1SDA100815R1 ABB TMA 800-8000 XT6 4-Pole Thermomagnetic Trip Unit

1SDA100815R1 ABB TMA 800-8000 XT6 4-Pole Thermomagnetic Trip Unit

ABB 1SDA100815R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible SACE Tmax XT6 breaking parts, providing adjustable thermal overload and instantaneous magnetic short-circuit protection with a fully rated neutral.

SKU: 1SDA100815R1MPN: 1SDA100815R1
Price
List Price £1,376.33 ex VAT
Your Price (ex VAT) Save 25%
£1,032.25 25% OFF
You save £344.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,032.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,032.25

Why Choose the ABB 1SDA100815R1 TMA 800-8000 XT6 4-Pole Trip Unit?

The ABB 1SDA100815R1 is a TMA thermomagnetic trip unit designed for compatible four-pole ABB SACE Tmax XT6 moulded-case circuit-breaker breaking parts. Rated at 800 A, it combines adjustable thermal overload protection with adjustable magnetic short-circuit protection for high-current AC and DC power-distribution applications.

The TMA 800-8000 release uses proven thermomagnetic protection technology. Its thermal element is adjustable from 0.7–1 × In, corresponding to 560–800 A, while the instantaneous magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A.

This four-pole version features a fully rated neutral (InN=100%In), meaning the neutral pole is protected at the same current rating as the phase poles. The release is supplied as a configurable XT6 component and is intended to be combined with a compatible four-pole ABB Tmax XT6 breaking part to form a complete protected circuit-breaker assembly.

Key Advantages

  • Genuine ABB SACE Tmax XT6 TMA thermomagnetic trip unit.
  • 800 A rated current for high-current power-distribution circuits.
  • Adjustable thermal overload protection from 560–800 A.
  • Adjustable instantaneous magnetic protection from 4000–8000 A.
  • Fully rated neutral at 100% of phase current for four-wire distribution systems.
  • Suitable for AC and DC applications when combined with a compatible XT6 breaking part.

Key Features

  • ABB TMA 800-8000 thermomagnetic protection release.
  • Designed for the SACE Tmax XT6 platform.
  • 800 A rated current (In).
  • Four-pole configuration.
  • Adjustable thermal overload protection.
  • Adjustable instantaneous magnetic short-circuit protection.
  • InN=100%In fully rated neutral.
  • Loose/configurable component for combination with a compatible four-pole XT6 breaking part.

Reliable Thermomagnetic Protection for Power Distribution

Thermomagnetic protection combines two complementary operating principles within a straightforward protection release. The thermal element responds to sustained overcurrents to provide overload protection, while the magnetic element operates rapidly when current reaches a high short-circuit level. The ABB TMA release provides adjustable thresholds for both functions, enabling protection to be matched to the requirements of the distribution circuit.

The InN=100%In configuration provides a fully rated neutral, so the neutral pole receives protection at the same current level as the phase conductors. This makes the 1SDA100815R1 particularly relevant to four-wire systems where the neutral conductor requires full-current protection. As a separate trip unit, it must be combined with a compatible four-pole ABB SACE Tmax XT6 breaking part to form the complete circuit-breaker assembly.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • High-current power-distribution feeders.
  • Commercial building electrical distribution systems.
  • Manufacturing and process-industry power networks.
  • Custom four-pole ABB Tmax XT6 circuit-breaker assemblies.
  • Four-wire circuits requiring adjustable thermomagnetic protection with a fully rated neutral.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA100815R1
Product type Thermomagnetic trip unit / release
Compatible frame XT6
Trip-unit type TMA
Release type TM
Protection technology Thermomagnetic
Rated current (In) 800 A
Number of poles 4
Thermal overload setting 0.7–1 × In
Thermal overload adjustment range 560–800 A
Magnetic short-circuit setting 5–10 × In
Instantaneous magnetic adjustment range 4000–8000 A
Neutral protection 100% of phase current
Neutral protection designation InN=100%In
Neutral configuration Fully rated neutral
Current type AC/DC
Configuration type Loose or configurable
Suitable for XT6 power-distribution circuit breakers
Standard IEC 60947-2
Product net weight 1.3 kg
Package dimensions 179 × 179 × 223 mm
EAN / GTIN 8056221008693
Customs tariff number 85389099
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA100815R1?

The ABB 1SDA100815R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible ABB SACE Tmax XT6 circuit-breaker breaking parts, providing adjustable thermal and magnetic protection with a fully rated neutral.

What is the thermal adjustment range of the ABB 1SDA100815R1?

The thermal overload protection is adjustable from 0.7–1 × In. With an 800 A rated current, this corresponds to an adjustment range of 560–800 A.

What is the magnetic short-circuit adjustment range?

The instantaneous magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A for this 800 A TMA trip unit.

What does InN=100%In mean on the ABB 1SDA100815R1?

InN=100%In means the neutral pole is fully rated and protected at the same current level as the phase poles, providing full neutral protection in compatible four-wire distribution systems.

Is the ABB 1SDA100815R1 a complete circuit breaker?

No. The ABB 1SDA100815R1 is a separate thermomagnetic trip unit and must be combined with a compatible four-pole ABB SACE Tmax XT6 breaking part to form a complete protected circuit-breaker assembly.

Trusted Circuit Protection from ABB

ABB SACE Tmax XT protection components provide flexible solutions for low-voltage power distribution, combining robust circuit-breaker platforms with thermomagnetic and electronic trip technologies for reliable protection across industrial, commercial and infrastructure applications.