1SDA073696R1 ABB YU E1.2..E6.2-XT7-XT7M 48 VAC/DC Undervoltage Release

1SDA073696R1 ABB YU E1.2..E6.2-XT7-XT7M 48 VAC/DC Undervoltage Release

ABB 1SDA073696R1 YU E1.2..E6.2-XT7-XT7M is a 48 V AC/DC non-delayed undervoltage release for compatible SACE Emax 2 E1.2 through E6.2 and Tmax XT7/XT7M circuit breakers.

SKU: 1SDA073696R1MPN: 1SDA073696R1
Price
List Price £222.73 ex VAT
Your Price (ex VAT) Save 25%
£167.05 25% OFF
You save £55.68 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £167.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£167.05

Why Choose the ABB YU E1.2..E6.2 48 VAC/DC Undervoltage Release?

The ABB YU E1.2..E6.2 48 VAC/DC, order code 1SDA073696R1, is a 48 V AC/DC undervoltage release designed for compatible ABB SACE Emax 2 circuit breakers. The YU accessory provides fail-safe circuit-breaker control by acting on the operating mechanism when its continuously supplied control voltage is lost or falls sufficiently below the required operating level.

The accessory is suitable for ABB SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 circuit breakers and is also specified for compatible ABB Tmax XT7 and XT7M devices. Its 48 V AC/DC rating provides flexibility for installations using either AC or DC control circuits, with the AC rating applicable at both 50 Hz and 60 Hz.

Unlike a shunt opening release, which trips the breaker when an external voltage command is applied, the YU undervoltage release is intended for applications where breaker operation depends on the presence of its control supply. This makes the ABB 1SDA073696R1 particularly suitable for fail-safe control systems, emergency shutdown arrangements and installations where loss of control voltage must initiate circuit-breaker opening.

Key Advantages

  • Genuine ABB YU undervoltage release for compatible circuit breakers.
  • Rated for a 48 V AC/DC control supply.
  • Supports 48 V AC at 50 Hz and 60 Hz.
  • Supports 48 V DC control circuits.
  • Compatible with SACE Emax 2 E1.2 through E6.2 frame sizes.
  • Also suitable for compatible ABB Tmax XT7 and XT7M circuit breakers.
  • Provides fail-safe undervoltage operation when the control supply is interrupted.
  • Original ABB accessory designed for integration with specified ABB circuit-breaker platforms.

Key Features

  • ABB SACE Emax 2 electrical accessory.
  • Accessory type: Undervoltage release / undervoltage coil.
  • ABB designation: YU.
  • Rated voltage (Ur): 48 V.
  • Rated control supply voltage: 48 V AC/DC.
  • AC control frequency: 50/60 Hz.
  • Actuation voltage type: AC/DC.
  • Delayed operation: No.
  • Suitable for power circuit breakers: Yes.
  • Compatible with Emax 2 E1.2, E2.2, E4.2 and E6.2 frames.
  • Compatible with specified Tmax XT7 and XT7M circuit breakers.
  • ABB US/Canada part number: ZEAUC.

Fail-Safe Undervoltage Control for ABB Circuit Breakers

The ABB YU undervoltage release is designed to provide circuit-breaker control based on the availability of its control supply. The coil is continuously energised during normal operation, and interruption or sufficient reduction of this supply causes the release to act on the circuit-breaker mechanism. This principle makes the YU particularly useful where loss of control power must result in a safe circuit condition.

The 48 V AC/DC design provides flexibility for both alternating-current and direct-current control systems. Compatibility across Emax 2 frame sizes from E1.2 through E6.2 also allows a common undervoltage-release concept to be used across switchboards incorporating different ABB air circuit breaker frame sizes.

Typical Applications

  • Undervoltage control of ABB SACE Emax 2 air circuit breakers.
  • Fail-safe circuit-breaker opening systems.
  • Emergency shutdown and safety control circuits.
  • Industrial low-voltage switchboards.
  • Automated power distribution systems.
  • Generator and transformer distribution switchgear.
  • Control systems requiring breaker response to loss of control voltage.
  • Industrial, commercial and infrastructure power distribution.

Technical Specifications

Product designation YU E1.2..E6.2-XT7-XT7M 48 VAC/DC
Order code / MPN 1SDA073696R1
Product group Emax2 Air Circuit Breaker
Product type Undervoltage release / circuit-breaker accessory
Accessory designation YU
Rated voltage (Ur) 48 V
Rated control supply voltage AC at 50 Hz 48 V
Rated control supply voltage AC at 60 Hz 48 V
Rated control supply voltage DC 48 V
Actuation voltage type AC/DC
Delayed No
Suitable for power circuit breaker Yes
Compatible Emax 2 frames E1.2, E2.2, E4.2 and E6.2
Additional compatibility Tmax XT7 and XT7M
Product net width 105 mm
Product net height 55 mm
Product net depth 135 mm
Product net weight 0.12 kg
Minimum order quantity 1 piece
Customs tariff number 85389099
US/Canada part number ZEAUC
EAN 8015644776299
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA073696R1 used for?

The ABB 1SDA073696R1 is a YU undervoltage release designed for compatible ABB circuit breakers. It enables fail-safe operation by acting on the circuit-breaker mechanism when its continuously supplied control voltage is lost or falls sufficiently below the required level.

What is the control voltage of the ABB YU 1SDA073696R1?

The ABB YU 1SDA073696R1 is rated for a 48 V AC/DC control supply. Its AC rating applies at both 50 Hz and 60 Hz.

Which Emax 2 circuit breakers are compatible with ABB 1SDA073696R1?

The YU release is suitable for SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 circuit breakers. It is also specified for compatible Tmax XT7 and XT7M circuit breakers.

What is the difference between an ABB YU and YO release?

The YU is an undervoltage release that relies on a continuously available control supply for normal breaker operation, whereas the YO is a shunt opening release that initiates circuit-breaker opening when an external trip voltage is applied.

Is the ABB 1SDA073696R1 a delayed undervoltage release?

No. The ABB 1SDA073696R1 is specified as a non-delayed undervoltage release.

Trusted ABB Circuit Breaker Accessories

ABB SACE Emax 2 electrical accessories provide integrated control functionality for low-voltage circuit breakers, supporting dependable fail-safe operation, automation and switchboard control in industrial, commercial and infrastructure power distribution systems.