ABB 1SDA071994R1 is an Emax 2 E6.2V/f 5000 A fixed four-pole air circuit breaker with a full-size neutral, rear horizontal terminals and an Ekip Touch LI electronic trip unit for high-current low-voltage distribution protection.
£38,326.38
The ABB 1SDA071994R1 is a high-performance Emax 2 E6.2V/f air circuit breaker designed for protection, switching and isolation in high-current low-voltage electrical distribution systems. This fixed four-pole circuit breaker has a rated current of 5000 A and incorporates an advanced Ekip Touch LI electronic trip unit providing long-time overload and instantaneous short-circuit protection.
As part of the ABB Emax 2 series, the E6.2V/f platform is engineered for demanding industrial, commercial and infrastructure switchboards where high interrupting performance and dependable system protection are essential. The V performance level provides an ultimate short-circuit breaking capacity of up to 150 kA at 415 V AC, while the Ekip Touch release provides an intuitive interface for configuring and monitoring circuit protection.
The E6.2V/f 5000 Ekip Touch LI 4p FHR is supplied in a fixed configuration with four poles, a full-size neutral and rear horizontal terminals. Its 690 V AC rated operational voltage and high-current construction make it particularly suitable for main incomers, transformer protection and major distribution feeders in large low-voltage switchboards.
Air circuit breakers such as the ABB Emax 2 E6.2 protect low-voltage distribution systems against abnormal current conditions while providing reliable switching and isolation. The Ekip Touch LI electronic release monitors circuit current and provides long-time overload and instantaneous short-circuit protection, helping protect cables, busbars, transformers and connected electrical equipment.
The E6.2 platform is designed for high-current switchboards where system availability and substantial fault interruption capability are critical. Its fixed construction, full-size neutral and rear horizontal terminals make the 1SDA071994R1 particularly suitable for integration into main distribution boards, industrial switchgear and infrastructure power systems.
| Series | Emax 2 |
|---|---|
| ABB order code | 1SDA071994R1 |
| EAN | 8015644758448 |
| Product type | Air circuit breaker |
| Frame | E6.2 |
| Performance level | V |
| Rated current | 5000 A |
| Rated operational voltage | 690 V AC |
| Current type | AC |
| Number of poles | 4 |
| Neutral | Full-size, 100% rated |
| Trip unit | Ekip Touch LI |
| Protection functions | L, I |
| Ultimate breaking capacity | 150 kA at 415 V AC |
| Rated impulse withstand voltage | 12 kV |
| Execution | Fixed |
| Terminal arrangement | Rear horizontal |
| Protection rating | IP30 |
| Mechanical durability | 12,000 operating cycles |
| Dimensions (W × H × D) | 1014 × 371 × 270 mm |
The ABB 1SDA071994R1 is an Emax 2 E6.2V/f fixed four-pole air circuit breaker rated at 5000 A and equipped with an Ekip Touch LI electronic trip unit.
The Ekip Touch LI release provides long-time overload (L) and instantaneous short-circuit (I) protection functions for low-voltage distribution systems.
The V-performance E6.2 configuration provides an ultimate short-circuit breaking capacity of up to 150 kA at 415 V AC and 100 kA at 690 V AC.
This model is a fixed air circuit breaker designed for permanent installation within a compatible low-voltage switchboard.
The circuit breaker has four poles with a full-size neutral, making it suitable for four-wire low-voltage distribution systems requiring neutral switching.
ABB Emax 2 air circuit breakers are used in industrial, commercial and infrastructure power distribution systems where dependable high-current switching, advanced electronic circuit protection and high short-circuit interruption performance are required.