1SDA101152R1 ABB XT7S 1250 Ekip G Dip LS/I In1250A 4p F F Circuit Breaker

1SDA101152R1 ABB XT7S 1250 Ekip G Dip LS/I In1250A 4p F F Circuit Breaker

ABB 1SDA101152R1 XT7S 1250 Ekip G Dip LS/I four-pole fixed moulded case circuit breaker with a 1250 A rated current, front terminals and adjustable electronic protection designed for generator applications.

SKU: 1SDA101152R1MPN: 1SDA101152R1
Price
List Price £4,817.00 ex VAT
Your Price (ex VAT) Save 25%
£3,612.75 25% OFF
You save £1,204.25 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,612.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,612.75

Why Choose the ABB XT7S 1250 Ekip G Dip LS/I In1250A 4p F F Circuit Breaker?

The ABB XT7S 1250 Ekip G Dip LS/I In1250A 4p F F, order code 1SDA101152R1, is a high-performance four-pole moulded case circuit breaker (MCCB) designed for generator protection and demanding low-voltage electrical distribution applications. As part of the ABB SACE Tmax XT series, it combines a 1250 A rated current with the Ekip G Dip LS/I electronic trip unit.

The Ekip G Dip LS/I solid-state release provides adjustable overload, selective short-circuit and instantaneous short-circuit protection specifically suited to generator applications. Its electronic protection characteristics help coordinate the breaker with generator-fed networks while protecting conductors, switchgear and connected equipment against potentially damaging overcurrent conditions.

With a rated uninterrupted current of 1250 A, a four-pole configuration and a rated operational voltage of 690 V AC, the XT7S is suitable for substantial generator and industrial power distribution systems. The S breaking-capacity version provides an ultimate short-circuit breaking capacity of 50 kA, while fixed construction and front terminals enable straightforward integration into low-voltage switchboards.

Key Advantages

  • High-performance 1250 A moulded case circuit breaker for generator protection.
  • Four-pole configuration suitable for three-phase systems with neutral.
  • Purpose-designed Ekip G Dip LS/I electronic trip unit.
  • Adjustable overload, selective short-circuit and instantaneous short-circuit protection.
  • 500–1250 A overload protection adjustment range.
  • 50 kA XT7S ultimate short-circuit breaking capacity.
  • Fixed installation with front terminals for switchboard integration.
  • Part of the advanced ABB SACE Tmax XT circuit breaker platform.

Key Features

  • ABB SACE Tmax XT7S moulded case circuit breaker.
  • 1250 A rated uninterrupted current.
  • Four-pole construction.
  • Ekip G Dip LS/I solid-state electronic release.
  • Designed for generator protection applications.
  • Overload adjustment from 500–1250 A.
  • Short-time delayed short-circuit adjustment from 750–12500 A.
  • Instantaneous short-circuit adjustment from 1250–12500 A.
  • 690 V AC rated operational voltage.
  • IP20 protection rating.
  • Fixed installation with front main-circuit connections.
  • Lever operating mechanism with optional motor operator capability.

Reliable Protection for Generator Applications

Generator-fed electrical systems require carefully coordinated protection because their short-circuit characteristics can differ significantly from conventional utility-fed networks. The ABB Ekip G protection platform is designed for generator applications, providing adjustable electronic overload and short-circuit functions that allow the protective response to be matched to generator and installation requirements.

The XT7S platform combines generator-focused electronic protection with robust high-current moulded case circuit breaker construction. With its 1250 A current rating, four-pole configuration, 690 V AC operational voltage and fixed front-terminal design, the 1SDA101152R1 is well suited to generator switchboards, standby power installations and industrial electrical distribution systems.

Typical Applications

  • Generator protection systems.
  • Generator control and distribution switchboards.
  • Standby and emergency power systems.
  • Industrial low-voltage switchboards.
  • Manufacturing and process plants.
  • Commercial and infrastructure power distribution.
  • High-current generator feeders.
  • Electrical systems requiring adjustable electronic overcurrent protection.

Technical Specifications

Series SACE Tmax XT
Order code / Product ID 1SDA101152R1
Product type Moulded case circuit breaker (MCCB)
Frame size XT7
Application Generator protection
Rated uninterrupted current (Iu) 1250 A
Rated current (In) 1250 A
Number of poles 4
Trip unit Ekip G Dip LS/I
Release type Solid-state electronic release
Protection functions Long-time, short-time and instantaneous (LS/I)
Rated operational voltage 690 V AC
Breaking-capacity class S
Rated ultimate short-circuit breaking capacity (Icu) 50 kA
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit release adjustment range 750–12500 A
Instantaneous short-circuit release adjustment range 1250–12500 A
Integrated earth-fault protection No
Power dissipation 57 W
Protection rating IP20
Installation Fixed
Main circuit connection Bolt connection
Terminal position Front
Operating mechanism Lever operating mechanism
Motor operator Optional
Standard IEC 60947-2
EAN 8056221014557

Frequently Asked Questions

What is the ABB 1SDA101152R1 used for?

The ABB 1SDA101152R1 is a 1250 A four-pole moulded case circuit breaker equipped with an Ekip G Dip LS/I electronic trip unit for generator protection and low-voltage electrical distribution applications.

What is the rated current of the ABB XT7S 1SDA101152R1?

The circuit breaker has a rated uninterrupted current of 1250 A.

Which trip unit is fitted to the ABB 1SDA101152R1?

The 1SDA101152R1 is fitted with an Ekip G Dip LS/I solid-state electronic trip unit designed for generator protection, with adjustable overload, selective short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB XT7S 1250?

The XT7S S-version has a rated ultimate short-circuit breaking capacity of 50 kA, providing robust fault interruption for demanding low-voltage distribution applications.

How is the ABB XT7S 1SDA101152R1 installed?

The 1SDA101152R1 is a fixed four-pole circuit breaker with front terminals and a lever operating mechanism, designed for installation within low-voltage switchboards and generator distribution assemblies.

Trusted Generator Protection from ABB

ABB SACE Tmax XT circuit breakers with Ekip G electronic protection provide dependable generator and electrical distribution protection, combining adjustable electronic trip functions, high breaking performance and robust construction for industrial and commercial power systems.