2CCG001675R0001 ABB FS401M-B32/0.03 RCBO 1P+N Type A 30mA 32A 10kA

2CCG001675R0001 ABB FS401M-B32/0.03 RCBO 1P+N Type A 30mA 32A 10kA

ABB FS401M-B32/0.03 is a 32 A 1P+N Type B RCBO with Type A 30 mA residual-current protection and 10 kA short-circuit capacity for ABB SMISSLINE TP plug-in distribution systems.

SKU: 2CCG001675R0001Alt SKU: FS401MB320.03MPN: 2CCG001675R0001
Price
List Price £207.83 ex VAT
Your Price (ex VAT) Save 35%
£135.09 35% OFF
You save £72.74 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £135.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£135.09

Why Choose the ABB FS401M-B32/0.03 RCBO?

The ABB FS401M-B32/0.03 is a high-performance residual current circuit breaker with overcurrent protection (RCBO) designed to protect single-phase final circuits against overloads, short circuits and earth leakage faults. As part of the ABB SMISSLINE TP plug-in system, it combines overcurrent and residual-current protection in a compact 1P+N protective device for residential, commercial and industrial electrical installations.

This RCBO has a rated current of 32 A, a Type B tripping characteristic and 30 mA residual-current sensitivity. Its Type A residual-current detection provides protection against sinusoidal AC and pulsating DC earth fault currents, while the DTI functionality assists with identification of residual-current tripping during inspection and fault finding.

With a 10 kA rated short-circuit breaking capacity according to EN 61009-1, the FS401M-B32/0.03 provides robust circuit protection in a compact two-module format. Its plug-in construction enables straightforward integration with compatible ABB SMISSLINE TP distribution systems, while its 32 A rating makes it suitable for higher-current single-phase final circuits.

Key Advantages

  • Combined overcurrent and residual-current protection in one compact RCBO.
  • 32 A rated current with Type B tripping characteristic.
  • 30 mA residual-current sensitivity for additional protection against electric shock.
  • Type A residual-current detection for sinusoidal AC and pulsating DC fault currents.
  • 10 kA rated short-circuit breaking capacity according to EN 61009-1.
  • Plug-in construction for efficient integration with the ABB SMISSLINE TP system.

Key Features

  • ABB FS401M / SMISSLINE TP RCBO series.
  • 1P+N configuration with one protected pole.
  • 32 A rated current.
  • Type B thermomagnetic tripping characteristic.
  • Type A residual-current protection.
  • 30 mA rated residual operating current.
  • 10 kA rated short-circuit capacity.
  • Compact two-module plug-in design for SMISSLINE TP systems.

Combined Overcurrent and Earth Leakage Protection

RCBOs such as the ABB FS401M-B32/0.03 combine miniature circuit breaker and residual-current protection functions in one device. This allows the protected circuit to be disconnected in response to overloads, short circuits or potentially hazardous residual currents, providing comprehensive protection for individual single-phase final circuits.

The FS401M series is designed for ABB's SMISSLINE TP plug-in distribution architecture. Its Type A residual-current detection responds to sinusoidal alternating and pulsating direct residual currents, while the 30 mA sensitivity provides additional protection against direct contact in suitable electrical installations.

Typical Applications

  • Single-phase final circuit protection.
  • Residential electrical distribution systems.
  • Commercial buildings and facilities.
  • Industrial electrical installations.
  • Higher-current equipment and general-purpose circuits.
  • ABB SMISSLINE TP plug-in distribution systems.

Technical Specifications

Series FS401M / SMISSLINE TP
ABB order code 2CCG001675R0001
EAN 7612271521448
Product type Residual current circuit breaker with overcurrent protection (RCBO)
Rated current 32 A
Number of poles 1P+N / 2 poles total
Protected poles 1
Tripping characteristic Type B
Residual-current type Type A
Rated residual current 30 mA
Voltage type AC
Rated short-circuit capacity 10 kA
Rated ultimate short-circuit breaking capacity at 240 V AC 15 kA
Rated service short-circuit breaking capacity at 240 V AC 7.5 kA
Rated residual breaking capacity 10 kA
Frequency 50/60 Hz
Energy limiting class 3
Overvoltage category III
Pollution degree 2
Protection rating IP20
Operating temperature -25 to 60 °C
Reference ambient temperature 30 °C
Power loss 5.6 W
Electrical endurance 10,000 cycles
Mechanical endurance 10,000 cycles
Dimensions (H × W × D) 91 × 36 × 78 mm
Width 2 modules
Weight approx. 0.2 kg
Standard EN 61009-1
System SMISSLINE TP plug-in system

Frequently Asked Questions

What is the ABB FS401M-B32/0.03 used for?

The FS401M-B32/0.03 protects single-phase final circuits against overloads, short circuits and residual earth leakage currents in residential, commercial and industrial installations.

What is the rated current of the FS401M-B32/0.03?

The ABB FS401M-B32/0.03 has a rated current of 32 A and a Type B tripping characteristic.

What residual-current sensitivity does this RCBO provide?

The FS401M-B32/0.03 has a rated residual operating current of 30 mA and uses Type A residual-current detection.

What is the breaking capacity of the FS401M-B32/0.03?

The FS401M-B32/0.03 has a rated short-circuit breaking capacity of 10 kA according to EN 61009-1.

What is the ABB order code for the FS401M-B32/0.03?

The ABB order code for the FS401M-B32/0.03 is 2CCG001675R0001.

Trusted ABB Circuit Protection

ABB SMISSLINE TP RCBOs combine residual-current and overcurrent protection with a flexible plug-in architecture, providing dependable circuit protection for residential, commercial and industrial electrical distribution systems.