ABB 1SDA101674R1 is an 800 A four-pole XT7S M fixed moulded case circuit breaker with front terminals and an Ekip Touch Measuring LSI electronic trip unit for advanced protection and electrical measurement.
£4,315.61
The ABB XT7S M 800 Ekip Touch Measuring LSI, order code 1SDA101674R1, is a high-performance four-pole moulded case circuit breaker from the ABB SACE Tmax XT7 range, designed for advanced protection, measurement and switching in demanding low-voltage electrical distribution systems. This configuration combines an 800 A rated current with the sophisticated Ekip Touch Measuring LSI electronic trip unit.
The Ekip Touch Measuring LSI trip unit provides long-time, short-time and instantaneous protection functions together with integrated electrical measurement capabilities. Its touchscreen interface supports convenient configuration and monitoring, allowing engineers to manage protection settings and obtain useful operating information from the electrical distribution system.
This XT7S M model is supplied as a fixed four-pole circuit breaker with front terminals and incorporates stored-energy and lever operating mechanisms. The XT7S performance class provides an ultimate short-circuit breaking capacity of 50 kA at 415 V AC, making the breaker suitable for industrial switchboards, main distribution boards and high-current feeder applications.
Moulded case circuit breakers such as the ABB XT7S M protect low-voltage electrical networks against overload and short-circuit conditions while providing dependable switching and isolation. The 800 A rating and 50 kA breaking capacity at 415 V AC make this breaker suitable for demanding industrial and infrastructure distribution systems.
The Ekip Touch Measuring LSI trip unit combines configurable electronic protection with integrated measurement capabilities. This allows protection settings to be coordinated with upstream and downstream devices while providing useful electrical data for monitoring system performance, supporting efficient operation and improved power-distribution management.
| Series | SACE Tmax XT7 |
|---|---|
| ABB order code | 1SDA101674R1 |
| EAN | 8056221017183 |
| Product type | Moulded case circuit breaker |
| Frame | XT7 M |
| Performance class | XT7S |
| Rated current | 800 A |
| Trip unit | Ekip Touch Measuring LSI |
| Protection functions | Long-time, short-time and instantaneous |
| Long-time protection setting | 0.4–1 × In |
| Instantaneous protection setting | 1–10 × In |
| Poles | 4 |
| Mounting type | Fixed |
| Terminal arrangement | Front terminals |
| Operating mechanism | Stored energy and lever operation |
| Ultimate breaking capacity at 415 V AC | 50 kA |
| Release type | Solid-state electronic release for AC applications |
| Measurement functionality | Integrated |
| ABB product group | T-Max XT 250 Range |
The ABB 1SDA101674R1 is an XT7S M fixed four-pole moulded case circuit breaker rated at 800 A and equipped with an Ekip Touch Measuring LSI electronic trip unit.
The trip unit provides long-time, short-time and instantaneous protection for overload and short-circuit conditions, together with integrated electrical measurement functionality.
This XT7S model has an ultimate short-circuit breaking capacity of 50 kA at 415 V AC.
The breaker has a four-pole configuration and is supplied in a fixed arrangement with front terminals.
It is typically used in industrial switchboards, main distribution boards, feeder circuits and other low-voltage systems requiring advanced electronic protection and integrated electrical measurement.
ABB SACE Tmax XT circuit breakers combine robust switching performance, advanced electronic protection and measurement capabilities to support dependable and efficient industrial, commercial and infrastructure power-distribution systems.