1SDA104951R1 ABB YU-C XT5 W 220...240 V AC - 220...250 V DC Undervoltage Release

1SDA104951R1 ABB YU-C XT5 W 220…240 V AC – 220…250 V DC Undervoltage Release

ABB 1SDA104951R1 YU-C XT5 W is a wired 220…240 V AC / 220…250 V DC undervoltage release designed for compatible withdrawable ABB SACE Tmax XT5 circuit breakers.

SKU: 1SDA104951R1MPN: 1SDA104951R1
Price
List Price £170.71 ex VAT
Your Price (ex VAT) Save 25%
£128.03 25% OFF
You save £42.68 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £128.03
Trade pricing is personalised to your account

Manufacturer Lead Time

£128.03

Why Choose the ABB 1SDA104951R1 YU-C XT5 W 220...240 V AC - 220...250 V DC?

The ABB 1SDA104951R1 is a genuine wired undervoltage release designed for compatible ABB SACE Tmax XT5 moulded-case circuit breakers. Supplied as the YU-C XT5 W 220...240 V AC - 220...250 V DC, it is specifically designed for withdrawable XT5 circuit breakers and provides undervoltage-dependent opening of the breaker.

The YU-C release monitors its auxiliary supply and interacts directly with the circuit breaker operating mechanism. If the supply voltage falls sufficiently or is lost, the release causes the breaker to open. When the release is not adequately energised, circuit breaker closing is inhibited, making it useful in systems where the breaker must not remain closed or be reclosed without a healthy control supply.

Designed for 220...240 V AC and 220...250 V DC control circuits, the 1SDA104951R1 provides flexible AC/DC operation for the ABB SACE Tmax XT5 withdrawable platform. Its dedicated ABB design makes it suitable for industrial switchboards, automated power distribution systems and OEM assemblies requiring undervoltage release functionality.

Key Advantages

  • Genuine ABB SACE Tmax XT5 undervoltage release.
  • Designed specifically for withdrawable XT5 circuit breakers.
  • Supports 220...240 V AC control supplies.
  • Supports 220...250 V DC control supplies.
  • Provides automatic circuit breaker opening following sufficient control-voltage loss.
  • Inhibits breaker closing when the undervoltage release is not adequately energised.

Key Features

  • ABB SACE Tmax XT accessory range.
  • YU-C wired undervoltage release.
  • Designed for XT5 frame size.
  • Suitable for withdrawable (W) circuit breaker configurations.
  • 220...240 V AC rated control voltage.
  • 220...250 V DC rated control voltage.
  • Provides undervoltage-dependent circuit breaker opening.
  • Supports closing inhibition when adequate auxiliary voltage is unavailable.

How an ABB Undervoltage Release Controls Circuit Breaker Operation

An undervoltage release is energised by an auxiliary control supply and acts directly on the circuit breaker operating mechanism. If that supply falls below the release's operating threshold, the mechanism trips the circuit breaker. This functionality is useful where equipment should be disconnected following a significant reduction or complete loss of control voltage.

The ABB 1SDA104951R1 provides this functionality for compatible withdrawable Tmax XT5 circuit breakers. The YU-C release also prevents the breaker from being closed while its auxiliary supply is insufficient, helping ensure that the circuit breaker can only be closed when the required control voltage has been restored.

Typical Applications

  • ABB SACE Tmax XT5 withdrawable circuit breaker installations.
  • Switchboards requiring undervoltage-dependent circuit breaker opening.
  • Industrial power distribution and automation systems.
  • Control schemes requiring breaker closing inhibition after auxiliary-voltage loss.
  • Process and machinery installations using 220...240 V AC or 220...250 V DC control supplies.
  • OEM switchgear requiring a wired undervoltage release for withdrawable XT5 breakers.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA104951R1
Alternate catalogue number KXT5YUCW5
Product type Circuit breaker electrical accessory
Accessory type Undervoltage Release (UVR)
Product main type Accessories - Electrical and Aux Contacts
Release version YU-C wired
Frame size XT5
Circuit breaker version Withdrawable
Rated AC control voltage 220...240 V AC
Rated DC control voltage 220...250 V DC
Control voltage type AC/DC
Function Undervoltage release and closing inhibition
Standards / approvals IEC / UL
Reference standards IEC 60947-2 / UL 489
RoHS compliance EU Directive 2011/65/EU and amendment 2015/863
Product net weight 0.12 kg
GTIN / EAN 8015644070434

Frequently Asked Questions

What is the ABB 1SDA104951R1 used for?

The ABB 1SDA104951R1 is a wired undervoltage release for compatible ABB SACE Tmax XT5 withdrawable circuit breakers, providing circuit breaker opening when its auxiliary supply falls sufficiently and inhibiting closing when adequate control voltage is unavailable.

What voltage does the ABB 1SDA104951R1 support?

The YU-C undervoltage release is rated for 220...240 V AC and 220...250 V DC control supplies.

Which ABB circuit breaker configuration is compatible with the 1SDA104951R1?

The 1SDA104951R1 is specifically designed for compatible ABB SACE Tmax XT5 withdrawable circuit breakers.

What does YU-C mean on the ABB 1SDA104951R1?

YU identifies an undervoltage release, while YU-C identifies the wired version. It monitors its auxiliary supply and interacts with the breaker mechanism to provide undervoltage opening and closing inhibition.

What is the EAN for the ABB 1SDA104951R1?

The GTIN / EAN is 8015644070434 for the ABB 1SDA104951R1 YU-C XT5 W 220...240 V AC - 220...250 V DC undervoltage release.

Trusted ABB Circuit Breaker Accessories

ABB SACE Tmax XT electrical accessories are engineered to complement the company's moulded-case circuit breaker platform, providing integrated control, release and operating functions for industrial low-voltage power distribution systems.