1SDA100814R1 ABB TMA 800-8000 XT6 4-Pole Thermomagnetic Trip Unit

1SDA100814R1 ABB TMA 800-8000 XT6 4-Pole Thermomagnetic Trip Unit

ABB 1SDA100814R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible SACE Tmax XT6 breaking parts, providing adjustable thermal overload and magnetic short-circuit protection with neutral protection at 50% of the phase setting.

SKU: 1SDA100814R1MPN: 1SDA100814R1
Price
List Price £1,376.33 ex VAT
Your Price (ex VAT) Save 25%
£1,032.25 25% OFF
You save £344.08 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,032.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,032.25

Why Choose the ABB 1SDA100814R1 TMA 800-8000 XT6 4-Pole Trip Unit?

The ABB 1SDA100814R1 is a TMA thermomagnetic trip unit designed for compatible four-pole ABB SACE Tmax XT6 moulded-case circuit-breaker breaking parts. Rated at 800 A, it combines adjustable thermal overload protection with adjustable magnetic short-circuit protection for reliable low-voltage power-distribution applications.

The TMA 800-8000 release uses proven thermomagnetic technology without requiring an electronic protection platform. Its thermal element is adjustable from 0.7–1 × In, corresponding to 560–800 A, while the magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A.

This four-pole version incorporates neutral protection at 50% of the phase setting (InN=50%In). At the nominal 800 A phase rating, this corresponds to a 400 A nominal neutral-protection reference. The trip unit is intended to be combined with a compatible four-pole XT6 breaking part to create a complete protected circuit-breaker assembly.

Key Advantages

  • Genuine ABB SACE Tmax XT6 TMA thermomagnetic trip unit.
  • 800 A nominal current for high-current distribution applications.
  • Adjustable thermal protection from 560–800 A for overload protection.
  • Adjustable magnetic protection from 4000–8000 A for short-circuit protection.
  • Four-pole configuration with 50% neutral protection for compatible four-wire systems.
  • Modular construction allows combination with a compatible ABB XT6 four-pole breaking part.

Key Features

  • ABB TMA 800-8000 thermomagnetic protection release.
  • Designed for the SACE Tmax XT6 platform.
  • 800 A rated current (In).
  • Four-pole configuration.
  • Adjustable thermal overload protection.
  • Adjustable instantaneous magnetic short-circuit protection.
  • InN=50%In neutral protection.
  • Designed for combination with a compatible four-pole XT6 breaking part.

Reliable Thermomagnetic Protection for Power Distribution

Thermomagnetic protection combines two complementary operating principles. The thermal element responds to sustained overcurrents and provides overload protection, while the magnetic element reacts rapidly when current rises to a high short-circuit level. The ABB TMA design provides adjustable thresholds for both functions, enabling the protection characteristics to be matched more closely to the protected distribution circuit.

The InN=50%In configuration provides reduced neutral protection appropriate to systems where the neutral conductor is sized or protected at half the phase-current level. Because the 1SDA100814R1 is a separate trip unit rather than a complete circuit breaker, it must be combined with a compatible four-pole ABB Tmax XT6 breaking part to provide the complete switching, interruption and protection assembly.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • High-current power-distribution feeders.
  • Commercial building electrical distribution systems.
  • Manufacturing and process-industry power networks.
  • Custom four-pole ABB Tmax XT6 circuit-breaker assemblies.
  • Four-wire circuits requiring adjustable thermomagnetic protection with 50% neutral protection.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA100814R1
Product type Thermomagnetic trip unit
Compatible frame XT6
Trip-unit type TMA
Protection technology Thermomagnetic
Rated current (In) 800 A
Number of poles 4
Thermal overload setting 0.7–1 × In
Thermal overload adjustment range 560–800 A
Magnetic short-circuit setting 5–10 × In
Magnetic short-circuit adjustment range 4000–8000 A
Maximum instantaneous short-circuit setting 8000 A
Neutral protection 50% of phase current setting
Neutral protection designation InN=50%In
Nominal neutral-current reference at 800 A In 400 A
Suitable for circuit breakers Yes
Compatible breaking part Four-pole ABB SACE Tmax XT6
EAN / GTIN 8056221008686
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA100814R1?

The ABB 1SDA100814R1 is an 800 A four-pole TMA thermomagnetic trip unit for compatible ABB SACE Tmax XT6 moulded-case circuit-breaker breaking parts, with adjustable thermal and magnetic protection and 50% neutral protection.

What is the thermal adjustment range of the ABB 1SDA100814R1?

The thermal overload protection is adjustable from 0.7–1 × In. With an 800 A rated current, this corresponds to an adjustment range of 560–800 A.

What is the magnetic short-circuit adjustment range?

The magnetic protection is adjustable from 5–10 × In, corresponding to 4000–8000 A for this 800 A TMA trip unit.

What does InN=50%In mean on the ABB 1SDA100814R1?

InN=50%In means the neutral-pole protection is configured at 50% of the phase-current setting. At the nominal 800 A rating, this represents a 400 A nominal neutral-current reference.

Is the ABB 1SDA100814R1 a complete circuit breaker?

No. The ABB 1SDA100814R1 is a separate thermomagnetic trip unit and must be combined with a compatible four-pole ABB SACE Tmax XT6 breaking part to create a complete protected circuit-breaker assembly.

Trusted Circuit Protection from ABB

ABB SACE Tmax XT protection components provide flexible solutions for low-voltage power distribution, combining robust circuit-breaker platforms with thermomagnetic and electronic trip technologies to support reliable protection across industrial, commercial and infrastructure applications.