ABB 1SDA071541R1 Emax 2 E2.2H 800 A four-pole fixed air circuit breaker with rear flat horizontal terminals, Ekip Dip LI electronic protection and 100 kA breaking capacity at 400–440 V AC for demanding low-voltage power distribution systems.
£6,256.19
The ABB E2.2H 800 Ekip Dip LI 4p FHR, order code 1SDA071541R1, is a high-performance four-pole air circuit breaker (ACB) designed for protection and switching in demanding low-voltage power distribution systems. As part of the ABB SACE Emax 2 series, it combines an 800 A rated current with high short-circuit breaking performance and reliable electronic protection for industrial, commercial and infrastructure installations.
This fixed circuit breaker is equipped with the Ekip Dip LI electronic trip unit, providing long-time overload and instantaneous short-circuit protection. The electronic release offers straightforward protection configuration while the E2.2H platform provides high fault-current interruption capability, making it suitable for installations where robust protection and dependable continuity of service are important.
With a rated operational voltage of up to 690 V AC, four-pole construction and an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC, the 1SDA071541R1 is engineered for demanding low-voltage distribution duties. Its fixed configuration uses rear flat horizontal terminals for efficient connection to switchboard busbar systems.
Air circuit breakers such as the ABB SACE Emax 2 provide essential switching and fault protection for high-current low-voltage electrical systems. By interrupting the circuit when configured protection thresholds are exceeded, the breaker helps protect cables, busbars, switchgear and connected equipment against potentially damaging overload and short-circuit conditions.
The Ekip Dip LI electronic trip unit combines long-time overload and instantaneous short-circuit protection in a straightforward protection platform. Together with the E2.2H breaker’s 100 kA breaking capacity at 400–440 V AC, this makes the 1SDA071541R1 particularly suitable for installations requiring high fault-current interruption capability and dependable power distribution protection.
| Product group | Emax2 Air Circuit Breaker |
|---|---|
| Series | SACE Emax 2 E2.2H |
| ABB order code | 1SDA071541R1 |
| EAN | 8015644753917 |
| Product type | Air circuit breaker |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Number of poles | 4 |
| Neutral pole current | 100% |
| Trip unit | Ekip Dip LI electronic release |
| Protection functions | L (overload) and I (instantaneous short circuit) |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate breaking capacity (Icu) at 400 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 415 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 440 V AC | 100 kA |
| Ultimate breaking capacity (Icu) at 500 / 525 V AC | 85 kA |
| Ultimate breaking capacity (Icu) at 690 V AC | 85 kA |
| Service breaking capacity (Ics) | 100% of Icu |
| Rated short-time withstand current (Icw) | 85 kA for 1 s; 66 kA for 3 s |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Main circuit connection | Bolt connection |
| Connecting capacity | 600 mm² |
| Terminal tightening torque | 70 N·m |
| Auxiliary contacts | 4 change-over contacts |
| Protection rating | IP30 |
| Power loss | 34 W |
| Electrical durability | 15,000 operating cycles |
| Mechanical durability | 25,000 operating cycles |
| Standard | IEC 60947-2 |
The ABB 1SDA071541R1 is a four-pole air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems where high short-circuit breaking capacity is required.
This Emax 2 air circuit breaker has a rated uninterrupted current of 800 A.
The Ekip Dip LI electronic trip unit provides long-time overload and instantaneous short-circuit protection for low-voltage electrical distribution systems.
The E2.2H has an ultimate short-circuit breaking capacity of 100 kA at 400–440 V AC and 85 kA at 500–690 V AC, with a service breaking capacity equal to 100% of Icu.
The FHR configuration identifies this Emax 2 breaker as a fixed version with rear flat horizontal terminals, designed for permanent integration into compatible low-voltage switchboards and busbar systems.
ABB SACE Emax 2 air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining advanced electronic trip technology with high short-circuit breaking performance.
We use cookies