Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072092R1 Emax 2 E1.2B 800 three-pole withdrawable air circuit breaker moving part with an 800 A rated current, 42 kA breaking capacity at 440 V AC and Ekip Dip LSI electronic protection.
£2,603.15
The ABB E1.2B 800 Ekip Dip LSI 3p WMP, order code 1SDA072092R1, is a withdrawable Emax 2 air circuit breaker (ACB) designed for reliable protection and switching in low-voltage electrical distribution systems. As part of the ABB SACE Emax 2 series, this three-pole moving part combines an 800 A rated uninterrupted current with an Ekip Dip LSI electronic trip unit for comprehensive overload and short-circuit protection.
The compact E1.2B platform is designed for industrial and commercial switchboards requiring dependable performance and efficient use of panel space. Its Ekip Dip LSI solid-state release provides long-time, short-time and instantaneous protection functions, allowing the breaker to respond appropriately to sustained overloads as well as delayed and severe short-circuit conditions.
With a rated uninterrupted current of 800 A, a three-pole configuration, an ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s, the E1.2B 800 is suited to demanding distribution applications. The WMP withdrawable moving-part configuration is designed for use with the corresponding Emax 2 fixed part, supporting convenient isolation, testing and maintenance.
Air circuit breakers such as the ABB Emax 2 E1.2B provide switching, isolation and protection for important circuits within low-voltage electrical distribution systems. The combination of an 800 A current rating and 42 kA short-circuit performance makes this model suitable for incoming supplies, distribution feeders and other applications requiring dependable fault interruption.
The Ekip Dip LSI trip unit adds short-time protection to the long-time and instantaneous functions, making it particularly useful where selective coordination between upstream and downstream protective devices is required. Long-time protection responds to sustained overloads, short-time protection provides controlled response to short-circuit conditions, and instantaneous protection rapidly interrupts severe faults. Together with the withdrawable construction, these capabilities provide a practical solution for maintainable and coordinated distribution switchboards.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 |
| ABB order code | 1SDA072092R1 |
| Product type | Air circuit breaker moving part |
| Frame | E1.2 |
| Performance level | B |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage (Ue) | up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Frequency | 50 / 60 Hz |
| Ultimate short-circuit breaking capacity (Icu) | 42 kA at 440 V AC |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic / solid-state |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload protection adjustment | 0.4–1 × In |
| Short-time protection | Adjustable |
| Instantaneous protection adjustment | 1.5–15 × In |
| Execution | Withdrawable moving part (WMP) |
| Standard | IEC 60947-2 |
| Application | Low-voltage power distribution and circuit protection |
The ABB 1SDA072092R1 is an Emax 2 air circuit breaker moving part designed for switching and protecting three-phase low-voltage electrical distribution circuits in industrial and commercial switchboards.
The circuit breaker has a rated uninterrupted current of 800 A.
The breaker uses an Ekip Dip LSI electronic trip unit providing long-time, short-time and instantaneous protection against overload and short-circuit conditions.
The E1.2B 800 has an ultimate short-circuit breaking capacity of 42 kA at 440 V AC and a rated short-time withstand current of 42 kA for 1 s.
WMP identifies the withdrawable moving part of the circuit breaker, designed for installation with the corresponding fixed part in an ABB Emax 2 withdrawable switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine dependable low-voltage circuit protection with electronic trip technology, selective protection capabilities and flexible withdrawable switchgear integration for modern industrial and commercial power distribution systems.