1SDA107706R1 ABB XT4V 160 MA 52 Im=260...520 3P F F

1SDA107706R1 ABB XT4V 160 MA 52 Im=260…520 3P F F

ABB 1SDA107706R1 is a fixed three-pole SACE Tmax XT4V 160 moulded-case circuit breaker with a 52 A MA magnetic trip unit, front terminals, adjustable 260–520 A instantaneous protection and 150 kA ultimate short-circuit breaking capacity at 415 V AC.

SKU: 1SDA107706R1MPN: 1SDA107706R1
Price
List Price £1,432.20 ex VAT
Your Price (ex VAT) Save 25%
£1,074.15 25% OFF
You save £358.05 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,074.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,074.15

Why Choose the ABB 1SDA107706R1 XT4V 160 MA 52 Circuit Breaker?

The ABB 1SDA107706R1, designated XT4V 160 MA 52 Im=260...520 3p F F, is a three-pole ABB SACE Tmax XT4 moulded-case circuit breaker designed particularly for motor protection applications. It combines the compact XT4 frame with a 52 A MA magnetic-only trip unit, providing adjustable instantaneous short-circuit protection without a thermal overload protection function.

The MA release provides an adjustable magnetic trip threshold from 260–520 A, equivalent to approximately 5–10 × In. This makes the breaker particularly suitable for motor circuits where overload protection is provided separately and the MCCB is required to provide high-performance short-circuit protection while accommodating normal motor starting currents.

The 1SDA107706R1 uses ABB's XT4V high-breaking-capacity configuration, providing an ultimate short-circuit breaking capacity of 150 kA at 415 V AC. It is supplied as a complete three-pole breaker for fixed installation with front terminals, providing a compact solution for demanding industrial motor and distribution applications.

Key Advantages

  • Genuine ABB SACE Tmax XT4 moulded-case circuit breaker.
  • 52 A MA magnetic-only protection optimised for motor applications.
  • Adjustable instantaneous magnetic protection from 260–520 A.
  • High 150 kA ultimate short-circuit breaking capacity at 415 V AC.
  • Three-pole configuration for three-phase circuits.
  • Fixed mounting with front terminals for straightforward switchboard integration.
  • Well suited to motor circuits where overload protection is provided by a separate motor protection device.

Key Features

  • ABB SACE Tmax XT4V 160 frame.
  • MA magnetic trip unit.
  • Rated current: 52 A.
  • Instantaneous magnetic setting: 260–520 A.
  • Magnetic adjustment: approximately 5–10 × In.
  • Number of poles: 3.
  • Mounting: Fixed.
  • Main terminals: Front terminals.
  • Operating mechanism: Toggle.
  • Front degree of protection: IP20.
  • Ultimate breaking capacity: 150 kA at 415 V AC.

High-Performance Magnetic Protection for Motor Circuits

The MA magnetic release is designed for applications where instantaneous short-circuit protection is required without integral thermal overload protection. On the 1SDA107706R1, the magnetic threshold is adjustable from 260–520 A, allowing the trip level to be coordinated with motor starting characteristics while maintaining rapid protection against high fault currents.

The XT4V configuration provides particularly high short-circuit performance for a compact XT4 breaker, reaching 150 kA at 415 V AC and 50 kA at 690 V AC. In motor applications, the MA breaker is typically coordinated with separate overload protection and switching equipment to provide a complete motor control and protection solution.

Typical Applications

  • Three-phase electric motor protection.
  • Industrial motor control centres.
  • Pumps, fans, compressors and conveyor systems.
  • Machinery and production equipment.
  • Industrial low-voltage switchboards.
  • Motor circuits using separate overload protection.
  • Installations with high prospective short-circuit currents.
  • Fixed MCCB applications requiring adjustable magnetic protection.

Technical Specifications

Series SACE Tmax XT / Tmax XT 250 Range
Order code 1SDA107706R1
Product type Moulded-case circuit breaker (MCCB)
Application Motor protection
Frame XT4V 160
Trip unit MA
Protection technology Magnetic
Rated current 52 A
Instantaneous magnetic protection setting 260–520 A
Magnetic adjustment 5–10 × In
Number of poles 3
Mounting Fixed
Terminal arrangement Front terminals
Rated voltage 690 V
Ultimate short-circuit breaking capacity at 415 V AC 150 kA
Ultimate short-circuit breaking capacity at 690 V AC 50 kA
Power loss 4.7 W
Operating mechanism Toggle
Front degree of protection IP20
Integrated earth-fault protection No
Integrated motor operator No
Optional motor operator Yes
Complete device with protection unit Yes
EAN / GTIN 8015644103736
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA107706R1?

The 1SDA107706R1 is an ABB SACE Tmax XT4V 160 three-pole moulded-case circuit breaker with a 52 A MA magnetic trip unit, adjustable 260–520 A instantaneous protection, fixed mounting and front terminals.

What is the rated current of the ABB 1SDA107706R1?

The breaker has a rated current of 52 A. Its instantaneous magnetic protection can be adjusted from 260–520 A.

What does the MA trip unit provide?

The MA trip unit provides magnetic short-circuit protection and is particularly suited to motor applications. It does not provide conventional thermal overload protection, so appropriate separate overload protection should be used where required by the application.

What is the breaking capacity of the ABB XT4V 1SDA107706R1?

The XT4V configuration provides an ultimate short-circuit breaking capacity of 150 kA at 415 V AC and 50 kA at 690 V AC.

What does XT4V 160 MA 52 Im=260...520 3p F F mean?

XT4V 160 identifies the XT4 high-breaking-capacity frame, MA 52 identifies the 52 A magnetic protection unit, Im=260...520 specifies the adjustable instantaneous magnetic trip range, 3p denotes three poles, and F F identifies fixed mounting with front terminals.

Trusted ABB Motor Circuit Protection

ABB SACE Tmax XT moulded-case circuit breakers provide compact and configurable protection for industrial power systems, with the 1SDA107706R1 combining a 52 A MA magnetic release, adjustable 260–520 A instantaneous protection and 150 kA breaking capacity at 415 V AC for demanding three-phase motor applications.