Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071597R1 Emax 2 E2.2S 1250 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip G Touch LSIG electronic protection and 85 kA breaking capacity at 400–440 V AC for generator and low-voltage power distribution systems.
£9,486.58
The ABB E2.2S 1250 Ekip G Touch LSIG 4p FHR, order code 1SDA071597R1, is a high-performance four-pole air circuit breaker (ACB) designed for generator and demanding low-voltage power distribution applications. Part of the ABB SACE Emax 2 series, it combines a 1250 A rated current, high short-circuit breaking performance and the generator-focused Ekip G Touch LSIG electronic trip unit.
The Ekip G Touch LSIG electronic release provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection. The Ekip G Touch platform is designed to extend conventional distribution protection with functions suited to generator applications, while its touchscreen interface provides intuitive access to protection settings and electrical information.
With a rated operational voltage of up to 690 V AC and an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC, the 1SDA071597R1 provides robust fault interruption for substantial electrical systems. Its four-pole fixed construction with rear flat horizontal terminals enables permanent integration into generator switchboards, main distribution panels and busbar assemblies.
Air circuit breakers used in generator and main distribution applications must provide reliable switching and fault interruption while supporting appropriate coordination throughout the electrical system. The ABB SACE Emax 2 platform combines high short-circuit performance with electronic protection technology for demanding low-voltage installations.
The Ekip G Touch LSIG release combines long-time overload, short-time selective, instantaneous short-circuit and earth-fault protection with a generator-oriented protection platform. This makes the 1SDA071597R1 particularly suitable for installations where generator protection, selective fault clearing and dependable distribution protection are required within the same electrical system.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2S |
| ABB order code | 1SDA071597R1 |
| EAN | 8015644754471 |
| Product type | Air circuit breaker |
| Rated current | 1250 A |
| Number of poles | 4 |
| Trip unit | Ekip G Touch LSIG electronic release |
| Release type | Solid-state electronic |
| Protection functions | L (long-time overload), S (short-time short circuit), I (instantaneous short circuit) and G (earth fault) |
| Rated operational voltage | up to 690 V AC |
| Ultimate breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 500–690 V AC | 66 kA |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Dimensions (W × H × D) | 366 × 371 × 270 mm |
| Net weight | 53 kg |
| Country of origin | Italy |
| Standard | IEC 60947-2 |
The ABB 1SDA071597R1 is a four-pole air circuit breaker designed for generator and low-voltage power distribution applications requiring high short-circuit performance and comprehensive electronic protection.
The ABB E2.2S 1250 has a rated current of 1250 A, making it suitable for substantial generator and low-voltage distribution circuits.
The Ekip G Touch LSIG electronic trip unit provides long-time overload, short-time selective short-circuit, instantaneous short-circuit and earth-fault protection, together with a protection platform designed for generator applications.
The E2.2S has an ultimate short-circuit breaking capacity of 85 kA at 400–440 V AC and 66 kA at 500–690 V AC, providing robust fault-current interruption for demanding electrical systems.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible generator panels, low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection with robust short-circuit performance and flexible system integration, providing dependable protection for generator and demanding low-voltage power distribution applications.
We use cookies