Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA101549R1 XT7L M 1600 is a 1600 A three-pole fixed moulded-case circuit breaker with front terminals and an Ekip G Hi-Touch LSIG electronic trip unit for advanced generator and low-voltage power distribution protection.
£10,031.06
The ABB 1SDA101549R1 is a high-performance SACE Tmax XT7L M moulded-case circuit breaker (MCCB) designed for generator, transformer, installation and demanding low-voltage power distribution protection. Rated at 1600 A, this three-pole circuit breaker combines ABB’s high-breaking-capacity XT7L platform with an advanced Ekip G Hi-Touch LSIG electronic trip unit.
The Ekip G Hi-Touch LSIG release provides sophisticated electronic protection for demanding electrical installations, combining long-time, short-time, instantaneous and ground-fault protection functions. Its generator-oriented protection capabilities make the breaker particularly suitable for generator switchboards, critical-power systems and industrial installations requiring configurable protection and high fault-interruption performance.
The XT7L M 1600 has a rated uninterrupted current of 1600 A, a rated operational voltage of up to 690 V AC and an L short-circuit performance level. It provides an ultimate and service short-circuit breaking capacity of 120 kA at 415 V AC, while its three-pole fixed construction with front terminals supports robust integration into high-current switchboards and distribution assemblies.
Generator-fed electrical systems can require specialised protection because their operating and short-circuit characteristics differ from conventional utility-fed networks. The ABB Ekip G Hi-Touch LSIG electronic trip unit provides advanced protection functions suited to generator and critical-power applications, helping protect electrical equipment against overloads, short circuits and ground faults while supporting coordinated operation within complex low-voltage systems.
Combining a 1600 A current rating with 120 kA Icu and Ics at 415 V AC, the 1SDA101549R1 delivers substantial interruption capability for demanding installations. Its Ekip G Hi-Touch LSIG release, fixed three-pole construction, front terminals and 20 kA short-time withstand rating make it a capable solution for generator switchboards, industrial power systems and critical high-current distribution circuits.
| Series | SACE Tmax XT |
|---|---|
| Frame | XT7 |
| Sub-type | XT7M |
| Order code / SKU | 1SDA101549R1 |
| ABB product group | T-Max XT 250 Range |
| Product type | Moulded-case circuit breaker (MCCB) |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Number of poles | 3 |
| Trip unit | Ekip G Hi-Touch LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and ground fault (LSIG) |
| Short-circuit performance level | L |
| Ultimate breaking capacity (Icu) at 415 V AC | 120 kA |
| Service breaking capacity (Ics) at 415 V AC | 120 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 50 kA |
| Service breaking capacity (Ics) at 690 V AC | 50 kA |
| Rated short-time withstand current (Icw) | 20 kA |
| Overload release adjustment range | 640–1600 A |
| Short-time delayed short-circuit adjustment range | 960–16000 A |
| Instantaneous short-circuit adjustment range | 2400–24000 A |
| Mounting configuration | Fixed |
| Terminal position | Front |
| Main circuit connection | Bolt connection |
| Motor operator | Optional |
| Degree of protection | IP20 |
| Power loss | 94 W per pole at rated operating conditions |
| Mechanical durability | 20,000 cycles |
| Standard | IEC 60947-2 |
| EAN | 8056221015936 |
| Application | Generator, transformer, installation and low-voltage power distribution protection |
The ABB 1SDA101549R1 is a 1600 A three-pole moulded-case circuit breaker equipped with an Ekip G Hi-Touch LSIG electronic trip unit for advanced generator, transformer, installation and low-voltage power distribution protection.
The XT7L M 1600 has a rated current and rated uninterrupted current of 1600 A, making it suitable for demanding high-current generator, industrial and critical-power applications.
The Ekip G Hi-Touch LSIG electronic trip unit provides long-time, short-time, instantaneous and ground-fault protection, commonly abbreviated as LSIG, with generator-oriented protection capabilities for demanding electrical systems.
The XT7L M 1600 provides an ultimate and service short-circuit breaking capacity of 120 kA at 415 V AC. At 690 V AC, its ultimate and service breaking capacities are 50 kA.
The 1SDA101549R1 is a fixed three-pole circuit breaker with front terminals and bolt-connected main circuit connections. An optional motor operator can be fitted where electrically operated switching is required.
ABB SACE Tmax XT moulded-case circuit breakers are widely used by electrical engineers, panel builders and industrial operators to provide advanced electronic protection, dependable switching and high-performance fault interruption in demanding low-voltage installations.