Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100631R1 is a 630 A three-pole TMG thermomagnetic trip unit for SACE Tmax XT5 circuit breaker assemblies, providing adjustable thermal overload and magnetic short-circuit protection for generator applications.
£429.13
The ABB TMG 630-3150 XT5 3p, order code 1SDA100631R1, is a three-pole thermomagnetic trip unit for generator protection designed for the ABB SACE Tmax XT5 moulded case circuit breaker platform. Rated at 630 A, it provides thermal overload and magnetic short-circuit protection for compatible XT5 circuit breaker assemblies.
The TMG release is engineered specifically for generator protection, where protection characteristics need to accommodate the operating behaviour and fault-current characteristics of generating equipment. Its thermal element is adjustable from 0.7–1 × In, while its magnetic element is adjustable from 5–10 × In.
The 1SDA100631R1 is supplied as a three-pole protection release for use with a compatible three-pole ABB XT5 breaking part. This modular arrangement allows the breaking-capacity class and generator-protection release to be selected independently to suit the requirements of the low-voltage installation.
The ABB TMG release provides protection characteristics specifically intended for generator applications. Its adjustable thermal element protects against sustained overload conditions, while the magnetic element provides rapid short-circuit protection. With a rated current of 630 A, the 1SDA100631R1 is the highest-current TMG option in the three-pole XT5 generator-protection range.
As part of ABB's modular SACE Tmax XT5 architecture, the TMG release is used together with a compatible XT5 breaking part. This allows the interruption-performance class of the circuit breaker and the generator-protection characteristics of the release to be selected according to the electrical system requirements.
| Series | SACE Tmax XT |
|---|---|
| Compatible frame | XT5 |
| ABB order code | 1SDA100631R1 |
| EAN / GTIN | 8056221007078 |
| Product type | Thermomagnetic trip unit |
| Trip unit | TMG |
| Rated current (In) | 630 A |
| Thermal protection adjustment | 0.7–1 × In |
| Thermal protection setting range | 441–630 A |
| Magnetic protection adjustment | 5–10 × In |
| Magnetic protection setting range | 3150–6300 A |
| Number of poles | 3 |
| Protection technology | Thermomagnetic |
| Application | Generator protection |
| Compatible device | ABB SACE Tmax XT5 three-pole breaking part |
| Standard | IEC/EN 60947-2 |
The ABB 1SDA100631R1 is a TMG 630 A three-pole thermomagnetic trip unit designed for generator protection using compatible ABB SACE Tmax XT5 breaking parts.
The thermal element is adjustable from 0.7–1 × In, corresponding to a setting range of 441–630 A for this 630 A trip unit.
The magnetic protection is adjustable from 5–10 × In, corresponding to a magnetic setting range of 3150–6300 A.
The TMG release is designed specifically for generator protection, combining adjustable thermal overload protection with magnetic short-circuit protection.
No. The 1SDA100631R1 is the thermomagnetic protection trip unit and is designed to be combined with a compatible three-pole ABB XT5 breaking part to form the required circuit breaker assembly.
ABB SACE Tmax XT TMG releases provide adjustable thermomagnetic protection specifically suited to generator applications, combining overload and short-circuit protection with the flexibility of ABB's modular XT5 circuit breaker architecture.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.