2CDS200985R0044 ABB S3C-UA 110 Undervoltage Release 110 V AC/DC

2CDS200985R0044 ABB S3C-UA 110 Undervoltage Release 110 V AC/DC

ABB S3C-UA 110 is a 110 V AC/DC undervoltage release with positive-safety tripping and LED event indication for compatible ABB modular circuit protection devices.

SKU: 2CDS200985R0044Alt SKU: S3CUA110MPN: 2CDS200985R0044
Price
List Price £102.32 ex VAT
Your Price (ex VAT) Save 45%
£56.28 45% OFF
You save £46.04 per unit
Manufacturer Lead Time Estimated Delivery 12 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £56.28
Trade pricing is personalised to your account

Manufacturer Lead Time

£56.28

Why Choose the ABB S3C-UA 110 Undervoltage Release?

The ABB S3C-UA 110 is an undervoltage release designed for compatible ABB modular circuit protection devices. Operating at a rated voltage of 110 V AC/DC, it trips the associated protection device when the control voltage falls below the specified operating range, helping protect connected equipment during significant supply-voltage reductions.

The S3C-UA 110 provides positive-safety operation, meaning the associated protection device trips when the control voltage is disconnected. This operating principle also allows the accessory to be incorporated into appropriately designed emergency-stop circuits using an external control button.

An integrated LED indication function identifies when an undervoltage event has occurred. The S3C-UA family is suitable for compatible ABB MCBs, RCCBs, RCBOs and switch-disconnectors, with interface modules available for selected additional device ranges.

Key Advantages

  • 110 V AC/DC rated operation for AC or DC control circuits.
  • Automatically trips the associated device during excessive voltage reduction.
  • Positive-safety function trips the device if control voltage is disconnected.
  • Can support appropriately designed emergency-stop applications.
  • Integrated LED indication shows when an undervoltage event has occurred.
  • Compatible with a broad selection of ABB modular circuit protection equipment.

Key Features

  • ABB S3C-UA undervoltage release series.
  • 110 V AC/DC rated voltage.
  • 50–60 Hz AC operating frequency.
  • Release range between approximately 35% and 70% of rated voltage.
  • Power consumption of approximately 0.94 VA DC and 1.73 VA AC.
  • LED undervoltage-event indication.
  • IPXXB / IP2X protection degree.
  • Can be installed in any operating position.
  • Designed in accordance with IEC/EN 60947-1.
  • Conducted emissions compliant with CISPR 11 Class A.

Automatic Protection Against Loss of Control Voltage

An undervoltage release mechanically trips its associated protection device when the monitored control supply falls below an acceptable level. ABB specifies the S3C-UA operating region between approximately 70% and 35% of rated voltage, helping prevent continued operation under significant undervoltage conditions.

The ABB S3C-UA 110 also provides positive-safety behaviour by tripping when the control voltage is removed completely. Combined with its 110 V AC/DC rating and LED event indication, this makes it suitable for industrial control, distribution and appropriately designed emergency-stop circuits.

Typical Applications

  • Undervoltage protection circuits.
  • Emergency-stop control arrangements.
  • Electrical distribution boards.
  • Commercial and industrial switchboards.
  • Machinery and automation control panels.
  • Remote tripping based on loss of a 110 V AC/DC control supply.

Technical Specifications

Series S3C-UA
Order code 2CDS200985R0044
EAN 4053546159431
Product type Undervoltage release
Rated voltage 110 V AC/DC
Frequency 50–60 Hz
Release range 0.35–0.70 × Un
DC consumption approx. 0.94 VA
AC consumption approx. 1.73 VA
Terminal capacity 1 × 0.75–2.5 mm² or 2 × up to 1.5 mm² each
Tightening torque 0.8 Nm
Protection degree IPXXB / IP2X
Dimensions (H × D × W) 85 × 71.1 × 17.4 mm
Mounting position Any
Standard IEC/EN 60947-1
Conducted emissions CISPR 11 Class A compliant
Weight approx. 0.09 kg
Pack quantity 1 piece
Product group MCB Accessories

Frequently Asked Questions

What is the ABB S3C-UA 110 used for?

The S3C-UA 110 is an undervoltage release that trips a compatible ABB protection device when its control voltage falls below the specified operating range or is disconnected.

What voltage does the S3C-UA 110 operate at?

The ABB S3C-UA 110 has a rated voltage of 110 V AC/DC, with AC operation at 50–60 Hz.

At what voltage level does the S3C-UA 110 release?

ABB specifies the undervoltage release region between approximately 35% and 70% of the rated voltage.

Does the S3C-UA 110 provide undervoltage indication?

Yes. The S3C-UA series incorporates an LED function to indicate that an undervoltage event has occurred.

Can the S3C-UA 110 be used for emergency stopping?

Yes. Its positive-safety operating principle allows the S3C-UA 110 to be incorporated into an appropriately designed emergency-stop circuit using a suitable external control button.

Trusted ABB Modular Protection Accessories

ABB S3C-UA undervoltage releases provide automatic voltage-loss protection and positive-safety tripping for compatible modular protection devices, supporting dependable control and electrical distribution applications.