1SDA100024R1 ABB XT2N 160 Ekip Dip LSIG In=160A 4p FF In=100%

1SDA100024R1 ABB XT2N 160 Ekip Dip LSIG In=160A 4p FF In=100%

ABB 1SDA100024R1 is a fixed four-pole SACE Tmax XT2N moulded case circuit breaker rated at 160 A with front terminals, a 100% fully rated neutral and an Ekip Dip LSIG electronic trip unit providing overload, short-circuit and ground-fault protection.

SKU: 1SDA100024R1MPN: 1SDA100024R1
Price
List Price £2,013.64 ex VAT
Your Price (ex VAT) Save 25%
£1,510.23 25% OFF
You save £503.41 per unit
Manufacturer Lead Time Estimated Delivery 3 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,510.23
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,510.23

Why Choose the ABB XT2N 160 Ekip Dip LSIG In=160A 4p FF In=100% Circuit Breaker?

The ABB XT2N 160 Ekip Dip LSIG In=160A 4p FF In=100% 1SDA100024R1 is a 4-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range, designed for advanced protection of low-voltage AC power distribution systems. Built on the compact XT2 160 frame, it has a 160 A rated current and ABB's N short-circuit performance level.

Protection is provided by an Ekip Dip LSIG electronic trip unit, delivering long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. The electronic release also incorporates thermal memory and front LED fault indication, providing a versatile protection platform for industrial and commercial power distribution.

The breaker is supplied in a fixed, 4-pole configuration with front terminals and a 100% fully rated neutral. It is rated for operation up to 690 V AC with a rated insulation voltage of 1,000 V AC, while its N performance level provides an ultimate and service short-circuit breaking capacity of 36 kA at 415 V AC.

Key Advantages

  • Ekip Dip LSIG electronic protection for comprehensive circuit protection.
  • Provides long-time, short-time, instantaneous and ground-fault protection functions.
  • 160 A rated current in the compact XT2 frame.
  • 100% fully rated neutral for four-pole distribution applications.
  • 36 kA Icu and Ics at 415 V AC.
  • Front LEDs provide useful fault indication information.
  • Thermal memory supports effective overload protection.
  • Fixed construction with front terminals for straightforward switchboard integration.

Key Features

  • ABB SACE Tmax XT2N moulded case circuit breaker.
  • 160 A rated current (In).
  • 160 A rated uninterrupted current (Iu).
  • Ekip Dip LSIG solid-state electronic release.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Ground-fault protection (G).
  • 4-pole configuration with fully rated neutral.
  • Fixed circuit breaker version.
  • Front terminal connections.
  • Rated operational voltage: 690 V AC.
  • Rated frequency: 50/60 Hz.
  • Rated impulse withstand voltage: 8 kV.

Advanced Ekip Dip LSIG Electronic Protection

The Ekip Dip LSIG electronic trip unit provides four key protection functions within the breaker. The L function protects against sustained overloads, the S function provides selective short-time short-circuit protection, the I function responds to severe short-circuit faults, and the G function provides ground-fault protection.

The trip unit also incorporates thermal memory and front LED fault indication. Combined with the breaker's 160 A rating, 100% fully rated neutral and 36 kA Icu/Ics at 415 V AC, these capabilities make the 1SDA100024R1 a versatile protection solution for distribution systems requiring electronic fault protection and four-pole switching.

Typical Applications

  • Industrial low-voltage distribution boards.
  • Commercial power distribution systems.
  • Three-phase and neutral feeder protection.
  • Four-pole electrical distribution circuits.
  • Systems requiring ground-fault protection.
  • Machinery and industrial control panels.
  • OEM switchboards and electrical assemblies.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA100024R1
Product type Moulded case circuit breaker (MCCB)
Frame / subtype XT2
Short-circuit performance level N
Rated current (In) 160 A
Rated uninterrupted current (Iu) 160 A
Release Ekip Dip LSIG
Release type Electronic / solid-state
Protection functions L, S, I, G
Neutral rating 100% fully rated neutral
Number of poles 4
Version Fixed
Terminal connection Front
Current type AC
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V AC
Rated insulation voltage (Ui) 1,000 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated frequency 50/60 Hz
Ultimate breaking capacity (Icu) at 220–240 V AC 65 kA
Ultimate breaking capacity (Icu) at 380 V AC 36 kA
Ultimate breaking capacity (Icu) at 415 V AC 36 kA
Ultimate breaking capacity (Icu) at 440 V AC 36 kA
Ultimate breaking capacity (Icu) at 500 V AC 30 kA
Ultimate breaking capacity (Icu) at 525 V AC 20 kA
Ultimate breaking capacity (Icu) at 690 V AC 10 kA
Service breaking capacity (Ics) at 220–240 V AC 65 kA
Service breaking capacity (Ics) at 380 V AC 36 kA
Service breaking capacity (Ics) at 415 V AC 36 kA
Service breaking capacity (Ics) at 440 V AC 36 kA
Service breaking capacity (Ics) at 500 V AC 30 kA
Service breaking capacity (Ics) at 525 V AC 20 kA
Service breaking capacity (Ics) at 690 V AC 10 kA
Power loss at rated operating conditions per pole 10.80 W
Mechanical endurance 25,000 operations
Electrical endurance 8,000 operations
Standard IEC 60947-2
EAN 8056221000796

Frequently Asked Questions

What is the rated current of the ABB 1SDA100024R1?

The ABB 1SDA100024R1 has a rated current (In) and rated uninterrupted current (Iu) of 160 A.

What protection does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG electronic trip unit provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.

Does the ABB 1SDA100024R1 have a fully rated neutral?

Yes. This 4-pole version has a 100% fully rated neutral, as indicated by the ABB designation In=100%.

What is the breaking capacity of the ABB XT2N 1SDA100024R1 at 415 V AC?

At 415 V AC, the breaker has an ultimate short-circuit breaking capacity (Icu) of 36 kA and a service short-circuit breaking capacity (Ics) of 36 kA.

How is the ABB 1SDA100024R1 configured?

The 1SDA100024R1 is a fixed, 4-pole moulded case circuit breaker with front terminals, an Ekip Dip LSIG electronic release, a 160 A rated current and a 100% fully rated neutral.

Trusted ABB Electronic Circuit Protection

ABB SACE Tmax XT moulded case circuit breakers combine compact construction with advanced electronic protection, providing dependable overload, short-circuit and ground-fault protection for industrial, commercial and OEM low-voltage power distribution systems.