1SDA107581R1 ABB XT6S 800 TMA 630-6300 4P Fixed MCCB InN=50%In

1SDA107581R1 ABB XT6S 800 TMA 630-6300 4P Fixed MCCB InN=50%In

ABB 1SDA107581R1 is a SACE Tmax XT6S 800 four-pole fixed moulded case circuit breaker with a 630 A TMA thermomagnetic trip unit, front terminals and a neutral rated at 50% of phase current.

SKU: 1SDA107581R1MPN: 1SDA107581R1
Price
List Price £2,660.72 ex VAT
Your Price (ex VAT) Save 25%
£1,995.54 25% OFF
You save £665.18 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,995.54
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,995.54

Why Choose the ABB XT6S 800 TMA 630-6300 4p F F InN=50%In?

The ABB 1SDA107581R1 is a high-performance SACE Tmax XT6S moulded case circuit breaker (MCCB) designed for reliable protection of low-voltage electrical distribution systems. This configuration combines the XT6S 800 frame with a 630 A TMA thermomagnetic trip unit, providing adjustable overload and instantaneous short-circuit protection for industrial, commercial and infrastructure installations.

The circuit breaker features a four-pole configuration with the neutral pole rated at 50% of the phase current. It is supplied in a fixed execution with front terminals, providing a practical arrangement for integration into low-voltage switchboards and distribution panels. The TMA release provides adjustable thermal overload protection together with magnetic instantaneous short-circuit protection.

With a rated current of 630 A, rated operational voltage up to 690 V AC and an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, the XT6S 1SDA107581R1 is engineered for demanding power-distribution applications. Its instantaneous short-circuit setting range of 3150–6300 A provides flexibility when coordinating protection within an electrical installation.

Key Advantages

  • High-performance ABB SACE Tmax XT6S moulded case circuit breaker.
  • 630 A rated current on the XT6 800 A frame platform.
  • TMA thermomagnetic trip unit for overload and instantaneous short-circuit protection.
  • Four-pole configuration with neutral rated at 50% of phase current.
  • 50 kA ultimate breaking capacity at 415 V AC.
  • Fixed mounting with front terminals for switchboard integration.

Key Features

  • ABB SACE Tmax XT6 series.
  • XT6S 800 frame.
  • 630 A rated current.
  • 690 V AC rated operational voltage.
  • TMA thermomagnetic release.
  • Adjustable thermal overload protection.
  • 3150–6300 A instantaneous short-circuit setting range.
  • 4-pole construction with 50% rated neutral.
  • Fixed circuit-breaker execution.
  • Front-terminal connection.

Reliable Protection for High-Current Distribution Systems

Moulded case circuit breakers such as the ABB SACE Tmax XT6 protect electrical distribution circuits, cables and connected equipment against overloads and short circuits. The TMA thermomagnetic release combines adjustable thermal overload protection with instantaneous magnetic short-circuit protection, providing dependable protection without requiring an electronic trip unit.

The four-pole construction of 1SDA107581R1 incorporates a neutral rated at 50% of the phase current, making it suitable for correctly engineered four-conductor distribution systems where a reduced neutral rating is appropriate. Combined with the XT6S platform's 50 kA breaking capacity at 415 V AC, the breaker provides robust protection for demanding industrial and commercial switchboards.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main and sub-distribution panels.
  • Transformer and plant protection systems.
  • Commercial building electrical distribution.
  • Industrial feeder and cable protection.
  • Four-conductor systems designed for a 50% rated neutral pole.

Technical Specifications

Series SACE Tmax XT
Order code 1SDA107581R1
Product type Moulded case circuit breaker (MCCB)
Frame size XT6
Frame rating 800 A
Rated current 630 A
Rated operational voltage 690 V AC
Rated frequency 50 / 60 Hz
Breaking-capacity version S
Ultimate short-circuit breaking capacity 50 kA at 415 V AC
Number of poles 4
Neutral rating 50% of phase current
Trip unit TMA
Trip-unit technology Thermomagnetic
Overload release setting 252–630 A
Instantaneous short-circuit setting 3150–6300 A
Mounting type Fixed
Terminal arrangement Front terminals
Main-circuit connection Bolt connection
Protection rating IP20
Motor operator Optional
EAN 8015644102340
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA107581R1 used for?

The ABB 1SDA107581R1 is a 630 A four-pole moulded case circuit breaker designed to provide overload and short-circuit protection in low-voltage electrical distribution systems.

What trip unit is fitted to the ABB 1SDA107581R1?

This circuit breaker uses a TMA thermomagnetic trip unit with adjustable thermal overload protection and an instantaneous magnetic short-circuit setting of 3150–6300 A.

What does InN=50%In mean on this XT6S circuit breaker?

It means the neutral pole is rated at 50% of the phase-current rating, providing a reduced-neutral configuration for suitable four-conductor electrical systems.

What is the breaking capacity of ABB 1SDA107581R1?

The XT6S configuration provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC.

How is the ABB XT6S 1SDA107581R1 installed?

This model is supplied as a four-pole fixed circuit breaker with front terminals and bolt-connected main-circuit connections for integration into compatible low-voltage switchboards.

Trusted by Electrical Professionals Worldwide

ABB SACE Tmax XT moulded case circuit breakers are widely used in industrial, commercial and infrastructure power-distribution systems, combining dependable circuit protection with flexible trip-unit technologies and comprehensive installation options.