Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100814R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible SACE Tmax XT6 breaking parts, providing adjustable thermal overload and magnetic short-circuit protection with neutral protection at 50% of the phase setting.
£1,032.25
The ABB 1SDA100814R1 is a TMA thermomagnetic trip unit designed for compatible four-pole ABB SACE Tmax XT6 moulded-case circuit-breaker breaking parts. Rated at 800 A, it combines adjustable thermal overload protection with adjustable magnetic short-circuit protection for reliable low-voltage power-distribution applications.
The TMA 800-8000 release uses proven thermomagnetic technology without requiring an electronic protection platform. Its thermal element is adjustable from 0.7–1 × In, corresponding to 560–800 A, while the magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A.
This four-pole version incorporates neutral protection at 50% of the phase setting (InN=50%In). At the nominal 800 A phase rating, this corresponds to a 400 A nominal neutral-protection reference. The trip unit is intended to be combined with a compatible four-pole XT6 breaking part to create a complete protected circuit-breaker assembly.
Thermomagnetic protection combines two complementary operating principles. The thermal element responds to sustained overcurrents and provides overload protection, while the magnetic element reacts rapidly when current rises to a high short-circuit level. The ABB TMA design provides adjustable thresholds for both functions, enabling the protection characteristics to be matched more closely to the protected distribution circuit.
The InN=50%In configuration provides reduced neutral protection appropriate to systems where the neutral conductor is sized or protected at half the phase-current level. Because the 1SDA100814R1 is a separate trip unit rather than a complete circuit breaker, it must be combined with a compatible four-pole ABB Tmax XT6 breaking part to provide the complete switching, interruption and protection assembly.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA100814R1 |
| Product type | Thermomagnetic trip unit |
| Compatible frame | XT6 |
| Trip-unit type | TMA |
| Protection technology | Thermomagnetic |
| Rated current (In) | 800 A |
| Number of poles | 4 |
| Thermal overload setting | 0.7–1 × In |
| Thermal overload adjustment range | 560–800 A |
| Magnetic short-circuit setting | 5–10 × In |
| Magnetic short-circuit adjustment range | 4000–8000 A |
| Maximum instantaneous short-circuit setting | 8000 A |
| Neutral protection | 50% of phase current setting |
| Neutral protection designation | InN=50%In |
| Nominal neutral-current reference at 800 A In | 400 A |
| Suitable for circuit breakers | Yes |
| Compatible breaking part | Four-pole ABB SACE Tmax XT6 |
| EAN / GTIN | 8056221008686 |
| ABB product group | T-Max XT 250 Range |
The ABB 1SDA100814R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible ABB SACE Tmax XT6 moulded-case circuit-breaker breaking parts, with adjustable thermal and magnetic protection and 50% neutral protection.
The thermal overload protection is adjustable from 0.7–1 × In. With an 800 A rated current, this corresponds to an adjustment range of 560–800 A.
The magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A for this 800 A TMA trip unit.
InN=50%In means the neutral-pole protection is configured at 50% of the phase-current setting. At the nominal 800 A rating, this represents a 400 A nominal neutral-current reference.
No. The ABB 1SDA100814R1 is a separate thermomagnetic trip unit and must be combined with a compatible four-pole ABB SACE Tmax XT6 breaking part to create a complete protected circuit-breaker assembly.
ABB SACE Tmax XT protection components provide flexible solutions for low-voltage power distribution, combining robust circuit-breaker platforms with thermomagnetic and electronic trip technologies to support reliable protection across industrial, commercial and infrastructure applications.