Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB FS401MC130.03 (FS401M-C13/0.03) is a 13 A 1P+N C characteristic Type A RCBO with 30 mA residual current sensitivity, 240 V AC rating and 10 kA Icn breaking capacity for single-phase circuit protection in ABB SMISSLINE TP systems.
£124.02
The ABB FS401MC130.03, type code FS401M-C13/0.03, is a pluggable 1P+N residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and residual earth fault currents. As part of the ABB FS401M series for the SMISSLINE TP plug-in system, it combines overcurrent and residual current protection in one compact protective device for industrial and commercial electrical installations.
This RCBO has a 13 A rated current, C tripping characteristic and 30 mA Type A residual current sensitivity. Type A residual current protection responds to sinusoidal AC and pulsating DC earth fault currents, while the C characteristic is suited to circuits where moderate starting or inrush currents may occur.
With a rated operational voltage of 240 V AC, a 10 kA rated breaking capacity (Icn) and a 25 kA rated ultimate short-circuit breaking capacity (Icu), the FS401M-C13/0.03 provides robust combined protection in a compact two-module format. Its direct SMISSLINE TP plug-in connection supports efficient installation and flexible circuit configuration within compatible ABB distribution assemblies.
The ABB FS401M-C13/0.03 combines miniature circuit breaker and residual current protective functions in a single device. It protects a single-phase final circuit against overload and short-circuit currents while monitoring for residual currents caused by insulation faults, providing both circuit protection and protection against the effects of earth leakage.
Its Type A 30 mA residual current protection responds to sinusoidal AC and pulsating DC earth fault currents, while its 10 kA Icn breaking capacity provides robust short-circuit protection. The C characteristic accommodates moderate starting currents, and direct connection to the SMISSLINE TP plug-in system supports efficient installation, maintenance and flexible circuit configuration.
| Product group | SMISSLINE Plug-in System |
|---|---|
| Series | FS401M |
| Model / type code | FS401M-C13/0.03 |
| SKU | FS401MC130.03 |
| ABB order code | 2CCG001678R0001 |
| Product type | Residual current circuit breaker with overcurrent protection (RCBO) |
| Application | Single-phase final circuit protection |
| Pole configuration | 1P+N |
| Number of poles | 2 |
| Number of protected poles | 1 |
| Rated current | 13 A |
| Overcurrent tripping characteristic | C |
| Residual current type | Type A |
| Rated residual current | 30 mA |
| Rated operational voltage | 240 V AC |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 4 kV |
| Frequency | 50/60 Hz |
| Rated breaking capacity (Icn) | 10 kA |
| Rated ultimate short-circuit breaking capacity (Icu) | 25 kA |
| Rated service short-circuit breaking capacity (Ics) | 15 kA at 240 V AC |
| Rated residual breaking capacity | 10 kA |
| Standards | IEC/EN/DIN EN 61009-1, EN/DIN EN 61009-2-1 |
| Current limiting class | 3 |
| Residual current operation | Undelayed |
| Surge current capacity | 3 kA |
| Power loss | 2.3 W |
| Overvoltage category | III |
| Pollution degree | 2 |
| Protection rating | IP20 |
| Operating ambient temperature | −25 to +60 °C |
| Width | 2 modules / 36 mm |
| Height | 91 mm |
| Built-in depth | 78 mm |
| Connectable multi-wired conductor cross-section | 0.75–25 mm² |
| Installation system | ABB SMISSLINE TP plug-in system |
| EAN / GTIN | 7612271521479 |
| Product net weight | 0.2 kg |
| Pack unit | 1 piece |
The ABB FS401MC130.03 is a 1P+N RCBO for single-phase final circuits, combining overload, short-circuit and residual current protection in one pluggable device.
The FS401M-C13/0.03 has a rated current of 13 A and uses a C tripping characteristic.
It provides Type A residual current protection with a 30 mA sensitivity, responding to sinusoidal AC and pulsating DC earth fault currents.
The FS401M-C13/0.03 has a rated breaking capacity (Icn) of 10 kA and a rated ultimate short-circuit breaking capacity (Icu) of 25 kA.
It is designed for the ABB SMISSLINE TP plug-in system, enabling direct integration into compatible modular electrical distribution assemblies.
ABB FS401M RCBOs combine residual current and overcurrent protection with SMISSLINE TP plug-in technology, providing compact and dependable protection for single-phase final circuits where robust short-circuit protection, straightforward maintenance and flexible system configuration are required.
We use cookies