Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA071535R1 is a SACE Emax 2 E2.2S 800 A fixed four-pole air circuit breaker with rear horizontal terminals, an Ekip Touch LSI electronic trip unit, 690 V AC rated operational voltage, 85 kA breaking capacity at 380–440 V AC and 66 kA short-time withstand current for 1 s.
£6,314.65
The ABB 1SDA071535R1 is a high-performance SACE Emax 2 E2.2S air circuit breaker (ACB) designed for advanced protection and control of demanding low-voltage electrical distribution systems. Rated at 800 A, this fixed four-pole circuit breaker combines ABB’s E2.2S frame with the Ekip Touch LSI solid-state electronic trip unit for configurable long-time overload, short-time delayed and instantaneous short-circuit protection.
As part of the ABB SACE Emax 2 series, the E2.2S combines high short-circuit performance with sophisticated electronic protection and an intuitive touchscreen interface. The Ekip Touch LSI release adds selective short-time protection to the standard long-time and instantaneous functions, making this configuration particularly suitable for installations where protection coordination and selectivity between upstream and downstream devices are important.
With a rated uninterrupted current of 800 A, rated operational voltage of 690 V AC, rated ultimate short-circuit breaking capacity of 85 kA at 380–440 V AC and rated short-time withstand current of 66 kA for 1 s, the 1SDA071535R1 provides substantial fault-handling capability. This version features a fixed four-pole configuration with rear horizontal terminals, making it well suited to high-performance switchboards with rear busbar connections.
Air circuit breakers such as the ABB SACE Emax 2 E2.2S protect important low-voltage distribution circuits against damaging overload and short-circuit conditions. The 1SDA071535R1 combines an 800 A continuous-current rating with 85 kA ultimate short-circuit breaking capability at 380–440 V AC and 66 kA short-time withstand capability for 1 s, providing the performance required for demanding main and distribution circuits.
The Ekip Touch LSI trip unit adds selective short-time delayed protection to long-time overload and instantaneous short-circuit functions. This allows more sophisticated coordination with downstream protective devices, while the touchscreen interface provides convenient access to protection settings and operating information. Combined with rear horizontal terminals, the breaker is well suited to switchboards requiring both high fault capability and practical rear busbar connectivity.
| Series | SACE Emax 2 |
|---|---|
| Frame / sub-type | E2.2S |
| Order code / MPN | 1SDA071535R1 |
| EAN / GTIN | 8015644753856 |
| Product type | Air circuit breaker |
| Short-circuit performance level | S |
| Rated current (In) | 800 A |
| Rated uninterrupted current (Iu) | 800 A |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V AC |
| Frequency | 50 / 60 Hz |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400–415 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–525 V AC | 66 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 66 kA |
| Rated short-time withstand current (Icw) for 1 s | 66 kA |
| Number of poles | 4 |
| Trip unit | Ekip Touch LSI |
| Release type | Solid-state electronic |
| Protection functions | LSI |
| Overload protection adjustment | 0.4–1 × In |
| Overload protection adjustment range | 320–800 A |
| Short-time protection adjustment | 0.6–10 × In |
| Short-time protection adjustment range | 480–8000 A |
| Instantaneous protection adjustment | 1.5–15 × In |
| Instantaneous protection adjustment range | 1200–12,000 A |
| Long-time overload protection | Yes |
| Short-time delayed short-circuit protection | Yes |
| Instantaneous short-circuit protection | Yes |
| Integrated ground-fault protection | No |
| User interface | Touch-sensitive display |
| Current type | AC |
| Installation version | Fixed |
| Terminal configuration | Rear horizontal |
| Main circuit connection | Bolted connection |
| Auxiliary contacts | 4 |
| Circuit-breaker position indication | Open / closed |
| Product net weight | 53 kg |
| Standard | IEC 60947-2 |
The ABB 1SDA071535R1 is an 800 A Emax 2 air circuit breaker designed to protect and control demanding low-voltage electrical distribution circuits in industrial, commercial and infrastructure switchboards.
The ABB 1SDA071535R1 has a rated uninterrupted current of 800 A and a rated operational voltage of 690 V AC.
The E2.2S 800 provides a rated ultimate short-circuit breaking capacity of 85 kA at 380–440 V AC and 66 kA at 500–690 V AC, with a rated short-time withstand current of 66 kA for 1 s.
The Ekip Touch LSI solid-state electronic trip unit provides configurable long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated ground-fault protection.
The 1SDA071535R1 is a fixed four-pole air circuit breaker with rear horizontal terminals, providing a practical connection arrangement for busbars within low-voltage switchboard assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection, high short-circuit performance, selective protection capability and flexible installation configurations for dependable operation in modern industrial, commercial and critical-power low-voltage distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.