Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA072077R1 is a SACE Emax 2 E1.2N 630 A three-pole withdrawable air circuit breaker moving part with Ekip G Touch LSIG electronic generator protection, a 690 V AC rating and 66 kA ultimate short-circuit breaking capacity at 400–440 V AC.
£6,936.74
The ABB E1.2N 630 Ekip G Touch LSIG 3p WMP, order code 1SDA072077R1, is a high-performance SACE Emax 2 air circuit breaker moving part designed for generator and low-voltage power distribution protection. Rated at 630 A, this three-pole unit incorporates the Ekip G Touch LSIG electronic release and is designed for use with the appropriate fixed part in a withdrawable Emax 2 installation.
The Ekip G Touch LSIG release combines long-time, short-time, instantaneous and ground-fault protection with generator-oriented protection and monitoring capabilities. This makes the breaker particularly suitable for generating sets, generator switchboards and critical distribution systems requiring precise electronic protection and dependable fault interruption.
The E1.2N performance level provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC, a 50 kA service breaking capacity and a 50 kA short-time withstand current for 1 second. Its withdrawable moving-part configuration supports convenient isolation, inspection and maintenance in compatible ABB SACE Emax 2 switchgear.
ABB SACE Emax 2 air circuit breakers combine dependable fault interruption with intelligent electronic protection and power-management capabilities. The Ekip G Touch LSIG release is suited to generator applications while providing comprehensive protection against overloads, delayed and instantaneous short circuits and ground faults.
With its 630 A rating, 66 kA maximum breaking capacity and withdrawable moving-part configuration, the 1SDA072077R1 is particularly suitable for generator switchboards, power-generation installations and critical distribution systems where advanced protection, high availability and convenient maintenance access are required.
| Series | SACE Emax 2 E1.2N |
|---|---|
| Order code | 1SDA072077R1 |
| EAN | 8015644759278 |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 630 A |
| Rated current (In) | 630 A |
| Number of poles | 3 |
| Current type | AC |
| Trip unit | Ekip G Touch LSIG |
| Release type | Electronic |
| Protection functions | LSIG – long-time, short-time, instantaneous and ground-fault |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400–440 V AC | 66 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 50 kA |
| Service short-circuit breaking capacity (Ics) | 50 kA |
| Rated short-time withstand current (Icw), 1 s | 50 kA |
| Rated short-time withstand current (Icw), 3 s | 30 kA |
| Integrated earth-fault protection | Yes |
| Execution | Moving part for withdrawable installation |
| Main circuit connection | Connection at separate chassis part |
| Auxiliary contacts | 4 change-over contacts |
| Switched-off indicator | Yes |
| Motor drive | Optional |
| Degree of protection | IP30 |
| Power loss | 62 W |
| Mechanical durability | 20,000 operating cycles |
| Electrical durability | 8,000 operating cycles |
| Dimensions (W × H × D) | 278 × 363.5 × 271 mm |
| Net weight | 14 kg |
| Standards | IEC 60947-2 |
It is the moving part of an ABB SACE Emax 2 E1.2N 630 three-pole air circuit breaker, equipped with an Ekip G Touch LSIG electronic release for generator and power distribution protection.
The circuit breaker moving part has a rated uninterrupted current of 630 A and a rated operational voltage of 690 V AC.
The Ekip G Touch LSIG release provides long-time, short-time, instantaneous and ground-fault protection, together with generator-oriented protection and monitoring capabilities.
The E1.2N 630 provides an ultimate short-circuit breaking capacity of 66 kA at 400–440 V AC and a rated short-time withstand current of 50 kA for 1 second.
WMP identifies the product as the moving part for a withdrawable circuit-breaker installation, intended for use with the appropriate ABB SACE Emax 2 fixed part.
ABB SACE Emax 2 air circuit breakers combine dependable switching, advanced generator protection and intelligent power-management capabilities for modern power generation, industrial and critical infrastructure systems.