ST202M-D2 provides robust protection for industrial control and distribution applications. Its UL 1077 interrupting rating is 10 kA at 480Y/277 V AC and 125 V DC, supporting use in demanding supplementary protection applications.
Miniature circuit breakers such as the ABB ST202M-D2 automatically interrupt a circuit when excessive current caused by an overload or short circuit is detected. This helps protect conductors and connected electrical equipment while providing a convenient resettable protection device for industrial control, auxiliary and machine-building circuits.
The ST200M series is designed for demanding industrial applications where compact supplementary protection and recognised international standards are required. The D characteristic accommodates high transient starting currents without unnecessary operation, making the ST202M-D2 particularly suitable for circuits supplying transformers, inductive equipment and other loads with substantial inrush current.
Tick the specs you need, then view products that match.
| Certification | UL 1077 | |
|---|---|---|
| Series | System pro M compact ST200M | |
| ABB order code | 2CDS272334R0021 | |
| EAN | 4016779021067 | |
| Product type | Miniature circuit breaker (MCB) | |
| Product group | UL 489 / UL 1077 MCB | |
| Number of poles | 2 | |
| Number of protected poles | 2 | |
| Rated current | 2 A | |
| Tripping characteristic | D | |
| Rated operational voltage | 400 V AC according to IEC 60947-2 | |
| Rated insulation voltage | 440 V | |
| Rated impulse withstand voltage | 4 kV | |
| Rated ultimate short-circuit breaking capacity | 15 kA at 400 V AC / 125 V DC | |
| Rated service short-circuit breaking capacity | 11.2 kA at 400 V AC | |
| UL 1077 interrupting rating | 10 kA at 480Y/277 V AC / 125 V DC | |
| Rated frequency | 50 / 60 Hz | |
| Input voltage type | AC | |
| Energy limiting class | 3 | |
| Overvoltage category | III | |
| Standards | UL 1077, CSA 22.2 No. 235, IEC/EN 60947-2 | |
| Terminal type | Double clamp | |
| Rigid conductor capacity | up to 35 mm² | |
| Flexible conductor capacity | up to 25 mm² | |
| Mounting type | DIN rail | |
| Modular width | 2 modules | |
| Dimensions (W × H × D) | 35 × 88 × 69 mm | |
| Built-in depth | 69 mm | |
| Weight | approx. 0.23 kg |
The ST202M-D2 is a two-pole miniature circuit breaker designed for supplementary overcurrent and short-circuit protection in industrial control, machinery and other electrical circuits, particularly those supplying loads with high starting currents.
The ABB ST202M-D2 has a rated current of 2 A.
The D tripping characteristic is designed to accommodate high starting and inrush currents, making it suitable for transformers, highly inductive equipment and other loads that can draw substantial transient current during start-up.
The ST202M-D2 has an ultimate short-circuit breaking capacity of 15 kA at 400 V AC and 125 V DC according to IEC/EN 60947-2 and a UL 1077 interrupting rating of 10 kA at 480Y/277 V AC and 125 V DC.
The ST202M-D2 is designed in accordance with major supplementary circuit protection standards including UL 1077, CSA 22.2 No. 235 and IEC/EN 60947-2.
ABB System pro M compact miniature circuit breakers provide dependable supplementary circuit protection for industrial control, automation and machine-building applications, combining compact DIN rail installation with robust overload and short-circuit protection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.