ABB 1SDA101474R1 XT7H M 800 is an 800 A three-pole fixed moulded-case circuit breaker with front terminals, a stored-energy operating mechanism and an Ekip G Dip LS/I electronic release for generator and low-voltage installation protection.
£2,541.89
The ABB 1SDA101474R1 is a high-performance SACE Tmax XT7H M moulded-case circuit breaker (MCCB) specifically configured for generator and installation protection in demanding low-voltage AC systems. Rated at 800 A, this three-pole circuit breaker combines ABB’s XT7 platform with an Ekip G Dip LS/I solid-state electronic trip unit.
The Ekip G Dip LS/I release is designed for generator protection and provides long-time overload protection together with short-circuit protection functions. Its adjustable electronic protection characteristics make the breaker suitable for applications where generator operating conditions require carefully coordinated protection against sustained overloads and fault currents.
The XT7H M 800 has a rated uninterrupted current of 800 A, a rated operational voltage of 690 V AC and an H short-circuit performance level. It provides an ultimate and service short-circuit breaking capacity of 70 kA at 415 V AC, while its three-pole fixed construction, front terminals and stored-energy operating mechanism support robust integration into generator switchboards and industrial power distribution assemblies.
Generator circuits have protection requirements that can differ from conventional distribution feeders because available short-circuit currents and permissible overload characteristics depend on the generator and installation design. The ABB Ekip G Dip LS/I release is intended for generator protection applications, combining adjustable electronic protection with the high-current switching capability of the Tmax XT7 platform.
With its 800 A rating, 70 kA breaking capacity at 415 V AC, 20 kA short-time withstand current and operation at voltages up to 690 V AC, the 1SDA101474R1 provides a robust solution for generator switchboards and demanding industrial power systems. Its fixed three-pole construction and front terminals also simplify integration into purpose-built low-voltage distribution assemblies.
| Series | SACE Tmax XT |
|---|---|
| Frame | XT7 |
| Sub-type | XT7M |
| Order code / SKU | 1SDA101474R1 |
| ABB product group | T-Max XT 250 Range |
| Product type | Moulded-case circuit breaker (MCCB) |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip G Dip LS/I |
| Release type | Solid-state electronic |
| Short-circuit performance level | H |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 70 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 70 kA |
| Rated ultimate breaking capacity (Icu) at 690 V AC | 42 kA |
| Rated service breaking capacity (Ics) at 690 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 20 kA |
| Overload release adjustment range | 320–800 A |
| Mounting configuration | Fixed |
| Terminal type | Front terminals |
| Operating mechanism | Stored energy |
| Power loss at rated operating conditions | 24 W per pole |
| Mechanical durability | 20,000 cycles |
| Electrical durability | 3,000 cycles |
| Dimensions (W × H × D) | 210 × 268 × 178 mm |
| Net weight | 11 kg |
| Standard | IEC 60947 |
| EAN | 8056221012881 |
| Customs tariff number | 85362090 |
| Application | Generator, transformer and installation protection |
The ABB 1SDA101474R1 is an 800 A three-pole moulded-case circuit breaker configured with an Ekip G Dip LS/I electronic release for generator, transformer and low-voltage installation protection.
The XT7H M 800 has a rated current and rated uninterrupted current of 800 A, making it suitable for demanding high-current generator and low-voltage distribution applications.
The Ekip G Dip LS/I is an electronic protection release designed for generator protection, providing adjustable overload and short-circuit protection characteristics suitable for generator-fed electrical systems.
The XT7H M 800 has rated ultimate and service short-circuit breaking capacities of 70 kA at 415 V AC and 42 kA at 690 V AC.
The 1SDA101474R1 is supplied as a fixed three-pole circuit breaker with front terminals and a stored-energy operating mechanism for integration into generator switchboards and low-voltage power distribution assemblies.
ABB SACE Tmax XT moulded-case circuit breakers are widely used by electrical engineers, panel builders and industrial operators for dependable generator, transformer and installation protection in demanding low-voltage power systems.