1SDA072053R1 ABB Emax 2 E1.2B 630 Ekip Dip LSIG 3-Pole Withdrawable Air Circuit Breaker

1SDA072053R1 ABB Emax 2 E1.2B 630 Ekip Dip LSIG 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA072053R1 is an Emax 2 E1.2B 630 A three-pole withdrawable air circuit breaker moving part with an Ekip Dip LSIG electronic trip unit for overload, short-circuit and earth-fault protection.

SKU: 1SDA072053R1MPN: 1SDA072053R1
Price
List Price £3,771.83 ex VAT
Your Price (ex VAT) Save 25%
£2,828.87 25% OFF
You save £942.96 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,828.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,828.87

Why Choose the ABB 1SDA072053R1 Emax 2 Air Circuit Breaker?

The ABB 1SDA072053R1 is a high-performance Emax 2 E1.2B air circuit breaker designed for protection, switching and isolation in low-voltage electrical distribution systems. This three-pole withdrawable circuit breaker has a rated uninterrupted current of 630 A and incorporates an Ekip Dip LSIG electronic trip unit providing long-time, short-time, instantaneous and earth-fault protection.

As part of the advanced ABB Emax 2 series, the E1.2 platform combines compact dimensions with dependable protection for industrial, commercial and infrastructure switchboards. The B performance level provides a rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC, while the Ekip Dip electronic release allows the protection characteristics to be configured for the requirements of the connected distribution system.

The E1.2B 630 Ekip Dip LSIG 3p WMP is the moving part of a withdrawable circuit-breaker system and connects to the main circuit through its separate fixed chassis. This arrangement supports maintainable switchboard designs where the breaker can be isolated and withdrawn without removing the complete fixed portion from the installation.

Key Advantages

  • Compact 630 A Emax 2 air circuit breaker for low-voltage distribution applications.
  • Three-pole configuration for three-phase electrical systems.
  • Ekip Dip LSIG electronic trip unit provides long-time, short-time, instantaneous and earth-fault protection.
  • Rated ultimate short-circuit breaking capacity of 42 kA at 400 V AC.
  • Withdrawable moving-part execution supports convenient switchboard isolation and maintenance.
  • Four change-over auxiliary contacts provide circuit-breaker status signalling.

Key Features

  • ABB Emax 2 E1.2B series.
  • 630 A rated uninterrupted current.
  • Three-pole construction.
  • Ekip Dip LSIG electronic protection release.
  • Long-time overload, short-time, instantaneous and integrated earth-fault protection.
  • 690 V rated voltage.
  • 42 kA ultimate short-circuit breaking capacity at 400 V AC.
  • Adjustable overload protection from 252–630 A.
  • Withdrawable moving-part configuration for use with a separate fixed chassis.
  • Four change-over auxiliary contacts and switched-off indication.

Reliable Protection for Low-Voltage Distribution Systems

Air circuit breakers such as the ABB Emax 2 E1.2 protect low-voltage distribution systems against overloads, short circuits and earth faults while providing dependable switching and isolation. The Ekip Dip LSIG electronic release monitors circuit current and provides long-time, short-time, instantaneous and earth-fault protection to help safeguard cables, busbars, transformers and connected electrical equipment.

The withdrawable E1.2 platform is particularly useful in switchboards where serviceability and operational flexibility are important. The moving circuit breaker can interface with a separate fixed chassis, allowing the breaker to be disconnected and withdrawn for inspection or maintenance while the fixed switchboard connections remain installed.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Transformer secondary protection.
  • Distribution feeder protection.
  • Commercial and infrastructure electrical systems.
  • Manufacturing and process-industry switchgear.

Technical Specifications

Series Emax 2
ABB order code 1SDA072053R1
Product type Air circuit breaker
Frame E1.2
Performance level B
Rated uninterrupted current 630 A
Rated voltage 690 V
Number of poles 3
Trip unit Ekip Dip LSIG
Protection functions L, S, I, G
Overload release adjustment range 252–630 A
Short-time delayed short-circuit adjustment range 378–6300 A
Instantaneous short-circuit adjustment range 945–9450 A
Integrated earth-fault protection Yes
Ultimate short-circuit breaking capacity 42 kA at 400 V, 50 Hz
Execution Withdrawable moving part
Main circuit connection Through separate chassis part
Auxiliary contacts 4 change-over contacts
Switched-off indicator Yes
Protection rating IP30

Frequently Asked Questions

What is the ABB 1SDA072053R1?

The ABB 1SDA072053R1 is an Emax 2 E1.2B three-pole withdrawable air circuit breaker moving part rated at 630 A and equipped with an Ekip Dip LSIG electronic trip unit.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG release provides long-time (L), short-time (S), instantaneous (I) and earth-fault (G) protection functions.

What is the breaking capacity of the ABB E1.2B 630?

The E1.2B configuration has a rated ultimate short-circuit breaking capacity of 42 kA at 400 V, 50 Hz.

Is the ABB 1SDA072053R1 fixed or withdrawable?

The 1SDA072053R1 is a withdrawable moving-part circuit breaker designed to connect to the main electrical circuit through a compatible separate fixed chassis.

Does the ABB 1SDA072053R1 provide earth-fault protection?

Yes. Its Ekip Dip LSIG trip unit includes integrated earth-fault protection in addition to overload and short-circuit protection.

Trusted by Electrical Distribution Professionals Worldwide

ABB Emax 2 air circuit breakers are widely used in industrial, commercial and infrastructure electrical systems where dependable switching, configurable electronic protection and maintainable low-voltage distribution equipment are required.