1SDA071699R1 ABB E2.2N 2500 Ekip Hi-Touch LSIG 4-Pole Fixed Air Circuit Breaker

1SDA071699R1 ABB E2.2N 2500 Ekip Hi-Touch LSIG 4-Pole Fixed Air Circuit Breaker

ABB 1SDA071699R1 Emax 2 E2.2N 2500 is a 2500 A four-pole fixed air circuit breaker with rear flat horizontal terminals and an Ekip Hi-Touch LSIG solid-state electronic trip unit providing long-time, short-time, instantaneous and ground-fault protection.

SKU: 1SDA071699R1MPN: 1SDA071699R1
Price
List Price £17,482.23 ex VAT
Your Price (ex VAT) Save 25%
£13,111.67 25% OFF
You save £4,370.56 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,111.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,111.67

Why Choose the ABB E2.2N 2500 Ekip Hi-Touch LSIG 4p FHR Air Circuit Breaker?

The ABB E2.2N 2500 Ekip Hi-Touch LSIG 4p FHR, order code 1SDA071699R1, is a high-performance SACE Emax 2 air circuit breaker (ACB) designed for advanced protection and switching in demanding low-voltage power distribution systems. This fixed four-pole E2.2N configuration combines a 2500 A rated current with ABB's Ekip Hi-Touch LSIG solid-state electronic trip unit and rear flat horizontal main terminals.

The Ekip Hi-Touch LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This comprehensive protection arrangement combines overload, selective short-circuit, rapid high-level fault and earth-fault protection within one advanced electronic release, making it particularly suitable for important main and feeder circuits.

The E2.2N performance level provides a short-circuit breaking capacity of 66 kA, while the four-pole fixed configuration is equipped with four auxiliary contacts and circuit-breaker open/closed position indication. The combination of a 2500 A current rating, N-level breaking performance and advanced LSIG protection makes the 1SDA071699R1 a strong choice for main switchboards, transformer secondary systems and critical industrial distribution networks.

Key Advantages

  • 2500 A rated current for substantial low-voltage power-distribution circuits.
  • Four-pole configuration supports three-phase systems incorporating the neutral conductor.
  • Ekip Hi-Touch LSIG electronic trip unit provides comprehensive overload, short-circuit and ground-fault protection.
  • Short-time protection supports selective coordination between upstream and downstream protective devices.
  • Integrated ground-fault protection provides an additional protection function for earth-fault conditions.
  • 66 kA breaking capacity provides substantial short-circuit interruption performance.
  • Hi-Touch architecture supports advanced protection, monitoring and power-management applications.
  • Four auxiliary contacts facilitate breaker status integration with control and monitoring systems.
  • Fixed construction with rear flat horizontal terminals provides practical switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2N frame.
  • 2500 A rated current.
  • Four-pole fixed air circuit breaker.
  • Ekip Hi-Touch LSIG solid-state electronic release.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Integrated ground-fault protection (G).
  • Advanced electronic protection platform for power-distribution applications.
  • 66 kA short-circuit breaking capacity.
  • Rear flat horizontal main terminals.
  • Bolted terminal connection.
  • 70 N·m terminal tightening torque.
  • Four auxiliary contacts fitted.
  • Circuit-breaker open/closed position indication.
  • Suitable for IT networks up to 690 V.
  • Fixed installation for permanent switchboard integration.
  • ABB EcoSolutions-designated product.

Advanced LSIG Protection for 2500 A Distribution Systems

The ABB SACE Emax 2 E2.2N is engineered for important switching and protection duties within high-current low-voltage networks. Its 2500 A current rating and 66 kA breaking performance make this configuration suitable for main distribution points where substantial fault currents, system selectivity and dependable interruption are key design considerations.

The Ekip Hi-Touch LSIG release combines four complementary protection functions. Long-time protection responds to sustained overloads, short-time protection supports selective coordination, instantaneous protection rapidly clears severe short circuits, and ground-fault protection responds to earth-fault conditions. Together, these functions provide comprehensive electronic protection for sophisticated low-voltage distribution systems.

Typical Applications

  • Main low-voltage switchboards and power-distribution assemblies.
  • Industrial main incomer protection.
  • High-current feeder circuits.
  • Transformer secondary distribution systems.
  • Manufacturing and process facilities.
  • Data centres and critical power infrastructure.
  • Large commercial and infrastructure electrical systems.
  • Networks requiring selective short-circuit and integrated ground-fault protection.

Technical Specifications

Series SACE Emax 2
Frame E2.2N
ABB order code 1SDA071699R1
EAN 8015644755492
Product group Emax2 Air Circuit Breaker
Product type Air circuit breaker
Rated current 2500 A
Number of poles 4
Trip unit Ekip Hi-Touch LSIG
Release technology Solid-state electronic
Protection functions Long-time (L), short-time (S), instantaneous (I) and ground-fault (G)
Integrated ground-fault protection Yes
Short-circuit breaking capacity 66 kA
Installation Fixed
Main connection position Rear
Terminal connection type Rear flat horizontal
Terminal type Bolt
Terminal tightening torque 70 N·m
Auxiliary contacts 4
Breaker position indication Open / closed
Suitable for IT networks Yes, up to 690 V
Product weight 53 kg
ABB EcoSolutions Yes
Product classification Air circuit breaker

Frequently Asked Questions

What is the ABB E2.2N 2500 Ekip Hi-Touch LSIG 4p FHR used for?

It is a 2500 A four-pole fixed air circuit breaker designed for advanced switching and protection of high-current low-voltage distribution circuits in industrial, commercial and critical-power installations.

What protection functions does the Ekip Hi-Touch LSIG trip unit provide?

The Ekip Hi-Touch LSIG electronic release provides long-time overload, short-time short-circuit, instantaneous short-circuit and integrated ground-fault protection.

What is the breaking capacity of ABB 1SDA071699R1?

The ABB E2.2N 2500 has a short-circuit breaking capacity of 66 kA, providing substantial fault-interruption capability for demanding low-voltage distribution applications.

What terminal arrangement does ABB 1SDA071699R1 use?

This configuration uses rear flat horizontal bolted terminals, with a specified terminal tightening torque of 70 N·m.

Is ABB 1SDA071699R1 fixed or withdrawable?

This configuration is a fixed four-pole air circuit breaker supplied with four auxiliary contacts and circuit-breaker open/closed position indication for integration into low-voltage switchgear.

Advanced Power Protection from ABB SACE Emax 2

ABB SACE Emax 2 air circuit breakers combine high-current switching capability, selective electronic protection and integrated ground-fault protection to support dependable operation of demanding low-voltage power distribution systems.