Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072182R1 E1.2C 1250 Ekip Dip LSI 3p WMP is a 1250 A three-pole withdrawable SACE Emax 2 air circuit breaker moving part with Ekip Dip LSI electronic overload and short-circuit protection.
£3,144.85
The ABB E1.2C 1250 Ekip Dip LSI 3p WMP, order code 1SDA072182R1, is a high-performance three-pole withdrawable air circuit breaker moving part from the ABB SACE Emax 2 range, designed for reliable protection and switching in low-voltage electrical distribution systems. Rated at 1250 A, it combines the compact E1.2C frame with an Ekip Dip LSI electronic trip unit for adjustable overload and short-circuit protection.
The Ekip Dip LSI solid-state release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. Its straightforward adjustment system allows protection thresholds to be configured for the installation, helping safeguard conductors, switchgear and connected equipment while supporting selective coordination within industrial and commercial distribution networks.
This version is a three-pole withdrawable moving part with a 1250 A rated uninterrupted current. The E1.2C performance class provides a breaking capacity of 50 kA at 400 V AC, while its withdrawable construction, four auxiliary contacts and open/closed position indication support dependable switchboard operation and convenient maintenance.
ABB SACE Emax 2 air circuit breakers are engineered to provide reliable switching and fault protection in low-voltage electrical networks. The compact E1.2 platform combines high current capability with strong short-circuit performance, helping switchboard manufacturers create efficient distribution systems for industrial, commercial and infrastructure installations.
The Ekip Dip LSI release adds short-time delayed protection to the long-time overload and instantaneous functions, enabling improved protection coordination compared with a basic LI release. Combined with the withdrawable Emax 2 construction, it provides a practical solution for switchboards where selective protection, straightforward configuration and convenient maintenance are important.
| Series | SACE Emax 2 |
|---|---|
| Frame | E1.2C |
| ABB order code | 1SDA072182R1 |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip Dip LSI |
| Protection functions | Long-time, short-time and instantaneous |
| Overload release setting range | 500–1250 A |
| Short-time delayed short-circuit setting range | 750–12500 A |
| Rated voltage | 690 V AC |
| Breaking capacity at 400 V AC | 50 kA |
| Installation | Withdrawable / draw-out moving part |
| Auxiliary contacts | 4 |
| Mechanical durability | 20,000 cycles |
| Electrical durability at ≤440 V | 8,000 cycles |
| Electrical durability at 500–690 V | 6,500 cycles |
| Product net width | 278 mm |
| Product net height | 363.5 mm |
| Product net depth | 271 mm |
| Product net weight | 14 kg |
| EAN | 8015644760328 |
The ABB 1SDA072182R1 is a 1250 A three-pole withdrawable Emax 2 air circuit breaker moving part used for switching and protecting low-voltage electrical distribution systems.
It is fitted with an ABB Ekip Dip LSI electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
This version has a rated uninterrupted current of 1250 A, with the overload release adjustable from 500–1250 A.
The E1.2C 1250 provides a breaking capacity of 50 kA at 400 V AC.
The 1SDA072182R1 is the withdrawable moving-part version, designed for use with the appropriate Emax 2 fixed switchboard section.
ABB SACE Emax 2 air circuit breakers combine compact construction, dependable electronic protection and flexible installation options for reliable switching and protection in demanding low-voltage power distribution systems.