Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072912R1 E2.2S 1000 Ekip Dip LSI 4p WMP is a 1000 A four-pole withdrawable Emax 2 air circuit breaker moving part with electronic long-time, short-time and instantaneous protection for low-voltage power distribution systems.
£6,358.51
The ABB E2.2S 1000 Ekip Dip LSI 4p WMP, order code 1SDA072912R1, is a high-performance four-pole air circuit breaker (ACB) moving part designed for protection, switching and isolation in low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 series, it combines a 1000 A rated uninterrupted current with electronic overcurrent protection for demanding industrial, commercial and infrastructure power distribution applications.
This Emax 2 circuit breaker is equipped with the Ekip Dip LSI solid-state electronic trip unit, providing long-time, short-time and instantaneous overcurrent protection. These protection functions enable effective overload and short-circuit protection while supporting selective coordination with other protective devices within the electrical distribution system.
The E2.2S 1000 provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and a rated short-time withstand current of 66 kA for 1 s. Its four-pole withdrawable moving-part (WMP) construction is designed for use with the corresponding Emax 2 fixed part, facilitating isolation, inspection, servicing and replacement in critical power distribution systems.
Air circuit breakers such as the ABB Emax 2 E2.2S provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The E2.2S performance level combines high short-circuit breaking capacity with substantial short-time withstand capability, helping protect switchboards, conductors and downstream electrical equipment during overload and fault conditions.
The Ekip Dip LSI trip unit provides electronic long-time protection against sustained overloads, short-time protection that supports selective coordination between protective devices and instantaneous protection against severe short circuits. Combined with the withdrawable Emax 2 architecture, these functions make the breaker particularly suitable for installations where protection coordination, high fault-breaking performance, system availability and straightforward maintenance are important.
| Series | SACE Emax 2 |
|---|---|
| Order code / MPN | 1SDA072912R1 |
| EAN | 8015644767624 |
| Product type | Air circuit breaker moving part |
| Product group | Emax2 Air Circuit Breaker |
| Frame | E2.2 |
| Performance level | S |
| Rated current (In) | 1000 A |
| Rated uninterrupted current (Iu) | 1000 A |
| Number of poles | 4 |
| Neutral pole current | 100% Iu |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | Long-time (L), short-time (S), instantaneous (I) |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) at 400–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 66 kA |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw), 1 s | 66 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Current type | AC |
| Connecting capacity | 600 mm² |
| Power loss | 113 W |
| Electrical durability | 15,000 cycles |
| Mechanical durability | 25,000 cycles |
| Execution | Withdrawable |
| Configuration | Moving part of withdrawable circuit breaker (WMP) |
| Weight | approx. 55 kg |
The ABB 1SDA072912R1 is a 1000 A four-pole air circuit breaker moving part used for protection, switching and isolation in low-voltage industrial, commercial and infrastructure power distribution systems.
The E2.2S 1000 has a rated uninterrupted current of 1000 A.
The Ekip Dip LSI trip unit provides long-time overload protection, short-time short-circuit protection and instantaneous short-circuit protection.
The E2.2S provides a rated ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC, with a rated short-time withstand current of 66 kA for 1 s.
Yes. The 1SDA072912R1 is the four-pole withdrawable moving part (WMP) of an ABB SACE Emax 2 E2.2S 1000 air circuit breaker and is designed for use with the corresponding fixed part.
ABB SACE Emax 2 air circuit breakers are designed for dependable protection, switching and management of low-voltage power distribution systems, combining high electrical performance with flexible electronic protection technology.