1SDA101766R1 ABB XT7L M 800 Ekip Dip LS/I 800A 4P Circuit Breaker

1SDA101766R1 ABB XT7L M 800 Ekip Dip LS/I 800A 4P Circuit Breaker

ABB 1SDA101766R1 is an 800 A four-pole XT7L M fixed moulded case circuit breaker with front terminals, a stored-energy operating mechanism and an Ekip Dip LS/I electronic trip unit for overload and short-circuit protection.

SKU: 1SDA101766R1MPN: 1SDA101766R1
Price
List Price £6,314.87 ex VAT
Your Price (ex VAT) Save 25%
£4,736.15 25% OFF
You save £1,578.72 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £4,736.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£4,736.15

Why Choose the ABB XT7L M 800 Ekip Dip LS/I Circuit Breaker?

The ABB XT7L M 800 Ekip Dip LS/I, order code 1SDA101766R1, is a high-performance four-pole moulded case circuit breaker from the ABB SACE Tmax XT7 range, designed for protection and switching in demanding low-voltage power-distribution systems. This configuration combines an 800 A rated current with the dependable Ekip Dip LS/I electronic trip unit.

The Ekip Dip LS/I electronic trip unit provides long-time overload and short-circuit protection with adjustable electronic settings. ABB specifies an overload adjustment range from 0.4 to 1 × In for this electronic trip-unit family, allowing the 800 A breaker to be coordinated with cables, feeders and downstream equipment according to the requirements of the installation.

This XT7L M configuration is supplied as a fixed four-pole circuit breaker with front terminals and a stored-energy operating mechanism. The XT7L performance class provides 120 kA short-circuit breaking capacity, making this breaker particularly suitable for industrial switchboards, main distribution boards and high-current feeder circuits where very high prospective fault currents may be present.

Key Advantages

  • High-performance 800 A moulded case circuit breaker for demanding power-distribution applications.
  • Ekip Dip LS/I electronic trip unit for configurable overload and short-circuit protection.
  • Adjustable electronic overload protection from 0.4 to 1 × In.
  • XT7L 120 kA performance class for installations with very high prospective fault currents.
  • Four-pole fixed configuration for comprehensive switching and protection.
  • Front terminals for straightforward switchboard integration.
  • Stored-energy operating mechanism suitable for advanced operating and automation requirements.

Key Features

  • ABB SACE Tmax XT7 series.
  • 800 A rated current.
  • Ekip Dip LS/I solid-state electronic trip unit.
  • LS/I protection characteristic for overload and short-circuit protection.
  • 320–800 A overload adjustment range.
  • XT7L 120 kA performance class.
  • Four-pole construction.
  • Fixed mounting configuration.
  • Front terminal connections.
  • Stored-energy operating mechanism.

High-Performance Protection for Demanding Distribution Systems

Industrial low-voltage networks with high prospective fault currents require circuit breakers capable of safely interrupting severe short-circuit conditions while maintaining dependable overload protection. The ABB XT7L M combines an 800 A current rating with the XT7L 120 kA performance class, providing robust protection for demanding main distribution and feeder applications.

The Ekip Dip LS/I electronic trip unit provides adjustable protection for overload and short-circuit conditions without unnecessary complexity. Combined with the fixed four-pole construction, front terminals and stored-energy mechanism, this configuration offers a practical solution for high-current switchboards where dependable protection, switching performance and integration flexibility are required.

Typical Applications

  • Main low-voltage distribution boards.
  • Industrial switchboards and power-distribution systems.
  • High-current incomer and feeder protection.
  • Transformer secondary distribution systems.
  • Manufacturing and process-industry installations.
  • Infrastructure systems with very high prospective short-circuit currents.

Technical Specifications

Series SACE Tmax XT7
ABB order code 1SDA101766R1
Product type Moulded case circuit breaker
Frame size XT7M
Performance class XT7L
Rated current 800 A
Trip unit Ekip Dip LS/I
Protection characteristic LS/I
Overload adjustment 0.4–1 × In
Overload adjustment range 320–800 A
Poles 4
Mounting type Fixed
Terminal arrangement Front terminals
Operating mechanism Stored energy
Breaking capacity 120 kA
Release type Solid-state electronic release for AC applications
Standard IEC 60947-2
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA101766R1?

The ABB 1SDA101766R1 is an XT7L M fixed four-pole moulded case circuit breaker rated at 800 A and equipped with an Ekip Dip LS/I electronic trip unit.

What protection does the Ekip Dip LS/I trip unit provide?

The Ekip Dip LS/I is an electronic trip unit designed to provide adjustable overload and short-circuit protection for low-voltage distribution circuits.

What is the breaking capacity of the ABB XT7L M 800?

The XT7L configuration is ABB's 120 kA performance class, making it suitable for installations with very high prospective short-circuit currents.

How many poles does the ABB 1SDA101766R1 have?

The breaker has a four-pole configuration and is supplied as a fixed circuit breaker with front terminals.

Where is the ABB XT7L M 800 Ekip Dip LS/I typically used?

It is typically used in industrial switchboards, main distribution boards, transformer secondary systems and high-current feeder circuits requiring dependable electronic protection and high short-circuit interruption performance.

Trusted ABB Protection for Industrial Power Distribution

ABB SACE Tmax XT circuit breakers combine high short-circuit interruption performance with advanced electronic protection technology, providing dependable circuit protection for demanding industrial, commercial and infrastructure power-distribution systems.