1SDA100653R1 ABB TMA 500-5000 XT5 4P InN=50%In

1SDA100653R1 ABB TMA 500-5000 XT5 4P InN=50%In

ABB 1SDA100653R1 TMA 500-5000 is a 500 A four-pole thermomagnetic trip unit for SACE Tmax XT5 circuit breakers with 50% neutral protection and adjustable 2500–5000 A instantaneous short-circuit protection.

SKU: 1SDA100653R1MPN: 1SDA100653R1
Price
List Price £684.93 ex VAT
Your Price (ex VAT) Save 25%
£513.70 25% OFF
You save £171.23 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £513.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£513.70

Why Choose the ABB TMA 500-5000 XT5 4P InN=50%In?

The ABB TMA 500-5000 XT5 4p InN=50%In, order code 1SDA100653R1, is a four-pole thermomagnetic trip unit designed for use with compatible ABB SACE Tmax XT5 moulded case circuit breaker breaking parts. Rated at 500 A, it provides reliable overload and instantaneous short-circuit protection for AC and DC low-voltage power distribution applications.

As part of the ABB Tmax XT5 TMA range, this trip unit combines thermal overload protection with adjustable magnetic short-circuit protection. Its instantaneous magnetic protection setting can be adjusted from 2500–5000 A, allowing the protection characteristics to be configured for the requirements of the electrical distribution system.

The four-pole 1SDA100653R1 incorporates neutral protection rated at 50% of the phase setting. Designed to operate with a compatible XT5 breaking part, the TMA release provides a straightforward thermomagnetic protection solution for switchboards, distribution panels and industrial power systems where dependable circuit protection without a complex electronic trip unit is required.

Key Advantages

  • Reliable thermomagnetic protection for ABB Tmax XT5 circuit breakers.
  • 500 A rated current for demanding low-voltage distribution applications.
  • Four-pole configuration provides switching and protection across three phases and neutral.
  • Neutral protection at 50% of the phase setting.
  • Adjustable instantaneous short-circuit protection from 2500–5000 A.
  • Suitable for AC and DC applications with compatible XT5 circuit-breaker assemblies.

Key Features

  • ABB TMA thermomagnetic trip unit.
  • 500 A rated current (In).
  • Four-pole configuration.
  • 50% neutral protection (InN=50%In).
  • Thermal protection against sustained overload conditions.
  • Magnetic protection against high short-circuit currents.
  • 2500–5000 A adjustable instantaneous magnetic trip range.
  • Magnetic adjustment corresponds to 5–10 × In.
  • Designed for use with ABB SACE Tmax XT5 breaking parts.
  • Suitable for power distribution and cable protection applications.
  • Mechanical thermomagnetic operation without reliance on an electronic protection release.
  • Designed for low-voltage circuit-breaker applications.

Reliable Thermomagnetic Protection for Power Distribution

Thermomagnetic trip units combine two complementary protection principles within a circuit breaker. The thermal element responds to sustained overload currents using an inverse-time characteristic, while the magnetic element operates rapidly when a high short-circuit current exceeds the configured instantaneous threshold.

The ABB TMA 500-5000 provides this protection in a robust four-pole format for the Tmax XT5 platform. Its adjustable 2500–5000 A magnetic threshold allows short-circuit protection to be coordinated with the installation, while the 50% neutral setting provides dedicated neutral protection for suitable four-wire distribution systems.

Typical Applications

  • Industrial low-voltage switchboards.
  • Three-phase and neutral distribution systems.
  • Main and sub-distribution panels.
  • Commercial building electrical distribution.
  • Manufacturing and process plant power systems.
  • Cable and feeder protection.
  • Infrastructure electrical installations.
  • OEM switchgear and electrical panel assemblies.

Technical Specifications

Series TMA / SACE Tmax XT5
ABB order code 1SDA100653R1
Product type Thermomagnetic trip unit / protection release
Suitable for ABB SACE Tmax XT5
Application Power distribution protection
Rated current (In) 500 A
Number of poles 4
Neutral protection 50% of phase setting
Neutral setting (InN) 50% In
Protection technology Thermomagnetic
Protection functions Thermal overload and magnetic short circuit
Instantaneous short-circuit setting (I3) 2500–5000 A
Magnetic setting range 5–10 × In
Current application AC / DC
Product net width 179 mm
Product net height 179 mm
Product net depth 223 mm
Product net weight 1.05 kg
Package dimensions (W × H × D) 120 × 180 × 225 mm
EAN 8056221007290
Customs tariff number 85389099

Frequently Asked Questions

What is the ABB 1SDA100653R1 used for?

The ABB 1SDA100653R1 is a TMA thermomagnetic trip unit designed for use with compatible ABB SACE Tmax XT5 moulded case circuit breaker breaking parts to provide overload and short-circuit protection.

What is the rated current of the ABB TMA 500-5000 1SDA100653R1?

The trip unit has a rated current of 500 A and uses a four-pole configuration.

What is the magnetic short-circuit setting range?

The instantaneous magnetic short-circuit protection can be adjusted from 2500–5000 A, equivalent to approximately 5–10 × In.

What does InN=50%In mean?

InN=50%In means that the neutral pole protection is set at 50% of the phase rated-current setting, providing dedicated neutral protection in the four-pole circuit-breaker configuration.

Which circuit breaker is the ABB 1SDA100653R1 designed for?

The 1SDA100653R1 is designed for use with a compatible ABB SACE Tmax XT5 breaking part and must be combined with the appropriate breaking unit to form a complete circuit breaker.

Dependable ABB Protection for Distribution Systems

ABB TMA thermomagnetic trip units provide robust overload and short-circuit protection within the SACE Tmax XT platform, offering straightforward adjustable protection for industrial, commercial and infrastructure low-voltage distribution systems.