Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100540R1 XT5H 630 fixed four-pole moulded case circuit breaker with front terminals, a 500 A TMG thermomagnetic release and a 100% rated neutral for generator, transformer and installation protection.
£2,070.05
The ABB 1SDA100540R1 is a high-performance Tmax XT5H moulded case circuit breaker (MCCB) designed for generator, transformer and installation protection in demanding low-voltage power systems. Part of the ABB SACE Tmax XT series, this fixed four-pole breaker uses an XT5 630 A frame with a TMG thermomagnetic trip unit rated at 500 A.
The TMG release is particularly suited to generator protection and combines adjustable thermal overload protection with magnetic short-circuit protection. Its overload setting range extends from 350–500 A, while the magnetic short-circuit setting is adjustable from 1250–2500 A, equivalent to 2.5–5 × In.
With four-pole construction, a fully rated neutral at 100% of In, fixed mounting and front terminals, the XT5H 630 TMG is well suited to three-phase four-wire distribution and generator systems. The XT5H performance level provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC and 40 kA at 690 V AC.
Generator circuits have different protection requirements from conventional utility-fed distribution circuits because available short-circuit current can be comparatively limited. The ABB TMG thermomagnetic release addresses these applications with a lower magnetic operating range of 2.5–5 × In, helping provide effective short-circuit protection while retaining adjustable thermal protection against sustained overloads.
The four-pole construction of the 1SDA100540R1 enables switching of all three phases and the neutral conductor, with the neutral rated at 100% of In. Combined with the XT5H high breaking-capacity class, fixed mounting and front-terminal arrangement, this configuration is well suited to generator switchboards, standby power systems and substantial industrial or commercial distribution installations.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA100540R1 |
| EAN / GTIN | 8056221006163 |
| Product type | Moulded case circuit breaker (MCCB) |
| Primary application | Generator, transformer and installation protection |
| Frame size | XT5 |
| Frame rating / rated uninterrupted current (Iu) | 630 A |
| Short-circuit performance level | H |
| Trip-unit rated current (In) | 500 A |
| Trip unit | TMG thermomagnetic release |
| Overload release setting | 350–500 A |
| Magnetic short-circuit setting | 1250–2500 A |
| Magnetic setting multiplier | 2.5–5 × In |
| Number of poles | 4 |
| Neutral rating | 100% of In |
| Mounting | Fixed |
| Terminal configuration | Front terminals |
| Rated operational voltage | up to 690 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 70 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 40 kA |
| Degree of protection | IP20 |
| Main circuit connection | Bolt connection |
| Standard | IEC / EN 60947-2 |
The ABB 1SDA100540R1 is a Tmax XT5H four-pole moulded case circuit breaker with a TMG thermomagnetic release designed particularly for generator protection as well as transformer and general low-voltage installation protection.
The circuit breaker has a rated uninterrupted current of 630 A and is fitted with a 500 A TMG thermomagnetic trip unit.
The thermal overload release is adjustable from 350–500 A, while the magnetic short-circuit protection is adjustable from 1250–2500 A, corresponding to 2.5–5 × In.
The 100% In designation indicates that the neutral is fully rated relative to the trip-unit current, making this four-pole breaker suitable for systems requiring a full-current neutral conductor.
The XT5H configuration provides an ultimate short-circuit breaking capacity of 70 kA at 415 V AC and 40 kA at 690 V AC.
ABB SACE Tmax XT moulded case circuit breakers combine compact construction, application-specific protection and robust fault interruption for generator, transformer and demanding industrial or commercial low-voltage power systems.