ABB 1SDA073102R1 E4.2V 2500 Ekip Dip LSI 4p WMP is a 2500 A four-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Dip LSI electronic protection and 150 kA breaking capacity at 400 V AC.
£15,728.15
The ABB E4.2V 2500 Ekip Dip LSI 4p WMP, order code 1SDA073102R1, is a high-performance four-pole air circuit breaker (ACB) moving part from the ABB SACE Emax 2 range, designed for protection and switching in demanding low-voltage power distribution systems. With a rated uninterrupted current of 2500 A, it provides robust circuit protection for high-current industrial, commercial, infrastructure and critical-power switchboards.
This E4.2V breaker is equipped with an Ekip Dip LSI electronic trip unit, providing long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection. The addition of adjustable short-time protection supports selective coordination between upstream and downstream protective devices, helping isolate faults while maintaining continuity elsewhere in the electrical distribution system.
The V performance level provides exceptionally high short-circuit capability, with a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC and a rated short-time withstand current of 100 kA for 1 s. Its four-pole WMP configuration uses ABB's withdrawable architecture, allowing the moving part to connect through a separate chassis for service-friendly installation in high-availability switchboards.
Air circuit breakers such as the ABB E4.2V protect high-current electrical distribution circuits against potentially damaging overload and short-circuit conditions. The Ekip Dip LSI electronic release combines long-time, short-time and instantaneous protection functions, allowing different levels of overcurrent to be detected and cleared according to the configured protection characteristics.
The E4.2V is particularly suited to installations with very high prospective fault currents. Its 150 kA breaking capacity at 400 V AC and 100 kA short-time withstand capability for 1 s provide robust fault-handling performance, while the short-time protection function assists with selective coordination and the withdrawable Emax 2 architecture supports efficient switchboard maintenance.
| Series | SACE Emax 2 |
|---|---|
| ABB order code | 1SDA073102R1 |
| Product type | Air circuit breaker moving part |
| Frame | E4.2 |
| Performance level | V |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 150 kA |
| Rated short-time withstand current (Icw) for 1 s | 100 kA |
| Number of poles | 4 |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | Long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) |
| Minimum overload release setting | 1000 A |
| Minimum short-time delayed short-circuit setting | 1500 A |
| Minimum instantaneous short-circuit setting | 3750 A |
| Integrated earth-fault protection | No |
| Construction | Withdrawable / draw-out moving part |
| Main-circuit connection | Connection at separate chassis part |
| Control element | Push button |
| Auxiliary change-over contacts | 4 |
| Switched-off indication | Yes |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP30 |
| Net weight | 74 kg |
The ABB 1SDA073102R1 is a 2500 A four-pole Emax 2 air circuit breaker moving part designed for high-current switching and protection in demanding low-voltage power distribution systems.
It is fitted with an Ekip Dip LSI electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E4.2V 2500 has a rated ultimate short-circuit breaking capacity of 150 kA at 400 V AC, providing very high fault-breaking capability for demanding power distribution systems.
The LSI protection functions provide long-time overload, short-time short-circuit and instantaneous short-circuit protection, with the short-time function helping support selective coordination between protective devices.
Yes. This WMP product uses a withdrawable moving-part construction with connection at a separate chassis part, supporting convenient inspection, servicing and replacement in compatible switchboards.
ABB SACE Emax 2 air circuit breakers combine configurable electronic protection, exceptional short-circuit performance and service-friendly withdrawable construction for dependable high-current power distribution in demanding industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.