1SDA071932R1 ABB E6.2V 6300 Ekip Dip LSI 4p FHR Air Circuit Breaker

1SDA071932R1 ABB E6.2V 6300 Ekip Dip LSI 4p FHR Air Circuit Breaker

ABB 1SDA071932R1 Emax 2 E6.2V 6300 is a 6300 A four-pole fixed air circuit breaker with Ekip Dip LSI electronic protection, up to 150 kA short-circuit breaking capacity and rear flat horizontal terminals for demanding high-current low-voltage power distribution systems.

SKU: 1SDA071932R1MPN: 1SDA071932R1
Price
List Price £62,522.76 ex VAT
Your Price (ex VAT) Save 25%
£46,892.07 25% OFF
You save £15,630.69 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £46,892.07
Trade pricing is personalised to your account

Manufacturer Lead Time

£46,892.07

Why Choose the ABB E6.2V 6300 Ekip Dip LSI 4p FHR Air Circuit Breaker?

The ABB E6.2V 6300 Ekip Dip LSI 4p FHR, order code 1SDA071932R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated current with very high short-circuit performance for major industrial, commercial and infrastructure installations.

This Emax 2 circuit breaker incorporates the Ekip Dip LSI electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The LSI protection functions support selective coordination between upstream and downstream devices, helping isolate electrical faults while maintaining continuity elsewhere in the distribution network.

The E6.2V 6300 is a fixed, four-pole breaker with rear flat horizontal terminals. Rated for operation at up to 690 V AC, it provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC, together with a rated short-time withstand current of 100 kA for both 1 s and 3 s.

Key Advantages

  • High-capacity 6300 A air circuit breaker for major low-voltage power distribution systems.
  • Four-pole configuration for comprehensive switching and isolation.
  • Ekip Dip LSI electronic trip unit provides long-time, short-time and instantaneous protection.
  • Short-time delayed protection supports selective coordination within complex distribution networks.
  • Exceptional 150 kA ultimate short-circuit breaking capacity at 400–440 V AC.
  • 100 kA short-time withstand current for 1 s and 3 s supports demanding high-fault-current installations.
  • Fixed installation for permanent integration into low-voltage switchboards.
  • Rear flat horizontal terminals facilitate connection to high-current busbar systems.

Key Features

  • ABB SACE Emax 2 E6.2V air circuit breaker.
  • 6300 A rated uninterrupted current.
  • Four-pole configuration.
  • Ekip Dip LSI electronic trip unit.
  • Long-time overload (L) protection.
  • Short-time delayed short-circuit (S) protection.
  • Instantaneous short-circuit (I) protection.
  • 690 V AC rated operational voltage.
  • 1000 V AC rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 150 kA ultimate and service short-circuit breaking capacity at 400–440 V AC.
  • 130 kA ultimate short-circuit breaking capacity at 500–525 V AC.
  • 100 kA ultimate and service short-circuit breaking capacity at 690 V AC.
  • 100 kA rated short-time withstand current for 1 s and 3 s.
  • Fixed construction with rear flat horizontal terminals.
  • Four auxiliary change-over contacts with circuit-breaker switched-off indication.

High-Capacity Selective Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E6.2V provide protection, switching and isolation for high-current low-voltage electrical networks. By detecting overload and short-circuit conditions, the breaker can disconnect the affected circuit to help protect cables, switchgear and connected equipment while supporting dependable operation of the wider distribution system.

The Ekip Dip LSI trip unit combines long-time overload, short-time delayed and instantaneous short-circuit protection, making it suitable for installations where selective fault coordination is required. Combined with the E6.2V frame's 6300 A current rating, breaking capacity of up to 150 kA and 100 kA short-time withstand capability, the 1SDA071932R1 is particularly suited to critical high-power distribution applications.

Typical Applications

  • Industrial low-voltage main distribution switchboards.
  • Manufacturing plants and large production facilities.
  • Transformer protection and distribution systems.
  • Generator and critical power distribution systems.
  • Data centres and high-availability infrastructure.
  • Utilities and major infrastructure installations.
  • High-fault-level incoming supply protection.
  • Main and feeder circuits requiring selective short-circuit protection.

Technical Specifications

Series SACE Emax 2
Order code / Product ID 1SDA071932R1
EAN 8015644757823
Product type Air circuit breaker
ABB product group Emax2 Air Circuit Breaker
Frame / subtype E6.2V
Short-circuit performance level V
Rated current 6300 A
Rated uninterrupted current (Iu) 6300 A
Number of poles 4
Neutral pole current 50%
Current type AC
Rated operational voltage (Ue) 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) 150 kA at 400–440 V AC; 130 kA at 500–525 V AC; 100 kA at 690 V AC
Service short-circuit breaking capacity (Ics) 150 kA at 380–440 V AC; 130 kA at 500 V AC; 100 kA at 660–690 V AC
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 100 kA for 1 s; 100 kA for 3 s
Trip unit Ekip Dip LSI
Release type Electronic
Protection functions Long-time (L), short-time (S) and instantaneous (I)
Integrated earth-fault protection No
Overload release current setting from 2520 A
Short-time delayed short-circuit release setting from 3780 A
Instantaneous short-circuit release setting from 9450 A
Installation version Fixed
Terminal configuration Rear flat horizontal
Main circuit connection Bolted
Connecting capacity 6000 mm²
Auxiliary contacts 4 change-over contacts
Degree of protection IP30
Power loss 767 W
Electrical durability 2000 cycles at ≤440 V AC; 2000 cycles at 500–690 V AC
Mechanical durability 12000 cycles
Suitable for IT networks Yes, up to 690 V
Terminal tightening torque 70 N·m
Product dimensions (W × H × D) 888 × 371 × 270 mm
Product net weight 125 kg
Standard IEC 60947-2

Frequently Asked Questions

What is the ABB 1SDA071932R1 used for?

The ABB 1SDA071932R1 is a 6300 A four-pole air circuit breaker used for protection, switching and isolation in high-current, high-fault-level low-voltage power distribution systems.

What protection functions does the Ekip Dip LSI trip unit provide?

The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB E6.2V 6300?

The E6.2V 6300 provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.

Is the 1SDA071932R1 a fixed or withdrawable circuit breaker?

The 1SDA071932R1 is a fixed-version circuit breaker equipped with rear flat horizontal terminals for permanent integration into low-voltage switchboards.

What is the short-time withstand current of the ABB E6.2V 6300?

The breaker has a rated short-time withstand current of 100 kA for both 1 s and 3 s, supporting selective protection in demanding high-fault-current power distribution systems.

Trusted for High-Capacity Power Distribution

ABB SACE Emax 2 air circuit breakers are designed for demanding low-voltage distribution systems where very high current capacity, dependable electronic protection, effective selectivity and exceptional short-circuit performance are required.