ABB 1SDA073315R1 Emax 2 E6.2V/f 4000 Ekip Touch LSI four-pole withdrawable air circuit breaker with a 4000 A rated current, up to 150 kA breaking capacity and LSI electronic protection for high-current low-voltage power distribution.
£34,593.25
The ABB E6.2V/f 4000 Ekip Touch LSI 4p WMP, order code 1SDA073315R1, is a high-performance Emax 2 air circuit breaker (ACB) designed for protection and control of high-current low-voltage electrical distribution systems. As part of the advanced ABB Emax 2 series, this four-pole circuit breaker combines a 4000 A rated uninterrupted current with the Ekip Touch LSI electronic trip unit for advanced overload and short-circuit protection.
Designed for demanding industrial, commercial and infrastructure power distribution applications, the E6.2V/f provides exceptionally high fault-current interruption capability together with configurable electronic protection. The Ekip Touch LSI trip unit provides long-time overload (L), selective short-circuit (S) and instantaneous short-circuit (I) protection, with a touchscreen interface for straightforward configuration, monitoring and protection management.
With a rated uninterrupted current of 4000 A, an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC and 100 kA at 690 V AC, the E6.2V/f 4000 is engineered for high-capacity switchboards and critical electrical distribution systems. This WMP version is supplied as the withdrawable moving part and is designed for integration with a compatible ABB Emax 2 fixed part.
Air circuit breakers such as the ABB Emax 2 E6.2 are used to protect high-current low-voltage electrical networks against overloads and potentially damaging short-circuit currents. The E6.2V/f combines a very high breaking capacity with advanced electronic protection, making it particularly suitable for main incomers, bus couplers and high-current feeder circuits where dependable interruption of severe fault currents is essential.
The Ekip Touch LSI trip unit provides three fundamental protection functions: long-time overload protection (L), selective short-circuit protection (S) and instantaneous short-circuit protection (I). The selective short-circuit function supports coordinated protection between upstream and downstream devices, while the touchscreen interface simplifies configuration and monitoring within modern electrical distribution systems.
| Series | Emax 2 |
|---|---|
| Order code / MPN | 1SDA073315R1 |
| Product type | Air circuit breaker |
| Product group | Emax 2 Air Circuit Breaker |
| Frame | E6.2 |
| Short-circuit performance level | V |
| Rated uninterrupted current (Iu) | 4000 A |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSI |
| Release type | Electronic |
| Protection functions | L, S, I |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 150 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 100 kA |
| Service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw), 1 s | 100 kA |
| Rated short-time withstand current (Icw), 3 s | 100 kA |
| Auxiliary contacts | 4 changeover contacts (4Q) |
| Trip indication contact | S51 |
| Suitable for IT networks | Yes, up to 690 V |
| Installation | Withdrawable |
| Execution | Moving part (WMP) |
| Fixed part | Ordered separately |
| Standard | IEC |
The ABB 1SDA073315R1 is an Emax 2 E6.2V/f air circuit breaker designed to protect and control high-current low-voltage electrical distribution systems in industrial, commercial and infrastructure applications.
This Emax 2 air circuit breaker has a rated uninterrupted current of 4000 A, making it suitable for high-capacity power distribution applications.
The Ekip Touch LSI electronic trip unit provides long-time overload (L), selective short-circuit (S) and instantaneous short-circuit (I) protection, together with a touchscreen interface for configuration and monitoring.
The E6.2V/f 4000 provides an ultimate short-circuit breaking capacity of 150 kA at 400/415/440 V AC, 130 kA at 500/525 V AC and 100 kA at 690 V AC.
The 1SDA073315R1 is a withdrawable moving-part (WMP) circuit breaker designed for integration with a compatible ABB Emax 2 fixed part, which is ordered separately.
ABB Emax 2 air circuit breakers are engineered for demanding low-voltage power distribution applications, combining very high breaking performance, advanced electronic circuit protection and flexible withdrawable switchboard integration.
We use cookies