Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S751DR-E16 is a 16 A single-pole E-characteristic selective main circuit breaker with 25 kA ultimate breaking capacity at 230 V AC for coordinated electrical distribution protection.
£59.36
The ABB S751DR-E16 is a high-performance single-pole selective main circuit breaker (SMCB) designed to provide overload and short-circuit protection in electrical distribution systems where high continuity of supply and coordinated protection are important. Part of the ABB S750 DR series, it combines selective protection with a voltage-independent operating principle for dependable distribution applications.
The S751DR-E16 provides E selective tripping characteristics and is engineered to achieve total selectivity with downstream miniature circuit breakers while providing excellent selectivity with upstream protective devices. ABB's current-limiting selectivity principle helps localise electrical faults so that downstream protective devices can clear appropriate faults without unnecessarily disconnecting larger parts of the installation.
With a rated current of 16 A, a single-pole configuration and a rated ultimate short-circuit breaking capacity of 25 kA at 230 V AC, the S751DR-E16 is suitable for demanding power distribution installations. Its DIN-rail format provides straightforward integration into compatible distribution boards, while ABB order code 2CDH781010R0162 identifies this specific E-characteristic model.
Selective main circuit breakers such as the ABB S751DR-E16 are designed to coordinate with other protective devices in an electrical installation. Selectivity helps ensure that the protective device nearest a fault operates first, reducing unnecessary interruption to unaffected circuits and supporting improved continuity of electrical supply.
The ABB S750 DR series operates independently of the supply voltage and does not require a separate control circuit to open or close its contacts. Combined with ABB's current-limiting selectivity principle, this makes the range particularly suitable for energy distribution systems where dependable protection and high system availability are required.
| Series | S750 DR |
|---|---|
| ABB order code | 2CDH781010R0162 |
| Product type | Selective main circuit breaker (SMCB) |
| Number of poles | 1 |
| Rated current | 16 A |
| Tripping characteristic | E selective |
| Rated operational voltage | 230 V AC |
| Rated frequency | 50/60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA at 230 V AC |
| Rated service short-circuit breaking capacity (Ics) | 12.5 kA at 230 V AC |
| Rated insulation voltage (Ui) | 690 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Operating temperature | −25 to +55 °C |
| Pollution degree | 3 |
| Protection degree | IP20 / IP40 |
| Contact-position indication | Red ON / green OFF |
| Terminal type | Screw terminals |
| Tightening torque | 2.5–3 N·m |
| Power loss | 4.1 W per pole at rated operating conditions |
| Dimensions (H × W × D) | 130 × 27 × 92 mm |
| Weight | approx. 0.35 kg |
| Mounting type | DIN rail |
| Standard | IEC/EN 60947-2 |
The ABB S751DR-E16 is a selective main circuit breaker designed to provide overload and short-circuit protection while coordinating with other protective devices in electrical distribution systems.
The S751DR-E16 has a rated current of 16 A and uses a single-pole configuration.
The breaker has a rated ultimate short-circuit breaking capacity of 25 kA at 230 V AC and a rated service short-circuit breaking capacity of 12.5 kA.
The E selective characteristic is designed for coordinated protection, helping the S750 DR achieve selectivity with downstream miniature circuit breakers and other protective devices in the distribution system.
The S751DR-E16 is designed for DIN-rail mounting in compatible electrical distribution boards and uses screw terminals for electrical connections.
ABB S750 DR selective main circuit breakers provide coordinated, voltage-independent protection for electrical distribution systems where high availability, dependable fault protection and selectivity between protective devices are essential.
We use cookies