ABB 1SDA073337R1 Emax 2 E6.2H/f 5000 is a 5000 A four-pole withdrawable air circuit breaker moving part with Ekip G Touch LSIG electronic protection for generator and high-current power-distribution applications.
£37,902.47
The ABB E6.2H/f 5000 Ekip G Touch LSIG 4p WMP, order code 1SDA073337R1, is a high-current SACE Emax 2 withdrawable air circuit breaker moving part designed for generator protection and demanding low-voltage power-distribution systems. Part of the ABB Emax 2 E6.2 full-size range, this four-pole breaker combines a 5000 A rated continuous current, H-level breaking performance and an advanced Ekip G Touch LSIG electronic protection release.
The integrated Ekip G Touch LSIG trip unit provides long-time overload (L), selective short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection. The generator-oriented Ekip G Touch platform extends conventional LSIG protection with functions designed for the protection and supervision of generators and complex electrical networks, while its touchscreen interface provides convenient configuration and access to electrical measurements.
The E6.2H/f 5000 provides an ultimate short-circuit breaking capacity of 100 kA at 440 V AC and a rated short-time withstand current of 100 kA for 1 s. Its withdrawable moving-part construction is designed for use with the corresponding Emax 2 fixed part, while four changeover auxiliary contacts and breaker open/closed indication support integration with switchboard control and monitoring systems.
Air circuit breakers used with generators must provide dependable protection against overloads, short circuits and earth faults while supporting the coordination requirements of the wider electrical network. The Ekip G Touch LSIG release combines the fundamental L, S, I and G current-protection functions with generator-oriented protection and monitoring capabilities, making the 1SDA073337R1 suitable for power-generation and complex distribution applications.
The combination of a 5000 A continuous-current rating, 100 kA breaking performance and 100 kA short-time withstand capability makes the E6.2H/f suitable for substantial switchboards with high prospective fault currents. Its withdrawable construction also allows the breaker moving part to be isolated from the separately installed fixed section, supporting inspection, servicing and continuity strategies in critical power systems.
| Series | SACE Emax 2 E6.2 |
|---|---|
| ABB order code | 1SDA073337R1 |
| EAN | 8015644771874 |
| Product type | Air circuit breaker moving part |
| Frame configuration | E6.2H/f full size |
| Performance level | H |
| Rated continuous current (Iu) | 5000 A |
| Number of poles | 4 |
| Trip unit | Ekip G Touch LSIG |
| Release type | Solid-state electronic release |
| Protection functions | Long-time, short-time, instantaneous and earth fault (LSIG) |
| Overload release adjustment | 2000–5000 A |
| Short-time delayed short-circuit adjustment | 3000–50000 A |
| Instantaneous short-circuit adjustment | 7500–75000 A |
| Rated voltage | 690 V AC |
| Ultimate breaking capacity (Icu) at 400/415 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 100 kA |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Integrated earth-fault protection | Yes |
| Installation | Withdrawable |
| Construction | Moving part (WMP) |
| Auxiliary contacts | 4 changeover contacts |
| Circuit-breaker position indication | Open / closed |
| Motor operating mechanism | Optional |
| Fixed part | Ordered separately |
| Product weight | 148 kg |
The ABB 1SDA073337R1 is an Emax 2 E6.2H/f full-size withdrawable air circuit breaker moving part rated at 5000 A, with four poles and an Ekip G Touch LSIG electronic protection release.
The Ekip G Touch LSIG provides long-time overload (L), selective short-time short-circuit (S), instantaneous short-circuit (I) and earth-fault (G) protection, together with generator-oriented protection and monitoring functionality.
The E6.2H/f 5000 provides an ultimate short-circuit breaking capacity of 100 kA at 400/415 V AC and 100 kA at 690 V AC, with a rated short-time withstand current of 100 kA for 1 s.
Yes. The Ekip G Touch LSIG release includes integrated earth-fault protection in addition to long-time, short-time and instantaneous overcurrent protection.
It is a withdrawable moving part (WMP) designed for use with the corresponding ABB SACE Emax 2 fixed part. The fixed part is installed separately in the switchboard.
ABB SACE Emax 2 air circuit breakers with Ekip G protection combine high-current switching, comprehensive electronic protection and maintainable withdrawable construction to support dependable generator and low-voltage power-distribution systems.