ABB 1SDA072872R1 is an Emax 2 E2.2N 800 A four-pole withdrawable air circuit breaker moving part with an Ekip Dip LSI solid-state trip unit providing overload and short-circuit protection for low-voltage power distribution systems.
£5,686.10
The ABB 1SDA072872R1 is a high-performance Emax 2 E2.2N 800 A four-pole air circuit breaker moving part designed for protection and control in low-voltage electrical distribution systems. As part of the advanced ABB SACE Emax 2 air circuit breaker series, it combines robust withdrawable construction with the reliable Ekip Dip LSI solid-state electronic trip unit.
This E2.2N circuit breaker is engineered for demanding industrial, commercial and infrastructure power distribution applications. The Ekip Dip LSI release provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, helping protect electrical circuits and connected equipment against sustained overcurrents and severe fault conditions.
With a rated current of 800 A, a four-pole configuration and an ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, the 1SDA072872R1 provides dependable protection across a wide range of low-voltage distribution systems. Its withdrawable moving-part design enables integration with the appropriate Emax 2 E2.2 fixed part and supports efficient inspection, servicing and replacement within switchgear assemblies.
Air circuit breakers such as the ABB Emax 2 E2.2N provide switching, isolation and protection for high-current low-voltage distribution circuits. They are commonly used in main switchboards and industrial distribution systems where high short-circuit performance and dependable protection are essential for maintaining electrical safety and system availability.
The Ekip Dip LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. The addition of short-time protection allows greater flexibility when coordinating upstream and downstream protective devices, while the E2.2N frame's high breaking capacity and withdrawable architecture make the 1SDA072872R1 well suited to demanding power distribution and switchgear applications.
| Series | SACE Emax 2 |
|---|---|
| Frame | E2.2 |
| Performance level | N |
| ABB order code / MPN | 1SDA072872R1 |
| Product type | Air circuit breaker moving part |
| Rated current | 800 A |
| Rated uninterrupted current | 800 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V AC |
| Rated impulse withstand voltage | 12 kV |
| Number of poles | 4 |
| Neutral pole current | 100% of rated current |
| Trip unit | Ekip Dip LSI |
| Trip unit type | Solid-state electronic release |
| Protection functions | LSI – long-time overload, short-time short-circuit and instantaneous short-circuit protection |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 525 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated service short-circuit breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw, 1 s) | 66 kA |
| Rated short-time withstand current (Icw, 3 s) | 50 kA |
| Current type | AC |
| Execution | Withdrawable moving part (WMP) |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 72 W |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability | 15,000 operating cycles |
| Dimensions (H × W × D) | 425 × 407 × 383 mm |
| Weight | 49 kg |
| Standard | IEC 60947-2 |
| EAN | 8015644767228 |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA072872R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure applications.
The E2.2N 800 has a rated current of 800 A and is supplied in a four-pole configuration.
The Ekip Dip LSI solid-state electronic trip unit provides long-time overload protection (L), short-time short-circuit protection (S) and instantaneous short-circuit protection (I).
The E2.2N 800 has an ultimate short-circuit breaking capacity of 66 kA at 400–690 V AC, with a rated short-time withstand current of 66 kA for 1 s and 50 kA for 3 s.
The 1SDA072872R1 is the withdrawable moving part (WMP) of an ABB Emax 2 circuit-breaker system and is designed for installation with the appropriate E2.2 fixed part.
ABB SACE Emax 2 air circuit breakers provide dependable protection and control for modern low-voltage power distribution systems, combining high short-circuit performance, intelligent electronic protection and flexible withdrawable switchgear integration.