Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MK-C16/0.03 is a 16 A 1P+N Type C RCBO with Type F 30 mA residual-current protection and 10 kA breaking capacity for ABB SMISSLINE TP plug-in distribution systems.
£169.16
The ABB FS401MK-C16/0.03 is a high-performance residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and earth leakage faults. As part of the ABB SMISSLINE TP plug-in system, it combines overcurrent and residual-current protection in a compact 1P+N protective device for residential, commercial and industrial electrical installations.
This RCBO has a rated current of 16 A, a Type C overcurrent tripping characteristic and 30 mA residual-current sensitivity. Its Type F residual-current characteristic provides protection against sinusoidal AC and pulsating DC residual currents and supports applications involving modern electronic and mixed-frequency loads, while providing increased resistance to unwanted tripping.
With a rated operational voltage of 240 V AC and a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS401MK-C16/0.03 provides robust circuit protection in a compact two-module format. Its plug-in construction enables straightforward integration with ABB SMISSLINE TP distribution systems, while DTI functionality assists with identification of residual-current tripping during inspection and fault finding.
The ABB FS401MK-C16/0.03 combines overload, short-circuit and residual-current protection in one compact device. Its Type F residual-current characteristic provides protection against sinusoidal alternating and pulsating direct residual currents and is suitable for applications where modern electronic equipment can introduce residual-current components at frequencies beyond the conventional mains frequency.
The FS401MK design provides increased resistance to unwanted tripping, helping achieve an effective balance between electrical safety and continuity of service. Combined with 30 mA residual-current sensitivity and ABB's SMISSLINE TP plug-in architecture, the FS401MK-C16/0.03 is suitable for residential, commercial and industrial circuits supplying resistive, inductive and electronically controlled loads.
| Series | FS401MK / SMISSLINE TP |
|---|---|
| ABB order code | 2CCG001700R0001 |
| EAN / GTIN | 7612271521691 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Rated current | 16 A |
| Number of poles | 1P+N / 2 poles total |
| Protected poles | 1 |
| Overcurrent tripping characteristic | Type C |
| Residual-current type | Type F |
| Rated residual current | 30 mA |
| Rated operational voltage | 240 V AC |
| Voltage type | AC |
| Rated frequency | 50/60 Hz |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Rated short-circuit breaking capacity | 10 kA according to EN 61009-1 |
| Breaking capacity according to IEC 60947-2 | 25 kA |
| Surge current resistance | 3 kA |
| Energy limiting class | 3 |
| Power loss | 2.7 W |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Operating temperature | -25 to 60 °C |
| Flexible conductor capacity | 0.75–25 mm² |
| Installation depth | 78 mm |
| Width | 2 modules / 36 mm |
| Weight | approx. 0.2 kg |
| Standards | IEC/EN 61009, EN 61009-1 |
| System | SMISSLINE TP plug-in system |
The FS401MK-C16/0.03 protects single-phase final circuits against overloads, short circuits and residual earth fault currents, with Type F protection providing increased resistance to unwanted tripping.
The ABB FS401MK-C16/0.03 has a rated current of 16 A and a Type C overcurrent tripping characteristic.
The FS401MK-C16/0.03 provides Type F residual-current protection with a rated residual operating current of 30 mA, making it suitable for circuits incorporating modern electronic as well as resistive and inductive loads.
The FS401MK-C16/0.03 has a rated short-circuit breaking capacity of 10 kA according to EN 61009-1 and a breaking capacity of 25 kA according to IEC 60947-2.
The ABB order code for the FS401MK-C16/0.03 is 2CCG001700R0001.
ABB SMISSLINE TP RCBOs combine residual-current and overcurrent protection with a flexible plug-in architecture, while FS401MK Type F variants provide enhanced continuity of service for circuits incorporating modern electronic, resistive and inductive loads.
We use cookies