ABB 1SDA071932R1 Emax 2 E6.2V 6300 is a 6300 A four-pole fixed air circuit breaker with Ekip Dip LSI electronic protection, up to 150 kA short-circuit breaking capacity and rear flat horizontal terminals for demanding high-current low-voltage power distribution systems.
£46,892.07
The ABB E6.2V 6300 Ekip Dip LSI 4p FHR, order code 1SDA071932R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection, switching and isolation in demanding low-voltage power distribution systems. Part of the ABB SACE Emax 2 series, it combines a substantial 6300 A rated current with very high short-circuit performance for major industrial, commercial and infrastructure installations.
This Emax 2 circuit breaker incorporates the Ekip Dip LSI electronic trip unit, providing long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The LSI protection functions support selective coordination between upstream and downstream devices, helping isolate electrical faults while maintaining continuity elsewhere in the distribution network.
The E6.2V 6300 is a fixed, four-pole breaker with rear flat horizontal terminals. Rated for operation at up to 690 V AC, it provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC, together with a rated short-time withstand current of 100 kA for both 1 s and 3 s.
Air circuit breakers such as the ABB SACE Emax 2 E6.2V provide protection, switching and isolation for high-current low-voltage electrical networks. By detecting overload and short-circuit conditions, the breaker can disconnect the affected circuit to help protect cables, switchgear and connected equipment while supporting dependable operation of the wider distribution system.
The Ekip Dip LSI trip unit combines long-time overload, short-time delayed and instantaneous short-circuit protection, making it suitable for installations where selective fault coordination is required. Combined with the E6.2V frame's 6300 A current rating, breaking capacity of up to 150 kA and 100 kA short-time withstand capability, the 1SDA071932R1 is particularly suited to critical high-power distribution applications.
| Series | SACE Emax 2 |
|---|---|
| Order code / Product ID | 1SDA071932R1 |
| EAN | 8015644757823 |
| Product type | Air circuit breaker |
| ABB product group | Emax2 Air Circuit Breaker |
| Frame / subtype | E6.2V |
| Short-circuit performance level | V |
| Rated current | 6300 A |
| Rated uninterrupted current (Iu) | 6300 A |
| Number of poles | 4 |
| Neutral pole current | 50% |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) | 150 kA at 400–440 V AC; 130 kA at 500–525 V AC; 100 kA at 690 V AC |
| Service short-circuit breaking capacity (Ics) | 150 kA at 380–440 V AC; 130 kA at 500 V AC; 100 kA at 660–690 V AC |
| Ics as percentage of Icu | 100% |
| Rated short-time withstand current (Icw) | 100 kA for 1 s; 100 kA for 3 s |
| Trip unit | Ekip Dip LSI |
| Release type | Electronic |
| Protection functions | Long-time (L), short-time (S) and instantaneous (I) |
| Integrated earth-fault protection | No |
| Overload release current setting | from 2520 A |
| Short-time delayed short-circuit release setting | from 3780 A |
| Instantaneous short-circuit release setting | from 9450 A |
| Installation version | Fixed |
| Terminal configuration | Rear flat horizontal |
| Main circuit connection | Bolted |
| Connecting capacity | 6000 mm² |
| Auxiliary contacts | 4 change-over contacts |
| Degree of protection | IP30 |
| Power loss | 767 W |
| Electrical durability | 2000 cycles at ≤440 V AC; 2000 cycles at 500–690 V AC |
| Mechanical durability | 12000 cycles |
| Suitable for IT networks | Yes, up to 690 V |
| Terminal tightening torque | 70 N·m |
| Product dimensions (W × H × D) | 888 × 371 × 270 mm |
| Product net weight | 125 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071932R1 is a 6300 A four-pole air circuit breaker used for protection, switching and isolation in high-current, high-fault-level low-voltage power distribution systems.
The Ekip Dip LSI electronic trip unit provides long-time overload (L), short-time delayed short-circuit (S) and instantaneous short-circuit (I) protection.
The E6.2V 6300 provides an ultimate short-circuit breaking capacity of 150 kA at 400–440 V AC, 130 kA at 500–525 V AC and 100 kA at 690 V AC.
The 1SDA071932R1 is a fixed-version circuit breaker equipped with rear flat horizontal terminals for permanent integration into low-voltage switchboards.
The breaker has a rated short-time withstand current of 100 kA for both 1 s and 3 s, supporting selective protection in demanding high-fault-current power distribution systems.