Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071664R1 E2.2N 2000 Ekip Touch LI 4p F HR is a 2000 A four-pole fixed SACE Emax 2 air circuit breaker with Ekip Touch LI electronic protection, 66 kA short-circuit breaking capacity and rear horizontal terminals.
£7,790.99
The ABB E2.2N 2000 Ekip Touch LI 4p F HR, order code 1SDA071664R1, is a high-performance four-pole air circuit breaker (ACB) designed for switching and protection in high-current low-voltage electrical distribution systems. Part of the ABB SACE Emax 2 series, it combines a 2000 A rated current with an Ekip Touch LI electronic trip unit for dependable overload and instantaneous short-circuit protection.
The Ekip Touch LI release provides adjustable long-time overload and instantaneous short-circuit protection through an intuitive touch-sensitive interface. The long-time threshold can be adjusted from 0.4–1 × In, while instantaneous protection can be configured from 1.5–15 × In, allowing the breaker to be coordinated with the characteristics of the protected electrical system.
With a rated operational voltage of 690 V AC, four-pole configuration and fixed construction with rear horizontal terminals, the E2.2N 2000 is designed for integration into low-voltage switchboards. Its N performance level provides a rated ultimate short-circuit breaking capacity of 66 kA across key operating voltages from 380–690 V AC, making it a robust solution for industrial and commercial power distribution.
Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage distribution circuits. With its 2000 A current rating and 66 kA short-circuit breaking capacity, the E2.2N 2000 helps protect switchboards, cables, transformers and connected electrical equipment against overloads and severe short-circuit conditions.
The Ekip Touch LI electronic release combines adjustable long-time overload protection with instantaneous short-circuit protection. Its touch-sensitive interface simplifies configuration of protection thresholds, while the fixed four-pole construction and rear horizontal terminals make the breaker particularly suitable for permanent installation in industrial and commercial low-voltage switchgear.
| Series | SACE Emax 2 |
|---|---|
| ABB product group | Emax2 Air Circuit Breaker |
| Frame / type | E2.2N |
| Order code | 1SDA071664R1 |
| Product type | Air circuit breaker |
| Rated current | 2000 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Number of poles | 4 |
| Release | Ekip Touch LI |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Long-time overload protection setting | 0.4–1 × In |
| Instantaneous short-circuit protection setting | 1.5–15 × In |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Short-circuit performance level | N |
| Version | Fixed (F) |
| Terminal connection | Rear horizontal (HR) |
| Reference standard | IEC 60947-2 |
The ABB 1SDA071664R1 is a 2000 A four-pole air circuit breaker used for switching and protecting high-current low-voltage power distribution circuits in industrial, commercial and infrastructure installations.
The circuit breaker has a rated current of 2000 A and is designed for low-voltage systems with a rated operational voltage of up to 690 V AC.
The Ekip Touch LI electronic trip unit provides adjustable long-time overload and instantaneous short-circuit protection, with long-time adjustment from 0.4–1 × In and instantaneous adjustment from 1.5–15 × In.
The E2.2N 2000 provides a rated ultimate short-circuit breaking capacity of 66 kA at 380 V AC, 400–415 V AC, 440 V AC, 500–525 V AC and 690 V AC.
The 1SDA071664R1 is a fixed four-pole air circuit breaker with rear horizontal terminals for permanent installation within a low-voltage switchboard.
ABB SACE Emax 2 air circuit breakers combine robust short-circuit performance, configurable electronic protection and flexible system integration to provide dependable protection for modern high-current low-voltage electrical distribution systems.
We use cookies