Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S802U-K50 is a 50 A two-pole Type K high-performance miniature circuit breaker with 50 kA breaking capacity at 240 V AC and UL 489 compliance for demanding industrial circuit protection.
£165.75
The ABB S802U-K50 is a robust two-pole high-performance miniature circuit breaker (MCB) designed to protect electrical circuits against overloads and short circuits in demanding industrial applications. Part of the ABB S800U high-performance circuit breaker series, it combines a 50 A rated current with a powerful 50 kA short-circuit breaking capacity and compliance with UL 489.
Featuring a Type K tripping characteristic, the S802U-K50 is particularly suitable for circuits containing equipment with elevated starting or inrush currents. Its thermal release provides effective overload protection, while the electromechanical release responds rapidly to short-circuit conditions, helping provide dependable protection for cables, conductors and connected equipment.
With a two-pole configuration, 50 A rated current and 240 V AC operational voltage, the S802U-K50 is engineered for industrial distribution and equipment applications requiring high fault-current interruption capability. Its S800U design and UL 489 certification also make it suitable for installations where recognised North American circuit-breaker standards are required.
High-performance circuit breakers such as the ABB S802U-K50 automatically disconnect electrical circuits when excessive current occurs. Its thermal release responds to sustained overload conditions, while its electromechanical short-circuit release provides rapid interruption when severe fault currents occur.
The S800U range is designed for industrial applications requiring high short-circuit interruption capability and compliance with international standards. The Type K characteristic makes the S802U-K50 particularly useful where normal equipment operation can produce elevated starting currents, while its 50 kA interruption capability provides robust protection in installations with substantial prospective fault currents.
Tick the specs you need, then view products that match.
| Certification | UL 489 | |
|---|---|---|
| Series | S800U | |
| ABB order code | 2CCS862017R0577 | |
| Product type | High-performance miniature circuit breaker (MCB) | |
| Rated current | 50 A | |
| Number of poles | 2 | |
| Number of protected poles | 2 | |
| Tripping characteristic | Type K | |
| Rated operational voltage | 240 V AC | |
| Rated voltage | 240 / 415 V AC | |
| Short-circuit breaking capacity | 50 kA at 240 V AC | |
| Standards | IEC/EN 60947-2, UL 489 | |
| Protection rating | IP20 | |
| Power loss | 4.3 W | |
| Terminal type | Screw | |
| Contact position indication | ON / OFF / TRIP | |
| Operating temperature | -25 to +60 °C | |
| Storage temperature | -40 to +70 °C | |
| Dimensions (H × W × D) | 95 × 54 × 82.5 mm | |
| Weight | approx. 0.49 kg |
The ABB S802U-K50 is used to protect industrial electrical circuits against overloads and short circuits, particularly where high breaking capacity and UL 489 compliance are required.
The circuit breaker has a rated current of 50 A.
The S802U-K50 provides a short-circuit breaking capacity of 50 kA at 240 V AC.
The Type K tripping characteristic is suited to circuits containing equipment that can experience elevated starting or inrush currents, helping reduce unwanted tripping while maintaining effective overload and short-circuit protection.
Yes. The S802U-K50 complies with UL 489 and also meets IEC/EN 60947-2 requirements for industrial circuit breakers.
ABB S800U high-performance circuit breakers provide dependable overload and short-circuit protection for demanding industrial electrical installations, combining high breaking capacity with UL 489 compliance and robust circuit protection technology.