ABB 1SDA100695R1 is a 320 A four-pole TMG thermomagnetic generator protection release for Tmax XT5 circuit breakers with an 800–1600 A magnetic protection range and a fully rated neutral.
£497.22
The ABB TMG 320-1600 XT5 4p InN=100%In is a thermomagnetic protection release designed for ABB Tmax XT5 moulded-case circuit breakers used in generator protection applications. Identified by ABB order code 1SDA100695R1, this four-pole release combines thermal overload protection with magnetic short-circuit protection for dependable low-voltage generator circuits.
As part of the ABB Tmax XT5 circuit-breaker platform, the TMG release is specifically intended for generator protection. It has a rated current of 320 A and an instantaneous magnetic protection range of 800–1600 A, providing a magnetic threshold suited to the particular protection requirements associated with generating equipment.
The four-pole configuration incorporates a fully rated neutral, with InN = 100% In, allowing the neutral pole to carry and be protected at the same rated current as the phase poles. The release is designed for use with a compatible ABB Tmax XT5 breaking part to create a complete generator-protection circuit-breaker assembly.
Generator circuits require protection characteristics that account for the operating behaviour and available short-circuit current of generating equipment. The ABB TMG release combines thermal overload protection with magnetic short-circuit protection, helping protect generators, conductors and associated distribution equipment against damaging overcurrent conditions.
The TMG 320-1600 release is engineered for the ABB Tmax XT5 platform and provides a magnetic protection range of 800–1600 A. Its four-pole design with a fully rated neutral makes it suitable for generator distribution systems where protection and switching of all phase conductors and the neutral are required.
| Series | Tmax XT5 |
|---|---|
| ABB order code | 1SDA100695R1 |
| EAN / GTIN | 8056221007719 |
| Product type | Thermomagnetic generator protection release |
| Trip unit type | TMG |
| Rated current | 320 A |
| Instantaneous magnetic protection range | 800–1600 A |
| Number of poles | 4 |
| Neutral rating | 100% In |
| Protection technology | Thermomagnetic |
| Application | Generator protection |
| Compatible breaker frame | ABB Tmax XT5 |
| Product net weight | 1.214 kg |
The ABB 1SDA100695R1 is a TMG thermomagnetic protection release designed for generator protection using compatible ABB Tmax XT5 moulded-case circuit-breaker assemblies.
The release has a rated current of 320 A.
The instantaneous magnetic protection range is 800–1600 A.
TMG identifies an ABB thermomagnetic release intended for generator protection, combining thermal overload and magnetic short-circuit protection.
Yes. This four-pole version has InN = 100% In, meaning the neutral is rated at 100% of the phase rated current.
No. The 1SDA100695R1 is the TMG protection release and is designed to be combined with a compatible ABB Tmax XT5 breaking part to form the required circuit-breaker assembly.
ABB Tmax XT circuit protection products are widely used by panel builders, generator-system integrators and electrical engineers to provide dependable overcurrent protection for industrial, commercial and infrastructure power distribution systems.