ABB S802S-UCK10 is a 10 A two-pole UC-K high-performance miniature circuit breaker with a 50 kA breaking capacity and 500 V DC rated operational voltage for demanding industrial DC circuit protection.
£171.44
The ABB S802S-UCK10 is a high-performance 2-pole miniature circuit breaker (MCB) designed to provide reliable overload and short-circuit protection in demanding DC electrical installations. As part of the ABB S800 high-performance circuit breaker range, it combines a 10 A rated current, UC-K tripping characteristic and high 50 kA breaking capacity for applications requiring robust circuit protection.
The S802S-UCK10 uses proven circuit protection technology to safeguard conductors and connected equipment against overcurrent conditions. Its high breaking capacity and current-limiting performance make it particularly suitable for industrial DC distribution and control systems where prospective fault currents can be substantial.
With a rated current of 10 A, a UC-K tripping characteristic and a rated operational voltage of 500 V DC, the S802S-UCK10 provides dependable protection for demanding DC circuits. The two-pole DIN rail format, compact 54 mm width and robust construction enable straightforward installation within electrical switchboards and industrial control panels.
The ABB S802S-UCK10 protects electrical conductors and connected equipment against damaging overcurrent and short-circuit conditions. Its current-limiting operation helps restrict the energy released during a fault, reducing electrical and thermal stress on downstream equipment and installation components.
The UC-K characteristic and 500 V DC rating make the S802S-UCK10 particularly suitable for demanding DC distribution and industrial control applications. Combined with the S800 platform's high 50 kA breaking capacity, compact construction and dependable switching performance, it provides a robust protection solution for modern industrial electrical systems.
| Series | S800 / S802S |
|---|---|
| ABB order code | 2CCS862001R1427 |
| Product type | High-performance miniature circuit breaker (MCB) |
| Number of poles | 2 |
| Rated current | 10 A |
| Tripping characteristic | UC-K |
| Breaking capacity | 50 kA |
| Rated operational voltage | 500 V DC |
| Energy limiting class | 3 |
| Overvoltage category | III |
| Protection rating | IP20 |
| Terminal type | Screw terminal |
| Mounting type | DIN rail mounting |
| Standard | IEC/EN 60947-2 |
| Additional approval | UL 1077 |
| Dimensions (H × W × D) | 95 × 54 × 82.5 mm |
| Weight | approx. 0.49 kg |
The ABB S802S-UCK10 is a high-performance miniature circuit breaker designed to protect demanding DC electrical circuits against overcurrent and short-circuit faults.
The S802S-UCK10 has a rated current of 10 A and uses a UC-K tripping characteristic.
The S802S-UCK10 has a high 50 kA breaking capacity, making it suitable for demanding circuit protection applications where substantial prospective fault currents may occur.
The S802S-UCK10 has a rated operational voltage of 500 V DC, making it suitable for industrial DC distribution and control applications.
The S802S-UCK10 is designed for DIN rail mounting inside electrical switchboards, distribution equipment and industrial control panels and uses screw terminals for conductor connection.
ABB S800 high-performance miniature circuit breakers are engineered for demanding electrical protection applications, combining high breaking capacity, current-limiting performance and dependable circuit protection in a compact DIN rail mounted design.