1SDA101265R1 ABB XT7L 1600 Ekip G Dip LS/I 1600A 4-Pole Circuit Breaker

1SDA101265R1 ABB XT7L 1600 Ekip G Dip LS/I 1600A 4-Pole Circuit Breaker

ABB 1SDA101265R1 XT7L 1600 is a fixed four-pole 1600 A moulded case circuit breaker with front terminals, XT7L 120 kA breaking-capacity class and an Ekip G Dip LS/I electronic trip unit designed for generator and low-voltage circuit protection.

SKU: 1SDA101265R1MPN: 1SDA101265R1
Price
List Price £8,639.21 ex VAT
Your Price (ex VAT) Save 25%
£6,479.41 25% OFF
You save £2,159.80 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £6,479.41
Trade pricing is personalised to your account

Manufacturer Lead Time

£6,479.41

Why Choose the ABB 1SDA101265R1 XT7L 1600 Circuit Breaker?

The ABB 1SDA101265R1 is a high-performance SACE Tmax XT moulded case circuit breaker (MCCB) designed for generator, transformer and installation protection in demanding low-voltage electrical distribution systems. Identified as XT7L 1600 Ekip G Dip LS/I In=1600A 4p F F, this four-pole circuit breaker combines fixed construction, front terminals, lever operation and ABB's Ekip G Dip LS/I electronic trip unit.

As part of the ABB SACE Tmax XT7 range, the breaker is configured with the Ekip G Dip LS/I release for generator protection applications. Its electronic trip system provides adjustable overload and short-circuit protection, helping safeguard generators and associated distribution circuits against damaging overcurrent conditions while supporting reliable system coordination.

With a rated uninterrupted current of 1600 A, a rated voltage of 690 V and the high-breaking-capacity XT7L 120 kA class, the 1SDA101265R1 is suited to high-capacity generator systems, industrial switchboards and critical power distribution installations. Its fixed four-pole construction with front terminals provides practical integration into low-voltage switchgear assemblies.

Key Advantages

  • High-performance ABB SACE Tmax XT7L moulded case circuit breaker for generator and power distribution protection.
  • 1600 A rated uninterrupted current for high-current electrical installations.
  • Four-pole configuration for three-phase systems requiring four-pole switching and protection.
  • Ekip G Dip LS/I electronic trip unit designed for generator protection applications.
  • Adjustable overload and short-circuit protection for dependable equipment protection.
  • XT7L 120 kA breaking-capacity class for installations with high prospective fault currents.
  • Fixed construction with front terminals simplifies integration into switchboards and generator panels.

Key Features

  • ABB SACE Tmax XT7L series.
  • 1600 A rated uninterrupted current.
  • Four-pole circuit breaker.
  • Ekip G Dip LS/I electronic trip unit.
  • Designed for generator protection applications.
  • Adjustable long-time overload protection.
  • Adjustable short-circuit protection.
  • 690 V rated voltage.
  • XT7L 120 kA breaking-capacity class.
  • Overload release adjustment from 640–1600 A.
  • Short-time delayed short-circuit adjustment from 960–16000 A.
  • Instantaneous short-circuit adjustment from 1600–16000 A.
  • Fixed circuit-breaker construction.
  • Front terminal connection.
  • Lever / toggle operating mechanism for manual switching.
  • Optional motor operating mechanism for automated applications.
  • IP20 protection rating.

Generator Circuit Protection with Ekip G Dip

Generator circuit breakers protect generating equipment and associated distribution networks against abnormal current conditions while providing reliable switching and isolation. Generator applications can have different fault-current characteristics from utility-fed distribution systems, making appropriately configured electronic protection important for dependable operation and equipment protection.

ABB's Ekip G Dip LS/I trip unit is designed for generator protection applications and provides adjustable overload and short-circuit protection. When integrated with the high-breaking-capacity XT7L platform, it provides a robust solution for generator feeders, standby power systems and industrial installations where dependable circuit protection is essential.

Typical Applications

  • Generator protection and generator outgoing circuits.
  • Standby and emergency power generation systems.
  • Industrial low-voltage switchboards and distribution panels.
  • Transformer and installation protection.
  • Main and sub-main electrical distribution circuits.
  • High-current incoming and distribution feeders.
  • Manufacturing plants and critical infrastructure.
  • OEM switchgear and generator control panel building.

Technical Specifications

Series SACE Tmax XT
Frame size XT7
Order code / MPN 1SDA101265R1
Product group T-Max XT 250 Range
Product type Moulded case circuit breaker (MCCB)
Primary application Generator, transformer and installation protection
Rated uninterrupted current (Iu) 1600 A
Rated current (In) 1600 A
Rated voltage 690 V
Number of poles 4
Trip unit Ekip G Dip LS/I
Trip unit technology Electronic
Protection functions Overload and short-circuit protection (LS/I)
Overload release current setting 640–1600 A
Short-time delayed short-circuit setting 960–16000 A
Instantaneous short-circuit setting 1600–16000 A
Integrated earth-fault protection No
Interruption rating L
Breaking-capacity class 120 kA
Power loss 94 W
Mounting type Fixed
Terminal position Front
Main circuit connection Bolted connection
Operating mechanism Lever / toggle
Integrated motor drive No
Motor drive Optional
DIN rail mounting No
Protection rating IP20
EAN 8056221010832

Frequently Asked Questions

What is the ABB 1SDA101265R1 used for?

The ABB 1SDA101265R1 is a four-pole moulded case circuit breaker equipped with an Ekip G Dip LS/I electronic trip unit and is particularly suited to generator protection as well as transformer and installation protection applications.

What is the rated current of the ABB 1SDA101265R1?

The XT7L 1600 has a rated uninterrupted current of 1600 A, making it suitable for high-current generator and low-voltage power distribution applications.

What protection does the Ekip G Dip LS/I trip unit provide?

The Ekip G Dip LS/I electronic trip unit provides adjustable overload and short-circuit protection designed to safeguard generators and associated electrical distribution circuits.

What is the breaking-capacity class of the ABB XT7L 1600?

The ABB XT7L version belongs to the 120 kA breaking-capacity class, providing high fault-interruption performance for demanding generator and electrical distribution installations.

How is the ABB 1SDA101265R1 installed?

The 1SDA101265R1 is a fixed four-pole circuit breaker with front terminals and a lever / toggle operating mechanism, designed for installation within low-voltage switchboards, generator panels and industrial electrical assemblies.

Trusted Generator and Industrial Circuit Protection from ABB

ABB SACE Tmax XT circuit breakers provide dependable low-voltage circuit protection for generator, industrial and infrastructure applications, combining electronic trip technology, high breaking performance and flexible integration into modern electrical distribution systems.