1SDA071621R1 ABB E2.2N 1600 Ekip Dip LI 4-Pole Air Circuit Breaker

1SDA071621R1 ABB E2.2N 1600 Ekip Dip LI 4-Pole Air Circuit Breaker

ABB 1SDA071621R1 is a SACE Emax 2 E2.2N 1600 A four-pole fixed air circuit breaker with rear flat horizontal terminals and an Ekip Dip LI solid-state electronic protection release for low-voltage power distribution.

SKU: 1SDA071621R1MPN: 1SDA071621R1
Price
List Price £7,912.81 ex VAT
Your Price (ex VAT) Save 25%
£5,934.61 25% OFF
You save £1,978.20 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,934.61
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,934.61

Why Choose the ABB 1SDA071621R1 E2.2N 1600 Ekip Dip LI Air Circuit Breaker?

The ABB 1SDA071621R1 is a SACE Emax 2 E2.2N air circuit breaker engineered for dependable protection, switching and isolation in low-voltage power distribution systems. Configured as an E2.2N 1600 Ekip Dip LI 4p F HR, it combines a 1600 A rated uninterrupted current, four-pole construction and ABB's Ekip Dip LI solid-state electronic protection release.

The Ekip Dip LI release provides Long-time (L) and Instantaneous (I) protection functions, delivering adjustable overload protection together with rapid response to high-level short-circuit faults. This combination provides straightforward electronic circuit protection for industrial and commercial distribution applications where LI functionality is required.

The 1SDA071621R1 is a fixed four-pole circuit breaker with rear flat horizontal terminals. Rated for operation up to 690 V AC, the E2.2N configuration provides an ultimate short-circuit breaking capacity of 66 kA from 400 to 690 V AC, making it suitable for demanding switchboards and high-current distribution assemblies.

Key Advantages

  • 1600 A SACE Emax 2 air circuit breaker for high-current low-voltage distribution.
  • Four-pole configuration for switching and protecting three-phase systems with neutral.
  • Ekip Dip LI electronic release for adjustable overload and instantaneous short-circuit protection.
  • 66 kA ultimate short-circuit breaking capacity from 400 to 690 V AC.
  • 100% Ics-to-Icu ratio for strong service short-circuit performance.
  • Fixed installation with rear flat horizontal terminals for efficient switchboard integration.

Key Features

  • ABB SACE Emax 2 E2.2 frame.
  • N short-circuit performance level.
  • 1600 A rated uninterrupted current.
  • Four-pole construction with neutral rated at 100% of Iu.
  • Ekip Dip LI solid-state electronic release.
  • Long-time (L) overload protection.
  • Instantaneous (I) short-circuit protection.
  • 66 kA Icu from 400 to 690 V AC.
  • 66 kA Ics from 220 to 690 V AC.
  • 66 kA short-time withstand current for 1 s.
  • Fixed (F) execution.
  • Rear flat horizontal (HR) terminals.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 provide switching, isolation and protection for high-current low-voltage distribution circuits. The electronic trip release monitors circuit current and initiates interruption when configured protection thresholds are exceeded, helping protect cables, switchgear and connected equipment against overload and high-level short-circuit faults.

The Ekip Dip LI release combines adjustable long-time overload protection with instantaneous short-circuit protection in a straightforward solid-state trip unit. Together with the E2.2N frame, 1600 A current rating, four-pole construction, fixed execution and rear horizontal terminals, the 1SDA071621R1 provides a robust solution for industrial and commercial power distribution systems.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Main incoming and outgoing power distribution circuits.
  • Transformer secondary distribution and protection.
  • Industrial plants and manufacturing facilities.
  • Commercial buildings and infrastructure power distribution.
  • Generator and critical power distribution systems.

Technical Specifications

Series SACE Emax 2
Frame / subtype E2.2N
ABB order code 1SDA071621R1
EAN / GTIN 8015644754716
Product type Air circuit breaker
Rated uninterrupted current (Iu) 1600 A
Rated current (In) 1600 A
Number of poles 4
Neutral pole current 100% of Iu
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V AC
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) 66 kA from 400 to 690 V AC
Service short-circuit breaking capacity (Ics) 66 kA from 220 to 690 V AC
Ics as percentage of Icu 100%
Rated short-time withstand current (Icw) 66 kA for 1 s; 50 kA for 3 s
Release Ekip Dip LI
Release type Solid-state electronic, EL type
Protection functions Long-time (L), Instantaneous (I)
Overload release adjustment 640–1600 A
Instantaneous short-circuit adjustment 2400–24000 A
Integrated earth-fault protection No
Installation version Fixed
Terminal connection Rear flat horizontal
Terminal type Bolt
Connecting capacity 1200 mm²
Recommended terminal screw size M12
Tightening torque 70 N·m
Auxiliary contacts 4
Mechanical durability 25,000 cycles
Electrical durability 12,000 cycles at Ue ≤ 440 V; 10,000 cycles at 500–690 V
Power loss 136 W
Suitable for IT networks Yes, up to 690 V
Standard IEC 60947-2
Dimensions (W × H × D) 366 × 371 × 270 mm
Net weight 53 kg

Frequently Asked Questions

What is the ABB 1SDA071621R1?

The ABB 1SDA071621R1 is a SACE Emax 2 E2.2N air circuit breaker rated at 1600 A, with four poles, fixed construction, rear flat horizontal terminals and an Ekip Dip LI solid-state electronic protection release.

What protection functions does the Ekip Dip LI release provide?

The Ekip Dip LI release provides Long-time (L) overload protection and Instantaneous (I) short-circuit protection.

What is the rated current of the ABB 1SDA071621R1?

The circuit breaker has a rated uninterrupted current of 1600 A.

What is the breaking capacity of the ABB 1SDA071621R1?

The E2.2N configuration has an ultimate short-circuit breaking capacity of 66 kA from 400 to 690 V AC and a service short-circuit breaking capacity of 66 kA from 220 to 690 V AC.

Does the ABB 1SDA071621R1 include ground-fault protection?

No. The Ekip Dip LI release provides long-time and instantaneous protection; integrated ground-fault protection is available on suitable LSIG configurations.

Is the ABB 1SDA071621R1 fixed or withdrawable?

The 1SDA071621R1 is a fixed-version Emax 2 air circuit breaker with rear flat horizontal terminals for permanent installation in suitable low-voltage switchgear.

Trusted by Power Distribution Professionals Worldwide

ABB SACE Emax 2 air circuit breakers are engineered for dependable low-voltage power distribution, combining electronic protection, robust switching performance and flexible system integration for industrial, commercial and infrastructure installations.