2CDA382799R0041 ABB M302P-D4 4 A 2-Pole Type D 25 kA Magnetic Circuit Breaker

2CDA382799R0041 ABB M302P-D4 4 A 2-Pole Type D 25 kA Magnetic Circuit Breaker

ABB M302P-D4 is a 4 A two-pole Type D magnetic-only circuit breaker from the M300P range providing high-performance short-circuit protection for industrial AC and DC electrical circuits where overload protection is coordinated separately.

SKU: 2CDA382799R0041Alt SKU: M302PD4MPN: 2CDA382799R0041
Price
List Price £118.83 ex VAT
Your Price (ex VAT) Save 45%
£65.36 45% OFF
You save £53.47 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £65.36
Trade pricing is personalised to your account

Manufacturer Lead Time

£65.36

Why Choose the ABB M302P-D4 Magnetic Circuit Breaker?

The ABB M302P-D4 is a compact two-pole magnetic-only circuit breaker designed to provide dedicated short-circuit protection for industrial electrical circuits. Part of ABB's M300P range within the System pro M compact® portfolio, it combines high fault-current performance with modular DIN-rail construction for industrial control, distribution and equipment-protection applications.

Featuring a Type D magnetic characteristic and a rated current of 4 A, the M302P-D4 is designed for circuits where comparatively high temporary inrush currents can occur during normal energisation. Its magnetic-only operating principle provides short-circuit protection without thermal overload protection, allowing overload protection to be coordinated separately where required.

The M302P-D4 combines a two-pole / two protected pole configuration with high breaking performance. ABB specifies an ultimate short-circuit breaking capacity (Icu) of 100 kA at 415 V AC and 25 kA at 125 V DC, together with a service short-circuit breaking capacity (Ics) of 12.5 kA at 440 V AC. Its compact 35 mm-wide construction occupies two DIN modules for efficient integration into industrial electrical assemblies.

Key Advantages

  • Magnetic-only short-circuit protection for coordinated industrial circuit protection.
  • 4 A rated current for equipment, control and distribution circuits.
  • Two-pole / two protected pole configuration for simultaneous multi-conductor protection.
  • Type D magnetic characteristic suitable for circuits with comparatively high inrush currents.
  • High AC and DC short-circuit breaking performance for demanding industrial installations.
  • Compact 35 mm two-module construction for DIN-rail installation.

Key Features

  • ABB M300P magnetic-only circuit breaker range.
  • 4 A rated current.
  • Two-pole / two protected pole configuration.
  • Type D magnetic characteristic.
  • 56 A rated instantaneous tripping current.
  • 100 kA Icu at 415 V AC.
  • 25 kA Icu at 125 V DC.
  • 6 kV rated impulse withstand voltage.
  • 500 V rated insulation voltage.
  • IP20 degree of protection.

Dedicated Magnetic Short-Circuit Protection for Industrial Circuits

Unlike a conventional thermal-magnetic miniature circuit breaker, the ABB M302P-D4 provides magnetic-only short-circuit protection. This allows short-circuit and sustained overload protection to be coordinated independently within an industrial electrical system, with a suitable separate protective device providing overload protection where required.

The Type D magnetic characteristic accommodates comparatively high short-duration inrush currents during normal equipment energisation. Combined with its two-pole configuration, high AC breaking performance and suitability for two-pole series-connected DC applications up to 125 V DC, the M302P-D4 provides a versatile solution for demanding industrial protection schemes.

Typical Applications

  • Industrial electrical control panels.
  • Dedicated short-circuit protection circuits.
  • Industrial circuits with separately coordinated overload protection.
  • Transformers and inductive electrical loads.
  • Equipment with comparatively high temporary inrush currents.
  • AC and low-voltage DC industrial electrical systems.

Technical Specifications

Series M300P
Product family S200M / S300P MCB
ABB order code 2CDA382799R0041
Product type Magnetic-only circuit breaker
Protection function Short-circuit protection
Number of poles 2
Number of protected poles 2
Magnetic characteristic Type D
Rated current 4 A
Rated instantaneous tripping current 56 A
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 100 kA
Service short-circuit breaking capacity (Ics) at 440 V AC 12.5 kA
Ultimate short-circuit breaking capacity (Icu) at 125 V DC 25 kA
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 6 kV
Rated frequency 50 / 60 Hz and DC
Reference standard IEC/EN 60947-2
Pollution degree 3
Degree of protection IP20
Terminal type Screw terminal
Tightening torque 2.8 N·m
Operating temperature -40 to +70 °C
Mounting type DIN rail
Number of modules 2
Dimensions (H × W × D) 88 × 35 × 69 mm
Weight approx. 0.248 kg

Frequently Asked Questions

What is the ABB M302P-D4 used for?

The ABB M302P-D4 is a two-pole magnetic-only circuit breaker designed to provide short-circuit protection for industrial electrical circuits, particularly where overload protection is coordinated separately.

What is the rated current of the ABB M302P-D4?

The M302P-D4 has a rated current of 4 A and a rated instantaneous magnetic tripping current of 56 A.

Does the ABB M302P-D4 provide thermal overload protection?

No. The M302P-D4 provides magnetic short-circuit protection rather than thermal overload protection. Where sustained overload protection is required, an appropriate separate protective device must be used.

What is the breaking capacity of the ABB M302P-D4?

ABB specifies an ultimate short-circuit breaking capacity (Icu) of 100 kA at 415 V AC and 25 kA at 125 V DC for the M302P-D4, with a service short-circuit breaking capacity (Ics) of 12.5 kA at 440 V AC.

Can the ABB M302P-D4 be used on DC circuits?

Yes. ABB's M300P range supports DC applications, and a two-pole device connected in series can be used up to 125 V DC with an Icu breaking capacity of 25 kA.