ABB S801S-B6 is a single-pole 6 A Type B high-performance miniature circuit breaker with 50 kA ultimate short-circuit breaking capacity at 240/415 V AC for overload and short-circuit protection in demanding AC and DC applications.
£65.34
The ABB S801S-B6 is a single-pole, 6 A high-performance miniature circuit breaker with a Type B tripping characteristic, designed to protect electrical installations against overloads and short circuits where a high breaking capacity is required. Part of ABB's S800S range, it combines compact DIN-rail construction with powerful current-limiting performance for demanding commercial and industrial applications.
The S801S-B6 provides an ultimate short-circuit breaking capacity of 50 kA at 240/415 V AC, with additional ratings of 30 kA at 254/440 V AC, 6 kA at 400/690 V AC and 30 kA at 125 V DC. Its Type B characteristic provides sensitive magnetic tripping suited to circuits with relatively low normal inrush currents.
Protection is provided through a thermal tripping mechanism for overload conditions and an electromechanical tripping mechanism for short circuits. Fast arc extinction and current-limiting operation help reduce fault energy, while the interchangeable cage terminal, robust S800S construction and broad accessory range support reliable installation in professional distribution systems.
The ABB S800S platform is engineered for electrical installations where high prospective fault currents demand greater breaking performance than conventional miniature circuit breakers can provide. The S801S-B6 combines rapid electromagnetic fault interruption with effective current limitation and fast arc extinction, helping reduce the electrical and thermal stresses generated during a short circuit.
Its Type B characteristic provides sensitive magnetic operation for circuits where normal starting currents are relatively low, making it well suited to appropriate resistive, control and distribution loads. With AC and DC capability, interchangeable terminals and compatibility with ABB's extensive S800 accessory system, the S801S-B6 provides a versatile solution for professional circuit protection.
Tick the specs you need, then view products that match.
| Certification | UL 1077 | |
|---|---|---|
| Series | S800S | |
| Product group | S800 / S800P / S750 MCB | |
| ABB order code | 2CCS861001R0065 | |
| EAN / GTIN | 7612271408107 | |
| Product type | High-performance miniature circuit breaker | |
| Rated current | 6 A | |
| Number of poles | 1P | |
| Tripping characteristic | Type B | |
| Maximum operating voltage | Up to 400/690 V AC | |
| DC application | Up to 125 V DC for single-pole configuration | |
| Ultimate breaking capacity (Icu>) at 240/415 V AC | 50 kA | |
| Ultimate breaking capacity (Icu>) at 254/440 V AC | 30 kA | |
| Ultimate breaking capacity (Icu>) at 400/690 V AC | 6 kA | |
| Ultimate breaking capacity (Icu>) at 125 V DC | 30 kA | |
| UL 1077 interrupting rating at 240 V AC | 30 kA | |
| UL 1077 interrupting rating at 277 V AC | 14 kA | |
| UL 1077 interrupting rating at 347 V AC | 6 kA | |
| Overload protection | Thermal tripping mechanism | |
| Short-circuit protection | Electromechanical tripping mechanism | |
| Terminal type | Interchangeable cage terminal | |
| Terminal tightening torque | 3.5 Nm | |
| Power loss | 1.8 W per pole | |
| Mounting | DIN rail | |
| Protection rating | IP20 | |
| Standards | IEC/EN 60947-2, IEC/EN 60898-1, UL 1077 | |
| Dimensions (H × W × D) | 95 × 27 × 82.5 mm | |
| Product net weight | approx. 0.24 kg | |
| Pack quantity | 1 piece |
The ABB S801S-B6 is a single-pole high-performance miniature circuit breaker designed to protect electrical circuits against overload and short-circuit currents in demanding commercial and industrial installations.
The S801S-B6 has a rated current of 6 A and a Type B tripping characteristic, making it suitable for appropriate circuits with relatively low normal starting or inrush currents.
The S801S-B6 has an ultimate short-circuit breaking capacity of 50 kA at 240/415 V AC. Its available breaking capacity varies according to the applied operational voltage.
Yes. The single-pole S801S-B6 can be used at up to 125 V DC, where ABB specifies an ultimate short-circuit breaking capacity of 30 kA.
The S801S-B6 uses a thermal tripping mechanism for overload protection and an electromechanical tripping mechanism for short-circuit protection, while its current-limiting construction and fast arc extinction help reduce fault energy.
ABB S800S high-performance miniature circuit breakers combine high short-circuit breaking capacity, effective current limitation and robust construction, with the S801S-B6 providing dependable 6 A Type B protection for demanding single-pole electrical circuits.