2CDA382799R0101 ABB M302P-D10 10 A 2-Pole Type D 25 kA Magnetic Circuit Breaker

2CDA382799R0101 ABB M302P-D10 10 A 2-Pole Type D 25 kA Magnetic Circuit Breaker

ABB M302P-D10 is a 10 A two-pole Type D magnetic-only circuit breaker from the M300P range with a 25 kA breaking-capacity class for dedicated short-circuit protection of industrial AC and DC electrical circuits.

SKU: 2CDA382799R0101Alt SKU: M302PD10MPN: 2CDA382799R0101
Price
List Price £99.07 ex VAT
Your Price (ex VAT) Save 45%
£54.49 45% OFF
You save £44.58 per unit
Manufacturer Lead Time Estimated Delivery 14 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £54.49
Trade pricing is personalised to your account

Manufacturer Lead Time

£54.49

Why Choose the ABB M302P-D10 Magnetic Circuit Breaker?

The ABB M302P-D10 is a compact two-pole magnetic-only circuit breaker designed to provide dedicated short-circuit protection for industrial electrical circuits. Part of ABB's M300P range within the System pro M compact® portfolio, it combines high fault-current performance with modular DIN-rail construction for industrial control, distribution and equipment-protection applications.

Featuring a Type D magnetic characteristic and a rated current of 10 A, the M302P-D10 is designed for circuits where comparatively high temporary inrush currents can occur during normal energisation. ABB specifies a rated instantaneous tripping current of 140 A for this current rating, while the magnetic-only operating principle allows overload protection to be coordinated separately where required.

The M302P-D10 combines a two-pole configuration with a 25 kA breaking-capacity class. The M300P range is suitable for DC applications, with two poles connected in series supporting operation up to 125 V DC with a 25 kA Icu rating. Its compact two-module construction makes it suitable for integration into industrial control panels and distribution assemblies.

Key Advantages

  • Magnetic-only short-circuit protection for coordinated industrial circuit protection.
  • 10 A rated current for industrial equipment, control and distribution circuits.
  • Two-pole configuration for simultaneous multi-conductor circuit protection.
  • Type D magnetic characteristic suitable for circuits with comparatively high inrush currents.
  • 25 kA breaking-capacity class for demanding industrial installations.
  • Compact two-module construction for straightforward DIN-rail installation.

Key Features

  • ABB M300P magnetic-only circuit breaker range.
  • 10 A rated current.
  • Two-pole configuration.
  • Type D magnetic characteristic.
  • 140 A rated instantaneous tripping current.
  • 25 kA breaking-capacity class.
  • 6 kV impulse withstand rating across the M300P platform.
  • Suitable for AC and DC industrial circuit-protection applications.
  • Two-pole series connection suitable for applications up to 125 V DC.
  • Compact modular construction for DIN-rail mounting.

Dedicated Magnetic Short-Circuit Protection for Industrial Circuits

Unlike a conventional thermal-magnetic miniature circuit breaker, the ABB M302P-D10 provides magnetic-only short-circuit protection. ABB specifies the M300P range for protection and control of circuits against short circuits, including protection applications involving long cable lengths in TN and IT systems. Where complete protection against overload is also required, a separate overload protection device must be provided.

The Type D magnetic characteristic accommodates comparatively high short-duration inrush currents during normal equipment energisation. Combined with its two-pole configuration, 25 kA breaking-capacity class and DC capability, the M302P-D10 provides a compact solution for industrial circuits requiring dedicated and separately coordinated short-circuit protection.

Typical Applications

  • Industrial electrical control panels.
  • Dedicated short-circuit protection circuits.
  • Industrial circuits with separately coordinated overload protection.
  • Long cable circuits in appropriately designed TN and IT systems.
  • Equipment and inductive loads with comparatively high temporary inrush currents.
  • AC and low-voltage DC industrial electrical systems.

Technical Specifications

Series M300P
Product family S200M / S300P MCB
ABB order code 2CDA382799R0101
Product type Magnetic-only circuit breaker
Protection function Short-circuit protection
Number of poles 2
Magnetic characteristic Type D
Rated current 10 A
Rated instantaneous tripping current 140 A
Breaking-capacity class 25 kA
DC capability Up to 125 V DC with two poles connected in series
DC ultimate short-circuit breaking capacity (Icu) 25 kA
Rated impulse withstand voltage 6 kV
Reference standard IEC/EN 60947-2
Mounting type DIN rail
Number of modules 2
Width approx. 35 mm
Weight approx. 0.248 kg

Frequently Asked Questions

What is the ABB M302P-D10 used for?

The ABB M302P-D10 is a two-pole magnetic-only circuit breaker designed to provide short-circuit protection for industrial electrical circuits, particularly where overload protection is coordinated separately.

What is the rated current of the ABB M302P-D10?

The M302P-D10 has a rated current of 10 A and a rated instantaneous magnetic tripping current of 140 A.

Does the ABB M302P-D10 provide thermal overload protection?

No. The M302P-D10 provides magnetic short-circuit protection only. ABB specifies that a separate protection device is required where complete protection against overload is also needed.

What is the breaking-capacity rating of the ABB M302P-D10?

The M302P-D10 belongs to ABB's M300P magnetic-only circuit breaker range with a 25 kA breaking-capacity class.

Can the ABB M302P-D10 be used on DC circuits?

Yes. The M300P range supports DC applications, and a two-pole device connected in series can be used up to 125 V DC with an ultimate short-circuit breaking capacity (Icu) of 25 kA.

Trusted ABB Industrial Circuit Protection

ABB M300P magnetic-only circuit breakers provide dedicated short-circuit protection for industrial electrical installations, combining high breaking performance, compact DIN-rail construction and Type D magnetic characteristics suited to coordinated protection schemes.