1SDA101252R1 ABB XT7L 1250 Ekip Touch Measuring LSIG 1250A 4-Pole Circuit Breaker

1SDA101252R1 ABB XT7L 1250 Ekip Touch Measuring LSIG 1250A 4-Pole Circuit Breaker

ABB 1SDA101252R1 XT7L 1250 is a fixed four-pole 1250 A moulded case circuit breaker with Ekip Touch Measuring LSIG electronic protection, integrated measurement functionality and 120 kA breaking capacity at 415 V AC for demanding low-voltage power distribution systems.

SKU: 1SDA101252R1MPN: 1SDA101252R1
Price
List Price £10,669.34 ex VAT
Your Price (ex VAT) Save 25%
£8,002.01 25% OFF
You save £2,667.34 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,002.01
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,002.01

Why Choose the ABB XT7L 1250 Ekip Touch Measuring LSIG 1SDA101252R1 Circuit Breaker?

The ABB 1SDA101252R1 is a high-performance four-pole moulded case circuit breaker (MCCB) designed for protection, switching, measurement and isolation in demanding low-voltage power distribution systems. Part of the ABB SACE Tmax XT7 range, this XT7L breaker combines a 1250 A rated uninterrupted current with the advanced Ekip Touch Measuring LSIG electronic trip unit.

The Ekip Touch Measuring LSIG release combines electronic circuit protection with integrated measurement capabilities. Its long-time, short-time, instantaneous and ground-fault (LSIG) protection functions provide comprehensive protection for electrical distribution systems, while the Ekip Touch platform supports monitoring and configuration for modern switchboards and connected power systems.

With a rated uninterrupted current of 1250 A, a four-pole configuration and XT7L breaking performance of 120 kA at 415 V AC, the 1SDA101252R1 is well suited to major feeders, industrial switchboards and high-current distribution circuits. Its fixed construction with front terminals and lever operating mechanism enables straightforward integration into low-voltage switchgear assemblies.

Key Advantages

  • High-performance ABB SACE Tmax XT7L moulded case circuit breaker.
  • 1250 A rated uninterrupted current for demanding power distribution applications.
  • Four-pole configuration for three-phase systems with neutral.
  • Advanced Ekip Touch Measuring LSIG electronic trip unit.
  • Long-time, short-time, instantaneous and ground-fault protection.
  • Integrated measurement functionality for enhanced electrical system monitoring.
  • High 120 kA breaking capacity at 415 V AC.
  • Fixed construction with front terminal connections for switchboard integration.

Key Features

  • ABB SACE Tmax XT7L series.
  • 1250 A rated current.
  • 4-pole configuration.
  • Ekip Touch Measuring LSIG solid-state electronic release.
  • Long-time overload protection.
  • Short-time short-circuit protection.
  • Instantaneous short-circuit protection.
  • Ground-fault protection.
  • Integrated measurement functionality.
  • Touch-interface electronic trip unit.
  • L short-circuit performance level.
  • Fixed mounting configuration.
  • Front terminal connections.
  • Lever operating mechanism.

Advanced Protection and Measurement for Power Distribution

Moulded case circuit breakers such as the ABB XT7L protect low-voltage electrical distribution systems against overloads and short circuits while providing dependable switching and isolation. The XT7L platform combines high current-carrying capability with substantial short-circuit breaking performance, making it suitable for industrial installations, infrastructure and large commercial power distribution systems.

The Ekip Touch Measuring LSIG electronic trip unit combines long-time, short-time, instantaneous and ground-fault protection with measurement functionality. This provides electrical engineers with an advanced platform for protecting and monitoring distribution circuits while supporting coordination, energy management and improved visibility of electrical system operation.

Typical Applications

  • Industrial low-voltage switchboards.
  • Main and sub-main power distribution circuits.
  • High-current feeder protection.
  • Power monitoring and energy management systems.
  • Manufacturing and process plants.
  • Commercial building electrical distribution.
  • Infrastructure and utility installations.
  • Low-voltage switchgear and distribution assemblies.

Technical Specifications

Series SACE Tmax XT
Frame XT7
Order code / MPN 1SDA101252R1
Product type Moulded case circuit breaker
Application Power distribution protection and measurement
Rated uninterrupted current (Iu) 1250 A
Rated current (In) 1250 A
Number of poles 4
Trip unit Ekip Touch Measuring LSIG
Release type Electronic / solid-state
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Overload release setting range 500–1250 A
Short-time short-circuit release setting range 750–12500 A
Instantaneous short-circuit release setting range 1875–18750 A
Rated operational voltage up to 690 V AC
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 120 kA
Short-circuit performance level L
Mounting version Fixed
Terminal connection Front
Main circuit connection Bolt connection
Operating mechanism Lever
Protection rating IP20
Motor operator Optional
Standard IEC 60947-2
Dimensions (H × W × D) 268 × 280 × 166 mm
Weight 12.5 kg
Power loss 57 W
EAN 8056221010702

Frequently Asked Questions

What is the ABB 1SDA101252R1 used for?

The ABB 1SDA101252R1 is a 1250 A four-pole moulded case circuit breaker designed for protection, switching, measurement and isolation in demanding low-voltage power distribution systems.

What trip unit is fitted to the ABB XT7L 1250 1SDA101252R1?

The breaker is fitted with an Ekip Touch Measuring LSIG electronic trip unit, combining measurement capabilities with long-time, short-time, instantaneous and ground-fault protection.

What is the rated current of this circuit breaker?

The ABB 1SDA101252R1 has a rated uninterrupted current of 1250 A.

What is the breaking capacity of the ABB XT7L 1250?

The XT7L version provides an ultimate short-circuit breaking capacity of 120 kA at 415 V AC, making it suitable for demanding installations with high prospective fault currents.

How is the ABB 1SDA101252R1 installed?

This model is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for integration into industrial switchboards and low-voltage power distribution assemblies.

Trusted Protection and Measurement from ABB

ABB SACE Tmax XT circuit breakers combine dependable low-voltage circuit protection with advanced electronic trip technology, measurement capabilities and high short-circuit performance for demanding industrial, commercial and infrastructure power distribution systems.