Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073460R1 E4.2N/MS 4000 four-pole fixed air switch disconnector with a 4000 A rated current, 690 V AC operational voltage and 66 kA 1-second short-time withstand capability for high-current low-voltage power distribution and isolation.
£17,496.84
The ABB E4.2N/MS 4000 4p FHR, order code 1SDA073460R1, is a high-current four-pole air switch disconnector from the ABB SACE Emax 2 range, designed for dependable switching and isolation in demanding low-voltage power distribution systems. Based on the E4.2 frame, this /MS version provides a substantial 4000 A rated uninterrupted current for major industrial, commercial and infrastructure electrical installations.
The E4.2N/MS performance level provides a rated short-time withstand current of 66 kA for 1 s, enabling the device to withstand high fault-current conditions while appropriately coordinated protective equipment provides automatic circuit protection. The /MS switch-disconnector configuration is designed to satisfy the isolation requirements of IEC 60947-3.
This model is supplied in a fixed four-pole configuration with horizontal rear terminals (FHR). With a rated operational voltage of 690 V AC, its high current capacity, robust Emax 2 construction and rear-connected arrangement make it particularly suitable for integration into high-power low-voltage switchboards.
ABB Emax 2 /MS switch disconnectors are designed for controlled switching and electrical isolation rather than automatic overcurrent protection. They provide a clear means of isolating sections of a low-voltage installation while dedicated protective equipment within the electrical system provides the required overload and short-circuit protection.
With its 4000 A continuous current rating and 66 kA 1-second short-time withstand capability, the E4.2N/MS is engineered for substantial power distribution loads. Its fixed four-pole design and horizontal rear connections make it particularly suitable for high-current switchboards where robust performance, dependable isolation and efficient busbar integration are required.
| Series | SACE Emax 2 |
|---|---|
| Order code | 1SDA073460R1 |
| EAN | 8015644773106 |
| Product type | Air switch disconnector |
| Frame | E4.2 |
| Performance level | N |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Rated operational voltage | 690 V AC |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Installation | Fixed |
| Terminal configuration | Horizontal rear terminals (FHR) |
| Power loss | 465 W |
| Isolation standard | IEC 60947-3 |
The ABB 1SDA073460R1 is an E4.2N/MS air switch disconnector designed for high-current switching and electrical isolation in low-voltage power distribution systems.
The E4.2N/MS 4000 has a rated uninterrupted current of 4000 A.
The E4.2N/MS 4000 has a rated short-time withstand current of 66 kA for 1 s.
The 1SDA073460R1 has a four-pole configuration, allowing four conductors to be switched and isolated together.
This model is supplied in a fixed configuration with horizontal rear terminals, making it suitable for permanent integration into high-current low-voltage switchboards.
ABB SACE Emax 2 switch disconnectors provide robust high-current switching and dependable electrical isolation for industrial, commercial and infrastructure power systems, with the E4.2N/MS platform engineered for demanding low-voltage distribution applications.
We use cookies