Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA073041R1 E2.2N 2500 Ekip Dip LI 4p WMP is a 2500 A four-pole withdrawable Emax 2 air circuit breaker moving part with adjustable long-time and instantaneous electronic protection for high-current low-voltage power distribution systems.
£10,597.47
The ABB E2.2N 2500 Ekip Dip LI 4p WMP, order code 1SDA073041R1, is a four-pole air circuit breaker moving part from the ABB SACE Emax 2 range, designed for protection, switching and isolation in high-current low-voltage power distribution systems. It combines a 2500 A rated uninterrupted current with the E2.2N performance level for demanding industrial, commercial and infrastructure installations.
This Emax 2 moving part incorporates the Ekip Dip LI solid-state electronic trip unit, providing long-time overload and instantaneous short-circuit protection. Protection settings are configured using DIP switches, providing a straightforward electronic protection solution for distribution circuits where dedicated ground-fault or short-time delayed protection is not required.
The E2.2N 2500 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380–690 V AC, a rated short-time withstand current of 66 kA for 1 s and a rated operational voltage of 690 V AC. Its four-pole withdrawable moving-part (WMP) construction is designed for use with the corresponding Emax 2 fixed part, supporting convenient isolation, inspection and servicing within maintainable switchgear assemblies.
The ABB SACE Emax 2 E2.2N platform provides switching, isolation and electronic overcurrent protection for high-current low-voltage distribution circuits. With a 2500 A rated uninterrupted current, 66 kA ultimate short-circuit breaking capacity across 380–690 V AC and 66 kA short-time withstand current for 1 s, this configuration is suitable for demanding main switchboards and feeder applications.
The Ekip Dip LI trip unit combines adjustable long-time protection against sustained overload conditions with instantaneous protection against severe short circuits. Its DIP-switch configuration provides straightforward protection adjustment, while the withdrawable Emax 2 architecture facilitates isolation and maintenance in installations where serviceability and continuity of operation are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA073041R1 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | N |
| Rated uninterrupted current (Iu) | 2500 A |
| Number of poles | 4 |
| Neutral pole | 100% rated current |
| Trip unit | Ekip Dip LI |
| Release type | Solid-state electronic |
| Protection functions | Long-time (L), instantaneous (I) |
| Long-time protection setting | 0.4–1 × In |
| Long-time overload adjustment range | 1000–2500 A |
| Instantaneous protection setting | 1.5–15 × In |
| Instantaneous short-circuit adjustment range | 3750–37500 A |
| Protection adjustment method | DIP switches |
| Integrated earth-fault protection | No |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500/525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50/60 Hz |
| Current type | AC |
| Auxiliary changeover contacts | 4 |
| Circuit-breaker position indication | Open/closed |
| Integrated undervoltage release | No |
| Integrated motor drive | No |
| Optional motor drive | Yes |
| Degree of protection | IP30 |
| Main circuit connection | Connection at separate chassis part |
| Standard | IEC 60947-2 |
| Execution | Withdrawable |
| Configuration | Moving part of withdrawable circuit breaker (WMP) |
The ABB 1SDA073041R1 is a 2500 A four-pole air circuit breaker moving part used for protection, switching and isolation in high-current low-voltage industrial, commercial and infrastructure power distribution systems.
The ABB E2.2N 2500 has a rated uninterrupted current of 2500 A, with the four-pole E2.2 configuration providing a neutral pole rated at 100% current.
The Ekip Dip LI electronic trip unit provides adjustable long-time overload protection from 0.4–1 × In and instantaneous short-circuit protection from 1.5–15 × In, with settings configured using DIP switches.
The E2.2N 2500 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380, 400/415, 440, 500/525 and 690 V AC, together with a rated short-time withstand current of 66 kA for 1 s.
Yes. The 1SDA073041R1 is the four-pole withdrawable moving part (WMP) of an ABB SACE Emax 2 E2.2N 2500 air circuit breaker and is designed for use with the corresponding withdrawable fixed part.
ABB SACE Emax 2 air circuit breakers combine high-current low-voltage switching and protection with electronic trip technology, while the Ekip Dip LI release provides adjustable overload and instantaneous short-circuit protection for demanding electrical distribution systems.
We use cookies